Rheem Heating, Cooling and Water Heating         5

 

HYDRONIC AIR HANDLER AIR FLOW PERFORMANCE - RHWB MODELS

21

!

WARNING

SETTING BLOWER

TIMINGS

The IAC (Integrated Air Handler
Controls) has four quick connect
terminals for connecting the motor
speed leads. These are:

1. FAN SPEED — motor runs on

this speed when the thermostat
is in the “FAN ON” position.

2. COOL — connect desired

cooling speed.

3. HEAT — connect desired

heating speed.

If cooling speed and fan speed are
desired to be the same, this may be
accomplished by not connecting “Y”
to the IAC.
If desired for cool, fan and heat to all
be the same speed, then “piggyback”
jumper “H/C” to “FAN” and do not
connect “Y” to the IAC. Do not
connect other motor leads to “H” or
“C.”

DIRECT DRIVE

INSTRUCTIONS FOR

CHANGING BLOWER

SPEED

DISCONNECT THE ELECTRICAL
SUPPLY TO THE AIR HANDLER
BEFORE ATTEMPTING TO
CHANGE THE BLOWER SPEED.
FAILURE TO DO SO CAN CAUSE
ELECTRICAL SHOCK RESULTING
IN PERSONAL INJURY OR DEATH.

The blower motor must be wired for
blower speeds required for normal
operation.
If additional blower speed taps are
available (leads connected to “M1”
and “M2” on the electronic control),
speeds may be changed if necessary
to fit requirements of the particular
installation. Reconnect the unused
motor leads to “M1” or “M2.” Check
motor lead color for speed
designation.
Heating speeds should not be
reduced where it could cause the air
handler air temperature rise to
exceed the maximum outlet air
temperature specified for the unit.

IMPORTANT:

Always check air

temperature rise after changing the
heating speed for any reason.

CFM @ ESP

Model

Blower / Motor HP Speed

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

Low

921

915

886

876

855

841

817

780

734

690

M-Lo

1189

1180

1179

1137

1131

1102

1072

1030

985

915

RHWB-06WMP48A

11x7, 3/4

M-Hi

1335

1315

1306

1307

1277

1246

1210

1161

1090

1019

High

1841

1795

1747

1681

1622

1560

1500

1420

1358

1288

Low

1319

1307

1300

1240

1236

1210

1177

1149

1100

1032

M-Lo

1484

1480

1471

1463

1418

1385

1359

1314

1246

1166

RHWB-08WRP60A

11x10, 3/4

M-Hi

1687

1676

1671

1611

1586

1553

1513

1453

1389

1284

High

1971

1974

1948

1929

1871

1806

1751

1699

1610

1511

Low

1299

1294

1308

1279

1257

1231

1205

1165

1122

1053

M-Lo

1515

1519

1499

1487

1415

1418

1394

1348

1296

1221

RHWB-10WRP60A

11x10, 3/4

M-Hi

1684

1695

1693

1663

1620

1586

1569

1514

1451

1365

High

1954

1971

1974

1982

1973

1944

1917

1818

1775

1700

HYDRONIC AIR HANDLER AIR FLOW PERFORMANCE - RHWB MODELS

TABLE 4

Note: Units tested without filters in place.

RTG-53

32600

39500

47500

N/A

N/A

RTG-64

40900

47100

51000

N/A

N/A

RTG-66

40200

46400

54700

63500

71300

RHWB-06WMP48A

RTG-74

High

0.5

1622

37800

46200

54000

62700

71300

RTG-84

40000

47800

52100

60300

68100

RTG-95

37200

45200

50900

59200

66400

RTG-53

35000

41300

50600

N/A

N/A

RTG-64

42000

50900

53400

N/A

N/A

RTG-66

40400

50500

56500

65500

73600

RHWB-08WRP60A

RTG-74

Med-High

0.5

1586

40300

49700

58800

71600

81600

RTG-84

45800

53300

56900

66900

76000

RTG-95

45300

53100

60000

70500

80700

RTG-53

35500

44500

53300

N/A

N/A

RTG-64

40800

48000

53200

N/A

N/A

RTG-66

48300

57800

62100

71800

83000

RHWB-10WRP60A

RTG-74

Med-High

0.5

1620

49300

59600

69500

79100

89700

RTG-84

43200

51800

56900

65100

75400

RTG-95

48300

58200

61000

71000

79800

9

HYDRONIC AIR HANDLER TANKLESS WATER HEATER PERFORMANCE

TABLE 1

Entering Water Temperature (°F)

Air Handler Model Tankless Model Blower Speed ESP (in. w.c.)

