background image

 

2305

 

2

 

GB

4

 

2.

TECHNICAL DATA

 

2.1

TECHNICAL DATA

2.2

OVERALL DIMENSIONS

2.3

WORKING FIELD  

 

(as EN 267)

TYPE

366 T1

 

Output  - Thermal power

1.2 / 1.45

 

 

5 kg/h

-

14 / 17

 

 

60 kW

Fuel

Light oil, viscosity  4 –

 

 

 

6 mm

 

2

 

/s at  20 °C

Electrical supply

Single phase,

230 V 

 

±

 

 10% 

 

~

 

 50Hz

Motor

Run current

0.85 A

2750 rpm

289 rad/s

Capacitor

 

µ

 

F

Ignition transformer

Secondary

8 kV

16 mA

Pump

Pressure:

8

 

 

15 bar

Absorbed electrical power

0.29 kW

196

111

122

180

130

150

4

22

210

254

11

72

72

91

45°

45°

D5699

112

ø

 

84

1

2

3

Light oil output – kg/h

15

20

30

40

Thermal power –  kW

0.8

0.6

0.4

0.2

0

Pressure in comb

ustion

c

hamber – mbar

D5354

4

50

1.0

5

60

Summary of Contents for 366 T1

Page 1: ...iks en onderhoudsvoorschriften Montage und Bedienungsanleitung 2902305 5 l Gebl sebrenner Br leur fioul Oil burner Stookoliebrander CODE MODELL MODELE MODEL TYP TYPE 3736650 RG1RKD 366 T1 D F GB NL Zw...

Page 2: ...Combustion adjustment 6 4 2 Electrodes adjustment 7 4 3 Pump pressure and air output 8 4 4 Fuel heating 9 4 5 Burner start up cycle 9 5 MAINTENANCE 9 6 FAULTS SOLUTIONS 10 1 Pump with pressure reduce...

Page 3: ...Electrical supply Single phase 230V 10 50Hz Motor Run current 0 85A 2750 rpm 289 rad s Capacitor 4 F Ignition transformer Secondary 8 kV 16 mA Pump Pressure 8 15 bar Absorbed electrical power 0 29 kW...

Page 4: ...using screws 2 and if necessary the nuts 3 interposing the insulating gasket 5 see fig 2 3 2 FUEL SUPPLY The burner is designed to allow entry of the oil supply pipes on either side Depending on the...

Page 5: ...over the fuel level a non return valve is required This solution however is less safe than previous one due to the possibility of leakage of the valve 8 H meters L meters i 8 mm i 10 mm 0 5 1 1 5 2 1...

Page 6: ...sembly of the control box retighten the screw A with a torque wrench setting of 1 1 2 Nm S7186 Fig 10 A 7 pin plug 7 pole socket h L1 B4 S3 T2 T1 N Black White Blue Capacitor Burner earth Switch with...

Page 7: ...tput Comb head adjustment Air damper adjustment bar kg h 4 1st stage 2nd stage GPH Angle 1st stage 2nd stage 1st stage 2nd stage Set point Set point Set point 0 40 80 9 14 1 3 1 7 0 3 0 0 6 0 50 60 80...

Page 8: ...ise the setting screw 7 until the set point marked on the regulating rod 8 is level with the outside plane of the nozzle holder assembly 1 In the sketch the combustion head is set for an output of 0 8...

Page 9: ...pressure gauge must be mounted in place of cap 8 see fig 15 2nd STAGE ADJUSTMENT ADJUSTMENT OF AIR SHUTTER Unloosen the nut 4 turn the screw 5 until the indicator 6 reaches the position desired Then...

Page 10: ...r control always first switch off the electrical supply to the bur ner acting on the main switch of the system THE BASIC CHECKS ARE Check that there are not obstructions or dents in the supply or retu...

Page 11: ...of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner will not start when the ad justment thermo stat closes Lack of electrical supply Check presence of voltage in the L1 N clamps of the...

Reviews: