RICHARD LE DROFF 1000 Horizon FV Instructions For Installation And Use Manual Download Page 10

4.8.  PREPARING OF THE FIREBOX (FIG. 48)

A personalised fireplace must: 
- be made of M0 (non-combustible) class materials.
- provide for a free cross section of at least 600 cm

2

in its lower part to enable

the free circulation of the air.

4.9.  HOOD (FIG. 4.6 REP. 2)

We recommend the use of M0 (non-combustible) class materials as well
as the placing of insulation.
The design of a personalised hood must:
- allow free access to the inside or include a trap door,
- be independent of the fire, which must not be serve to support the hood.

The appliance must be able to dilate freely.

- for appliances with side opening doors, the brick fascia or hood will be

placed at least 1 cm forward of the front of the fire so that the air can
circulate.

- for appliance with lift-up doors, the brick fascia or hood will be placed at

least 3 cm forward of the front of the fire so that the air can circulate.

The hood must include the following elements (fig. 4.6):

4.9.1.  False ceiling (rep. 9)

The hood must have a false ceiling fixed at least 30 cm below the ceiling
of the room.
This false ceiling channels the warm air towards the outside, avoids it being
confined to the upper part of the hood and protects the ceiling of the room.
Make the false ceiling using class M0 (non-combustible) materials and then
insulate it. The chamber thus formed must:
- include effective ventilation openings, communicating with the outside of

the hood.

- be airtight as regards the

lower part of the hood in
order to avoid warm air
escaping upwards.

Insulate the side resting

against the wall, the pipe
and the ceiling.

4.9.2.  Warm air distri-
bution (rep. 10)

The hood must include, in its
upper part, close to the
ceiling, one or more outlets
for the distribution of warm
air with a total, non-closable
cross section of 600 cm².

4.9.3.  Inspection door 

The connecting pipes to the
chimney must be visible
along all their length, either
directly, or by an inspection
door or by means of a grille
fitted into the hood. If required
for sweeping, the connecting
pipes must be accessible
(French regulations DTU 24.2).

4.10.  PROTECTION OF THE BEAM

No part of the wooden beam (C) must be subject to heat coming in parti-
cular from the smoke collector, the pipe or rising air (window convection).
An installation must be made (cf. fig. 4.11) using an insulating material (A),
rock wool, and our standard protection kit (D) available from your dealer.
(E) brick fascia, (B) hood.

W

W

ARNING

ARNING

In order to allow the fire to dilate, none of its parts must be in contact
with the fireplace.
A clearance of 5 mm must be allowed, in particular between the
jambs of the fireplace and the body of the fire (fig. 6.1).

7cm

A

B

C

D

E

F

G

1

cm

GB 10/12

39417-05-16

4.1

4.1

1

1

A rock wool
B hood
C beam
D protection kit
E non-combustible pediment
F smoke collector compartment
G rock wool

Ø 180

170

175

Ø 180

Ø 150

220

150

550

80

Ø 75

490

1000

1000

170

500

105

105

490

135

Ø 75

300

770

310

830

4.10

Summary of Contents for 1000 Horizon FV

Page 1: ...TION AND USE 05 16 39417 FIREBOX INSERT 1000 HORIZON FV 1 TECHNICAL CHARACTERISTICS 3 2 CONNECTION POSSIBILITIES 4 3 INSERT INSTALLATION 5 4 FIREBOX INSTALLATION 7 5 USE 10 6 MAINTENANCE 12 7 WARRANTY...

Page 2: ...safe place The manufacturer s liability is limited to the supply of the appliance It may not be held liable in the event of any failure to respect these instructions The following are especially prohi...

Page 3: ...distributor outlet diameter 150 mm External air inlet diameter 75 mm Minimal dimensions of chimney block 20 x20 cm Min of tubing or insulated metal box 150 mm Min height above firebox 4 m DRAUGHT 10 P...

Page 4: ...DTU 24 1 Warm air is blown in front of the appliance Warm air distribution is possible with nozzles 125 or 150 option In this case the warm air blows out only over the firebox Fig 2 2 Combustion air...

Page 5: ...ing is optimal with an approximately 40 m3 hour of fresh air consumption A system of ventilation french VMC a centralized ventilation system a n extractor hood can perturb the functioning of the fireb...

Page 6: ...5 Lock the baffle in the firebox on the brackets 3 7 CONNECTION TO THE SMOKE FLUE Remove the smoke baffle 3 6 Connect the nozzle to the flue 3 3 from inside the firebox Lock the baffle into the firebo...

Page 7: ...mbustion air supply connected outside A direct supply of air combustion in the room is possible respect the following recommendations 4 1 6 1 Combustion air not connected If no outside nozzle connecti...

Page 8: ...s 4 6 1 2 3 5 6 7 8 9 10 FOYER 4 13 14 11 12 15 16 17 18 19 FIREBOX MONTAGE 1 Supporting wall class M0 materials 2 Decorative hood material according to model 3 Air access 4 Air access through firepla...

Page 9: ...ahead of the firebox to the room fig 4 6 Rep 17 4 7 WARM AIR DISTRIBUTION Connect the warm air nozzless option available sp cific documentation Switch the warm air direction valve to direct warm air...

Page 10: ...openings communicating with the outside of the hood be airtight as regards the lower part of the hood in order to avoid warm air escaping upwards Insulate the side resting against the wall the pipe a...

Page 11: ...onal Start with a small fire then in stages increase the load The progressive rise in the temperature allows the materials to dilate slowly and stabilise Smoke and a smell will be given off at first d...

Page 12: ...l operation When operating at reduced speed the clean glass system is less efficient 6 4 OBLIGATORY CHIMNEY SWEEPING The law in France requires that the chimney be swept twice a year including once du...

Reviews: