background image

TECHNICAL SERVICE DEPARTMENT 

Technical Service Bulletin 

1-800-432-8373 

 

AdvantagePlus Troubleshooting 

 
When first diagnosing an AdvantagePlus, check the following: 
 

 

If the unit is not operating, is the power on?  

 

Is the unit gas valve turned on?  

 

Is the unit thermostat temperature setting high enough to call for heat?  

 

What is the temperature of the water in the tank?   

 

Is there "LOC" in the LED panel window? (Press red reset button on front panel. Allow retrying for 
ignition. Then diagnose based on the table below.) 

 

LINE LED is off; does not have 120VAC 

 
Explanation: This LED monitors incoming AC line voltage. The LED is ON when 120VAC line voltage is present 
on the control board. If the wall plug is properly wired, you will see a green LED light on the bottom left hand 

corner of the control board.  

 
 
 
 

At a minimum, check the following: 

1.

 

Plug in unit; check circuit breaker 

2.

 

Polarity is correct or ground is missing on wall plug 

3.

 

Re-seat CN1 Molex plug on control board  

4.

 

Verify display ribbon cable is connected to main 
board and display board 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Is there 120VAC at the 
black and white wires to 
connector 1 (CN1)? 

Yes 

No

Verify power at wall plug or line connection 

1.

 

Verify power connection in box on heater. 

2.

 

Check and remove wall plug. Ensure the black lead is to 
the brass screw; the white lead is to the silver screw; and 
there is a ground wire present. 

Continue to next step 

Summary of Contents for RUUD AdvantagePlus

Page 1: ...AC line voltage The LED is ON when 120VAC line voltage is present on the control board If the wall plug is properly wired you will see a green LED light on the bottom left hand corner of the control...

Page 2: ...e power Is the green LED on the bottom left side of the control board lit up Yes No Replace control board Remove and check wall plug Ensure the black lead is to the brass screw the white lead is to th...

Page 3: ...power to the water heater If the blower does not come on go to step 1 if the blower is does come on go to step 2 Unit appears to be fine Recycle power and try again Is there 24 VAC from the transforme...

Page 4: ...ton on the display Yes No Unit appears to be fine Recycle power ECO will trip at 2000 F and automatically reset when the water cools to 1600 F Measure the water temperature from the T P valve If the w...

Page 5: ...If you has continuity then follow yes 1 Disconnect the Molex and jumper the two green wires 2 Recycle power 3 If the unit goes to main burner then replace low water cut off switch 4 If the unit does n...

Page 6: ...ct both side of the venting and recycle power If the unit goes to main burner the problem is in the venting If the unit does not go to main burner the venting is probably OK Replace pressure switch 1...

Page 7: ...turn on and off This signal is generated by the control board Press the red reset button on the LED panel When the blower LED comes on then Measure for 2 0 and 8 8 DC volts on the orange and blue wir...

Page 8: ...3 feet of either a This will cause the combustion gases to re circulate back in to the fresh air intake 11 Is the termination behind bushes or shrubs a This will cause the combustion gases to re circu...

Page 9: ...om the AdvantagePlus Continue to next step Is the gas valve operating properly Yes No Replace control board 1 Recycle power to the heater When the GAS VALVE LED is ON measure 24 VAC between the yellow...

Page 10: ...g devices and do not respond well 6 Verify the gas orifice is installed and it is the correct orifice for the gas in use 7 Is there a fabricated drip leg to keep debris out of the gas valve Adjust the...

Page 11: ...check the following 1 Molex connections are tight on the board 2 Molex connects are tight on the blower Continue to next step Unit appears to be fine Recycle power and try again Does the igniter circ...

Page 12: ...0 VAC Yes No Replace control board The main control board passes the 120VAC from the power source there is not a direct link to line voltage except through the main control board 1 Measure for 120 VAC...

Page 13: ...d needs replacement CONTROL HEALTH problem with the control self diagnosis If the unit is operating but not holding temperature verify the flow rate of water is within the GPM performance for the temp...

Page 14: ...pts Explanation The unit will make three attempts for main burner then locks out This is probably associated with a fuel supply problem At a minimum check the following 1 Gas valve ON 2 Gas valve conn...

Page 15: ...AdvantagePlus Fault Tree Troubleshooting 1706 doc 15...

Page 16: ...383 165 1 536 85 8 251 126 3 313 166 1 508 86 8 056 127 3 244 167 1 480 87 7 869 128 3 178 168 1 453 88 7 685 129 3 112 169 1 426 89 7 507 130 3 049 170 1 400 90 7 333 131 2 986 171 1 375 91 7 164 13...

Reviews: