RHINO PSS24-035 Installation Instructions Download Page 1

RHINO 

Installation Instructions for PSS24-035 Power Supply

READ INSTRUCTIONS BEFORE INSTALLING OR OPERATING THIS DEVICE. KEEP FOR FUTURE REFERENCE

.

1. Safety instructions

•   To ensure sufficient convection cooling, always maintain a safety distance of 

20 mm [.79in] from all  

ventilated surfaces while the device is in operation.

•   The device is not recommended to be placed on low thermal conductive surface, for example, plastics.
•    Note that the enclosure of the device can become very hot depending on the ambient temperature and load 

of the power supply. Do not touch the device while it is in operation or immediately after power is turned OFF. 
Risk of burning.

•   Do not touch the terminals while power is being supplied. Risk of electric shock.
•   Prevent any foreign material, particles or conductors from entering the device through the openings during 

installation. It can cause electric shock, safety hazard, fire, and/or product failure.

•   Warning: When connecting the device, secure GND connection before connecting L and N. When  

disconnecting the device, remove the L and N connections before removing the GND connection.

2. Device description (Fig. 1)

(1) Input & Output terminal block connector
(2) DC voltage adjustment potentiometer
(3) DC OK control LED (green)

3. Installation of the Device (Fig. 2)

A.  Mounting holes for power supply assembly onto the mounting surface. Power supply shall be mounted on 

minimum 2 mounting holes using M3 x 0.5 screw minimum 5 mm (0.19in) length.  

  

B.  This surface belongs to customer’s system or panel where the power supply is mounted.
C. Connector. 

Use flexible (stranded wire) or solid wire 0.32-3.3 mm

²

 (AWG 22-12). The torque at the connector shall not 

exceed 1.3 Nm (11.3 in-lb). The insulation stripping length should not exceed 0.28 in or 7 mm.  
AutomationDirect P/N BM-00120 lug or equivalent recommended for stranded wire. Refer to figure 3. 

4. Installation of Mounting Accessories (Fig. 4)

•   Only use M3 screw 

6 mm through the base mounting holes. This is to keep a safety distance between the 

screw and internal compontents. 

•   Recommended mounting tightening torque: 0.4 to 0.8 Nm (3.5 to 7 in-lb).

FOR TECHNICAL ASSISTANCE CALL 770-844-4200

1

2

3

Ventilated surface

Side surface

Top surface

Base surface

Figure 1 - Device Descriptions

Side Mounting (Vertical)

C

A

B

Figure 2 - Mounting

C

A

Side Mounting (Horizontal)

B

Base Mounting 

(Vertical)

C

A

B

Lug

Stripped wire

7mm

[0.28in]

Figure 3 - Wire Type

AutomationDirect P/N 

BM-00120 can be used.

Mounting

accessories

Chassis of

the device

Mounting 

screw

6mm max.

Figure 4 - Mounting Screw