Rheem Guardian Warm Water Owner'S Manual And Installation Instructions Download Page 4

 

 

ABOUT YOUR WARM WATER SYSTEM 

 

WATER HEATER APPLICATION 

This warm water system is designed for the  purpose  of  providing potable  water. Its use in  an application  other 
than this may shorten its life. 
 

MODEL TYPE 

Congratulations for choosing Rheem  Guardian Warm Water. The model  you have chosen  will  be  either an 80, 
160  or  240  litre/min  model. Warm  water  is  produced  by  blending  hot  water  from  separate  water  heating  plant, 
with cold water by means of thermostatic mixing valve(s). The warm water unit can be installed either indoor or 
outdoor. The system is supplied in a tamperproof cabinet. A UV disinfection unit is supplied with the warm water 
system and forms part of a maintenance regime to safeguard against Legionella. 
 

MAINS PRESSURE 

Rheem Guardian is designed to operate at mains pressure by connecting directly to the mains water supply. The 
cold  and  hot  water  supply  to  the  unit  is  taken  from  the  same  source  and  the  pressures  should  be  nominally 
balanced. If the mains supply pressure  in  your area exceeds that shown on page 11, a  pressure limiting  valve 
must  be  fitted.  The  supply  pressure  should  be  greater  than  500 kPa  for  true  mains  pressure  operation  to  be 
achieved. 
 

HOW HOT SHOULD THE WATER BE? 

The  water  temperature  should  be  set  in  accordance  with 
local authority requirements for the intended application. 
 
The  system  is  factory  set  at  43

C.  Following 

commissioning,  the  system  can  be  set  to  operate  within 
the  temperature  limits  as  shown  on  page  7  under  normal 
operating conditions. 

Normal Operating Conditions 

are considered as: 

- inlet pressures nominally balanced to within 10% of each 
other during flow. 
- a differential of approximately 50

o

C between the hot and 

cold inlet temperatures, and with differentials of  
15-35

o

C between the blend setting and either supply. 

-  installation  and  usage  environment  not  subject  to 
extremes of temperature, unauthorised tampering or willful 
abuse. 
 
To  meet  the  requirements  of  the  National  Plumbing 
Standard the temperature of stored hot water must not be 
below 60°C. 
 
 

TEMPERATURE ADJUSTMENT 

The warm water system features tradesperson adjustable 
thermostats.  They  require  a  licensed  tradesperson  to 
make  any  temperature  adjustments. We  advise  the  thermostats  are  adjusted  to the  lowest  temperature  setting 
that meets your needs, especially if there are young children or elderly people in the premises.  
 

The Rheem warranty may not cover faults if relief valves or other safety devices are tampered with or if 
the installation is not in accordance with these instructions. 

 

PRECAUTIONS 

Where damage to property can occur in the event of the water heater leaking, the water heater must be installed 
in a safe tray. Construction, installation and draining of a safe tray must comply with AS/NZS 3500.4 and all local 
codes and regulatory authority requirements. 
 
If  this  warm  water  system  is  to  be  used  where  an  uninterrupted  warm  water  supply  is  necessary  for  your 
application  or  business  you  should  ensure  that  you  have  back  up  redundancy  within  the  hot  water  system 
design. This should ensure the continuity of warm water system in the event that this warm water system were to 
become inoperable for any reason. We recommend you seek advice from your plumber or specifier about your 
needs and building back up redundancy into your warm water system. 
 

 

 

 

 
 

Maximum hot water 

supply temperature to 

warm water system 

(70

°

C) 

Factory set warm water 

supply temperature 

(43

C) 

Minimum hot water 

supply temperature 

(60

C) 

Summary of Contents for Guardian Warm Water

Page 1: ...This warm water system must be installed and serviced by a qualified person Please leave this guide with a responsible officer Owner s Guide and Installation Instructions Rheem Guardian Warm Water...

Page 2: ...a licensed person will give you a Compliance Certificate showing that the work complies with all the relevant Standards Only a licensed person will have insurance protecting their workmanship for 6 ye...

Page 3: ...ead pages 4 10 The other pages are intended for the installer but may be of interest Contents 3 About your warm water system 4 Operating parameters 6 Water supplies 6 Save a service call 10 Installati...

Page 4: ...ifferential of approximately 50oC between the hot and cold inlet temperatures and with differentials of 15 35oC between the blend setting and either supply installation and usage environment not subje...

Page 5: ...rm water system must be installed by a qualified person and in accordance the installation instructions and in compliance with Standards AS NZS 3500 4 AS NZS 3000 and all local codes and regulatory au...

Page 6: ...valves to give the total system flow at a given pressure loss TEMPERATURES Minimum Cold Water Temperature 1 C Maximum Hot Water Temperature 70 C Minimum Hot Water Supply Temperature Blend water tempe...

Page 7: ...of the water TDS in mg L is approximately 70 of the conductivity in S cm CHLORIDE AND PH In a high chloride water supply the water can corrode stainless steel parts and cause them to fail Where the ch...

Page 8: ...or scaling properties In a corrosive water supply the water can attack copper parts and cause them to fail Where the saturation index is less than 1 0 the water is very corrosive and the Rheem warrant...

Page 9: ...l Range 35 C 50 C Note For optimum performance reasons it is recommended that the maximum hot water temperature is limited to 65 C Caution During thermal disinfection the mixing valve can operate up t...

Page 10: ...er supply to another can have a detrimental effect on the operation and or life expectation of the warm water system Where there is a changeover from one water supply to another e g a rainwater tank s...

Page 11: ...ate Have you checked the heat loss in the system As warm water is supplied at or near user temperatures heat loss reduction is a critical factor in ensuring suitable temperatures are delivered at the...

Page 12: ...om the same source for the correct operation of system recirculation This will also help ensure balanced inlet pressures to the warm water unit Clearance must be allowed for servicing of the thermosta...

Page 13: ...avity fed tank supply systems If a tank supply is used a booster pump must be installed to supply cold water to the water heating plant and warm water unit REDUCING HEAT LOSSES PIPE SIZING Maintaining...

Page 14: ...INSTALLATION 14 WARM WATER UNIT DIMENSIONS...

Page 15: ...ATER RHEEM COMMERCIAL WATER HEATERS LEGEND LEGEND GUARDIAN WARM WATER WITH RAYPAK WATER HEATERS TYPICAL INSTALLATION WARM WATER WITH RHEEM COMMERCIAL WATER HEATERS TYPICAL INSTALLATION WARM WATER WITH...

Page 16: ...INSTALLATION 16 TYPICAL INSTALLATION MANIFOLDED WARM WATER UNITS TYPICAL INSTALLATION WARM WATER WITH LOLINE SOLAR PRE HEAT RHEEM GUARDIAN WARM WATER UTILISING COMMERCIAL LOLNE SOLAR PRE HEAT LEGEND...

Page 17: ...INSTALLATION 17 TYPICAL INSTALLATION WARM WATER WITH HILINE SOLAR PRE HEAT TYPICAL INSTALLATION WARM WATER WITH COMMPAK RHEEM GUARDIAN WARM WATER UTILISING COMMERCIAL HILNE SOLAR PRE HEAT LEGEND...

Page 18: ...let to the water heating plant The pipe work must be cleared of foreign matter before connection Where solar preheat forms a part of the system particular attention needs to be given to the cold water...

Page 19: ...to the building warm water flow line Note If a UV system is not a part of the installation an isolating valve MUST be fitted before connecting to the building flow line WARM WATER BY PASS To facilita...

Page 20: ...culator s Air will begin to be forced out of the taps As water flows freely from each tap close it Open the cold water isolation valve s at the inlet s to the thermostatic mixing valve s Open the near...

Page 21: ...perature is pre set at the factory to approximately 43oC under ideal installation conditions Site conditions sanitising prior to commissioning or personal preference will mean the maximum blend temper...

Page 22: ...mum blend temperature is achieved re fit the hub without disturbing the spindle positioning it so that the centre stop slot in the hub fits over the top of the cartridge stop refer to Figure 2 prevent...

Page 23: ...stem will automatically shut down Record the maximum and stabilised temperature recorded at the test point and at the first outlet in the building Reinstate the cold water supply to the mixing valves...

Page 24: ...emperature Hot water 60 70 o C Supply pressure Temperature Warm Water Valves exercised Test point temperature Valve 1 Valve 2 Valve 3 Combined valves Full Flow Min Flow Return temperature Pump speed s...

Page 25: ...UMBER____________ SERIAL NUMBER___________ Signature Comments UV tube cleaned UV hours run Shut off test final max Return test point temp Nearest outlet temp Valve 3 test point temp Valve 2 test point...

Page 26: ...26 WATER QUALITY TEST RESULT LOG RHEEM GUARDIAN WARM WATER Model Number______________ Serial Number____________ Date Sample Point ID Report No Result Report Filed Signature Sample 1 Sample 2...

Page 27: ...onella Sampling Unless prescribed by a regulating authority sampling at the following rates is recommended 1st 3 months 2 samples once per month Month 6 2 samples 6 monthly there after 2 samples The a...

Page 28: ...arried out in accordance with these instructions and must be conducted by designated qualified and competent personnel This mixing valve is designed for minimal maintenance under conditions of normal...

Page 29: ...artridge is replaced the In service test should be repeated as if it was a new valve Note In service tests should be carried out with a frequency which identifies a need for service work before an uns...

Page 30: ...structions 3 Measure and record blend temperature flow rate at maximum flow 4 Measure and record blend temperature and flow rate at minimum flow Has mixed water temperature changed by more than 1K 5 C...

Page 31: ...31 This page is left intentionally blank...

Page 32: ...shall be the owner s responsibility 2 5 Where the Rheem warm water system is installed in a position that does not allow safe or ready access the cost of that access including the cost of additional m...

Page 33: ...b Is not installed in Australia 5 HOW TO MAKE A CLAIM UNDER THIS WARRANTY 5 1 If you wish to make a claim under this warranty you need to a Contact Rheem on 131031 and provide owner s details address...

Reviews: