Rheem SMUL 12 Installation Instruction Download Page 6

P. 08

P. 05

 

LIQUID PIPE AND DRAIN PIPE              

 
 

 *   Drain pipe should be above ground 
     and the end off the pipe does not dip  
     into water all pipes must be restrained 
     wall by saddled. 
 
IF THE OUTDOORS UNIT IS INSTALLED 
LOWER THAN INDOOR UNIT 
 *  Taping method ,taping from lower part  
    to upper 
 *   All pipes are bound together by tape 
     and restrained to the wall by saddles. 
 
IF THE OUTDOORS UNIT IS INSTALLED 
HIGHER THAN INDOOR UNIT 
 *  Taping  should done from lower to upper part. 
 *  All pipes are bound and taped together and trapped 
    the pipes to prevent water returning to the room. 
    (see picture) 
 *  Restrain all pipes to the wall with saddles. 
 
            

 
 
 
 
 

REFRIGERANT PIPING WORK 

  

1. Selection of copper pipe for gas pipe and liquid pipe as informed in specific table(see pipe table)  
2. For dust moisture protection , before assembly the pipe and its insulation, both end of the pipe 
   must be coverage. 
3. Avoid pipe bending as mush as possible. If it is necessary, the bending radius must be more 
   than 3  or  4  cm. 

Gas pipe and liquid pipe insulation depending upon copper pipe size and the insulation thickness=3/8’’ 

 

    

 
 
 
 
 
 
                                                                          

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

 

 

 

 

 
 
 
 

4. the connection indoor unit and outdoor unit.     

 

Unscrew flare nut for releasing pressure gas in indoor unit .If there is no high-pressure                    
gas blowing  out, it is the signal of leaking indoor unit. 

 

Fit flare nut with liquid pipe. Flaring the pipe ‘s end with fare tool. 

Connecting Wire

Liquid Pipe
Heat  pump only

Piping tape

Drain pipe 1/2"

Gas pipe

 

PIPE LIMITATION AMD RECOMENATION FOR CHARGING R-22 

 

BTU/HR 

PIPNG BETWEEN INDOOR & OUTDOOR UNIT  PIP SIZE OD.  EXTRA CHARGING R-22 

    

HEIGHT DIFFERENT 

PIPNG 

( INCH.) 

FOR PIPE LENGTH 

    

H(CON.ABOVE  H(CON.UNDER 

LENGTH 

  

  

MORE THAN 5 M 

  

 

FANCOIL) 

FANCOIL)  (ONE 

WAY)  LIQUID  GAS 

(GRAM/M) 

  10,000-12,000 

15 M. 

10 M. 

20 M. 

1/4 

1/2 

30 

  16,000-33,000 

20 M. 

15 M. 

30 M. 

3/8 

5/8 

60 

  36,000-48,000 

25 M. 

20 M. 

35 M. 

3/8 

3/4 

70 

    

25 M. 

20 M. 

55 M. 

3/8 

7/8 

80 

  56,000-60,000 

25 M. 

20 M. 

35 M. 

1/2 

3/4 

120 

    

25 M. 

20 M. 

50 M. 

1/2 

7/8 

120 

    

25 M. 

20 M. 

60 M. 

1/2  1-1/8 

120 

Reviews: