50
Table Q: Boiler Menu
Item
Application
Description
BOILER 1
ALL
Enables Boiler for operation.
BOILER 2
CASCADE
Enables Boiler for cascade operation.
BOILER 3
CASCADE
Enables Boiler for cascade operation.
BOILER 4
CASCADE
Enables Boiler for cascade operation.
IGNITION
(IGNITION 1/2, models
1532-2342)
ALL
IDLE=no CFH; PREP=pre-purge or inter-purge
between trials for ignition; IGN=trial for ignition;
BURN=burner operating; POST=post purge;
HARD=a hard lockout fault has occured requir-
ing manual high limit); and SOFT=a soft
lockout fault has occurred which interrupts the
manual high limit).
The CFH will resume after the soft lockout fault
has been corrected and a 15 min. waiting peri-
od has expired.
VENT WALL
Not Available Not Available.
LIMIT TEMP
ALL
Current Outlet -Limit temperature.
EMS VDC
ALL
Current EMS signal in Volts DC.
FIRE RATE
ALL
PIM firing rate.
OUTLET MAX
H Mode 1,2,3
Defines Max Outlet temperature offset above
Target Setpoint (Press and hold up and down
arrows for 3 seconds to enable adjustment),
see VERSA IC manual, catalog 5000.72.
OPERATOR
ALL
Operator Potentiometer setting on PIM.
DIFF
ALL
Current auto differential – Fixed by PIM.
PUMP POST
ALL
Sets the length of the boiler pump purge.
FLAME CUR
ALL
Flame current in micro-amps (µA).
MASS
ALL
Thermal mass recovery, see VERSA IC manu-
al, catalog 5000.72.
IDENTITY
ALL
Identifies the unit as boiler, water heater or
pool heater.
IGN TYPE
ALL
PIM Board type.
ID CARD
ALL
Identifies Raypak Identity Card.
SW ID
ALL
PIM Software identification number.
ERROR CODE
ALL
Current Error Code.
* Fixed values based on ID card
Boiler Menu
The Boiler View displays various items regarding ignition, temperature monitoring, and modulation rates. As well
as software and hardware information.
Summary of Contents for Raypak Hi Delta 1262C
Page 54: ...54 Wiring Diagram Models 992C 1262C...
Page 55: ...55 Wiring Diagram Models 1532C 2342C...
Page 69: ...69...
Page 70: ...70...