17
Model RQPM- Series
A060CK
A060JK
Cooling Performance
1
Gross Cooling Capacity Btu [kW]
61,000 [17.87]
61,000 [17.87]
EER/SEER
2
11.9/14
11.9/14
Nominal CFM/ARI Rated CFM [L/s]
2000/1900 [944/897]
2000/1900 [944/897]
ARI Net Cooling Capacity Btu [kW]
59,500 [17.43]
59,500 [17.43]
Net Sensible Capacity Btu [kW]
45,300 [13.27]
45,300 [13.27]
Net Latent Capacity Btu [kW]
14,200 [4.16]
14,200 [4.16]
Net System Power kW
5
5
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
59,500 [17.43]
59,500 [17.43]
System Power KW / COP
4.74/3.72
4.74/3.72
Low Temp. Btuh [kW] Rating
36,600 [10.72]
36,600 [10.72]
System Power KW / COP
4.26/2.54
4.26/2.54
HSPF (Btu/Watts-hr)
8
8
Compressor
No./Type
1/Copeland Scroll
1/Copeland Scroll
Outdoor Sound Rating (dB)
78
78
Outdoor Coil - Fin Type
Louvered
Louvered
Tube Type
Rifled
Rifled
Tube Size in. [mm] OD
0.375 [9.5]
0.375 [9.5]
Face Area sq. ft. [sq. m]
16.54 [1.54]
16.54 [1.54]
Rows / FPI [FPcm]
2 / 18 [7]
2 / 18 [7]
Refrigerant Control
TX Valves
TX Valves
Indoor Coil - Fin Type
Louvered
Louvered
Tube Type
Rifled
Rifled
Tube Size in. [mm]
0.375 [9.5]
0.375 [9.5]
Face Area sq. ft. [sq. m]
5.78 [0.54]
5.78 [0.54]
Rows / FPI [FPcm]
4 / 13 [5]
4 / 13 [5]
Refrigerant Control
TX Valves
TX Valves
Drain Connection No./Size in. [mm]
1/1 [25.4]
1/1 [25.4]
Outdoor Fan - Type
Propeller
Propeller
No. Used/Diameter in. [mm]
1/24 [609.6]
1/24 [609.6]
Drive Type/No. Speeds
Direct/1
Direct/1
CFM [L/s]
4000 [1888]
4000 [1888]
No. Motors/HP
1 at 1/3 HP
1 at 1/3 HP
Motor RPM
1075
1075
Indoor Fan - Type
FC Centrifugal
FC Centrifugal
No. Used/Diameter in. [mm]
1/11x9 [279.4x228.6]
1/11x9 [279.4x228.6]
Drive Type/No. Speeds
Direct/2
Direct/2
No. Motors
1
1
Motor HP
1
1
Motor RPM
1050
1050
Motor Frame Size
48
48
Filter - Type
Field Supplied
Field Supplied
Furnished
No
No
(NO.) Size Recommended in. [mm x mm x mm]
(1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g]
193 [5472]
193 [5472]
Weights
Net Weight lbs. [kg]
481 [218]
481 [218]
Ship Weight lbs. [kg]
507 [230]
507 [230]
3
4
GENERAL DATA - RQPM
NOMINAL SIZES 2-5 TONS [7-17.6 kW]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity
is net and includes the effect of fan motor heat. Units are suitable for operation in CFM range shown in airflow tables. Units are certified in accordance with the Unitary Air
Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Heating Performance is rated at 47° F ambient, 70° F entering dry bulb for High Temp rating and 17° F ambient, 70° F entering dry bulb for Low Temp rating. Performance
ratings do include the effect of fan motor heat.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.