Heating Air Delivery

(CFM)

120

130

140

150

160

Performance is based on the following assumptions:

1) an estimated 100 ft. equivalent length of 0.75-inch piping.

2) 0.80” w.c. of external air static.

HYDRONIC AIR HANDLER WITH TANKLESS WATER HEATER PERFORMANCE

Performance is based on the following assumptions:
1) an estimated 100 ft. equivalent length of 0.75-inch piping
2) 0.50” w.c. of external air static.

Summary of Contents for RHWB series

Page 1: ...r Handler Low profile 34 inch design is lighter easier to handle and leaves room for optional accessories Left or right side electric connections Integrated control board features diagnostics manages...

Page 2: ...ween the tankless water heater and the hydronic coil 3 COOLING COIL In cooling mode the cooling coil operates the same as any other Rheem heating and cooling system STANDARD EQUIPMENT Completely assem...

Page 3: ...major design change in the product line i e capacity Nominal Heating Capacity BTU HR 06W 60 000 08W 80 000 10W 100 000 Revision A Rev 0 Blower Size M 11x7 R 11x10 Variations P PSC Motor 48 15 1700 CF...

Page 4: ...11 32 593 225 8 575 7 8 22 600 2025 32 528 0 0 0 1 25 2 51 10WR 241 2 622 2311 32 593 225 8 575 7 8 22 600 2025 32 528 0 0 0 1 25 2 51 UPFLOW MODELS Designates Metric Conversions FIGURE 4 CLEARANCE TO...

Page 5: ...77 1246 1210 1161 1090 1019 High 1841 1795 1747 1681 1622 1560 1500 1420 1358 1288 Low 1319 1307 1300 1240 1236 1210 1177 1149 1100 1032 M Lo 1484 1480 1471 1463 1418 1385 1359 1314 1246 1166 RHWB 08W...

Page 6: ...assembly High altitude capability up to 9 840 ft elevation above sea level no chip required Exclusive Guardian OFW overheat film wrap All Rheem tankless models are third party efficiency certified by...

Page 7: ...and maintenance codes Built in electric blower Supplied with a 120 volt power cord Environmentally friendly Low NOx burner meets SCAQMD rule 1146 requirements Freeze protection to 30 F Product appeara...

Page 8: ...etting and maintenance codes Built in electric blower Supplied with a 120 volt power cord Environmentally friendly Low NOx burner meets SCAQMD rule 1146 requirements Freeze protection to 30 F Product...

Page 9: ...ay be used or a suitable 1 25 4 mm filter Designates Metric Conversions Rheem Heating Cooling and Water Heating 7 FILTER RACK FILTER SIZES INCHES mm MODEL RXGF CB BOTTOM RHWB 04WMAES 153 4 x 25 400 x...

Page 10: ...heem Heating Cooling and Water Heating TYPICAL PIPING ARRANGEMENT FOR DIRECT SPACE HEATING AND DOMESTIC WATER SUPPLY WITH TANKLESS All piping to be 3 4 inch BV DV Evaporator Coil Air Separator Flow Sw...

Page 11: ...Rheem Heating Cooling and Water Heating 11...

Page 12: ...S A 04 10 DC FORM NO H11 534 Supersedes Form No G11 450 Rev 16 Rheem Heating Cooling and Water Heating 5 Designates Metric Conversions GENERAL TERMS OF LIMITED WARRANTY Rheem will furnish a replacemen...

Reviews: