COMMISSIONING
55
MULTIPAK – FAULT FINDING PROCEDURE
Fault
Possible
Causes
Description & Recommended Corrective Action
No Hot
Water
Gas
Failure
•
Check gas supply and reinstate
Power
Failure
•
Check and reinstate Power Supplies to all the power outlets.
Water
Supply
Failure
•
Check adequate cold water supply is available to all CFWH & no
valves are shut.
•
Check for minimum 140KPa water supply pressure available.
•
Check CFWH strainers for cleanliness
RECFWH
Fault
•
Refer to Rheem Owner’s Guide and Installation Instructions for
additional Information
Long delay
for Hot water
Supply
Optional
Pump
Fault
•
Check pump operation (if fitted) as per commissioning list - item
8
•
(Page 46) of this manual.
•
Check Pump installation has been completed in accordance to
technical notes on page 18 of this manual
MULTIPAK – CFWH STRAINER CLEANING
1.
Isolate the CFWH cold and hot water valves.
2.
Remove the strainer assembly. Clean and refit.
3.
Re-instate the CFWH cold and hot water valves to open position.
4.
Complete above procedure for all the CFWH of the Multipak
Strainer
Natural Gas /
Propane Feed
Cold Water
Feed
Hot Water
Outlet