background image

Humidification System 

 

11 

69-2307—01

M24766

Position template sticker on remote location.

Note:

 The humidifier will weigh 12–15 lbs. (+/- 2 lbs.) 

with water, so if mounting onto drywall or plaster, 

position one side over a wall stud.

3

4

Insert wall anchors (4) into pilot holes and secure 

bracket to location.

M24767A

Push down to secure the humidifier 

to bracket arms.

5

M24768

RemoTe mounT InsTallaTIon

RemoTe mounT InsTallaTIon

Summary of Contents for RXIH-AS06A

Page 1: ...Steam Humidifier As Easy as 1 2 3 4 PROFESSIONAL INSTALLATION GUIDE See inside for detailed instruction and remote mounting options 1 Mount 2 Hang 3 Plumb 4 Wire 69 2307 01...

Page 2: ...ud com or call 479 648 4900 Installation Recommendations 1 List of tools supplies 2 Safety Precautions 3 Duct Mount Instructions Installation 4 Remote Mount Instructions Installation 6 Plumbing and Wi...

Page 3: ...and back flow prevention valve Check that the main water supply line is open Ensure there are no water leaks drips at any of the water connections Plug into a circuit with at least enough capacity to...

Page 4: ...n the home depending on the amount of supplied ventilation If the remote hose is used there may be a slight rubber odor These odors will dissipate within days of installation If the homeowner sees the...

Page 5: ...tic water line 1 2 in drain hose and clamps Mounting bracket and hardware In line water filter 50028044 001 Saddle valve Back flow valve 50030142 001 Options Remote Installation Kits 10 foot hose and...

Page 6: ...humidifier s weight when it is full of water approximately 12 to 15 lbs and to hold the humidifier in a level position for safe reliable operation Otherwise additional duct or wall reinforcement will...

Page 7: ...H AS09A 10 Amps RXIH AS12A 12 Amps M24745 Install duct nozzle 2 M24746 Ensure o ring gasket is properly seated in the groove M24894 Insert nozzle and twist clock wise to ensure tight seal of nozzle to...

Page 8: ...eal in duct hole Secure bracket to duct using 8 self drilling sheet metal screws 4 M24749 5 6 Proceed to page 14 for plumbing and wiring instructions M24750 A B Foam gasket M24748 SUPPLY 12 INCHES 4 D...

Page 9: ...pported to prevent sagging or low spots 1 Choose a location for the humidifier and the remote duct nozzle see remote installs on page 8 It should have access for Remote hose installation Steam hose mu...

Page 10: ...ted in a conditioned space running a remote hose to the duct M24786 Living Area Remote Options M24781 Furnace or Mechanical Room Remote M24785 Garage Remote M24936 Duct Mount Remote Proper Hose Instal...

Page 11: ...SLOPE TYPICAL INSTALLATION WHEN HUMIDIFIER IS ABOVE REMOTE NOZZLE KINKED SAG NO SLOPE NO SLOPE M29028 UNDRAINED ELBOW NOTES Minimum upward slope of hose in direction of steam flow at 2 in per foot Min...

Page 12: ...Mount Kit sold separately Hose Adapter Duct Nozzle Hose Clamps Remote Hose M24894 Insert hose adapter and twist clockwise to ensure tight seal of nozzle to the humidifier Ensure o ring gasket is prope...

Page 13: ...he humidifier will weigh 12 15 lbs 2 lbs with water so if mounting onto drywall or plaster position one side over a wall stud 3 4 Insert wall anchors 4 into pilot holes and secure bracket to location...

Page 14: ...angle iron with the appropriate slope Then attach the hose to the top of this support If remote hose requires downward pitch refer to pages 7 and 9 for instruction M24771 Run remote hose from the hum...

Page 15: ...01 Remote mount installation To install clamps onto the insulated steam hose Cut a slit in the insulation half way around the house Do not cut into the steam hose Insert the hose clamp into the slit a...

Page 16: ...downslope To water supply Manual shutoff valve sold separately Draining water may be hot Ensure drain outlet not exposed Ensure drain or condensate pump is rated for at least 120 F water CAUTION Hot w...

Page 17: ...y switched to call for fan GT GT connects to thermostat G terminal GF connects to fan board G terminal Thermostat G passes through the normally closed NC relay contacts to GF allowing fan activation W...

Page 18: ...auto operation also wire W and G to thermostat W and G B HVAC DIGITAL HUMIDISTAT THERMOSTAT HUM HUM R C G Y W R Rc G Y W R C 24V 24V HUM HUM C GT R RT GF EXT RECOMMENDED AIR FLOW SWITCH AFS M29030 HV...

Page 19: ...LL SERVICE PRESS RESET PRESS EMPTY RESET EMPTY SEE LABEL BELOW M24763 M24762 Confirm that the furnace blower turns on to circulate air This will take about 10 15 minutes upon call for humidity 16 Impo...

Page 20: ...nd remains empty until next call for humidity 1 year of total time operational and inactive before the Press Empty light will blink indicating it is time to manually clean the water tank 30 hrs of hum...

Page 21: ...ttach cover and plug the humidifier in If fault reappears follow the cleaning steps on pages 23 25 Reassemble tank and press the RESET button If fault returns replace with applicable wattage heating e...

Page 22: ...w is present follow the cleaning steps on pages 23 25 Press EMPTY button to drain tank Set humidistat RH setpoint to Test mode If fault returns unplug the humidifier Loosen cover screw and remove cove...

Page 23: ...IFYING light turning on Allow unit to run and check for steam leaks around tank and ventilation holes If steam is present replace the humidifier 13 Tank failed to drain No Water in tank may be hot 140...

Page 24: ...e tank with water in it Flush cycle takes approximately 15 minutes to empty the tank completely To override press hold the EMPTY button while the Clean Tank light is blinking Drain Hose Operating Temp...

Page 25: ...ight to be on solid not blinking The flush cycle takes approximately 15 minutes to empty the tank completely To override the flush cycle press hold the EMPTY button a second time for 3 seconds The tan...

Page 26: ...ard to release the tank Note Latch does not come off humidifier with tank M24777 M24778 M24779 5 Use tap water to flush loose minerals from the tank Sediment screen at tank s bottom is removable For a...

Page 27: ...til humidity is needed again This prevents water from stagnating within the tank The tank will refill with water upon next humidity call There are a few house cleaning steps to follow to keep your hum...

Page 28: ...efer to installation instructions packaged with each model as well as complying with all Federal State Provincial and Local codes Part Part Number Fig Reference 10 foot Remote Hose and Nozzle Kit 5002...

Reviews: