Rheem ECOH200DV Use And Care Manual Download Page 36

36

Venting

INSTALLATION INSTRUCTIONS

Venting for Direct-Vent Water Heater (cont.)

In the Commonwealth of 

Massachusetts

The Commonwealth of Massachusetts requires 

compliance with regulation 248 CMR 4.00 and 5.00 for 

installation of through-the-wall vented gas appliances as 

follows:

5.08: Modifications to NFPA–54, Chapter 10

(1) Revise NFPA–54 section 10.5.4.2 by adding a second 

exception as follows:

Existing chimneys shall be permitted to have their use 

continued when a gas conversion burner is installed, 

and shall be equipped with a manual reset device that 

will automatically shut off the gas to the burner in the 

event of a sustained back-draft.
(2) Revise 10.8.3 by adding the following additional 

requirements:

(a) For all side-wall, horizontally vented, gas-fueled 

equipment installed in every dwelling, building, 

or structure used in whole or part for residential 

purposes, including those owned or operated by the 

Commonwealth and where the side-wall exhaust vent 

termination is less than seven (7) feet above finished 

grade in the area of the venting, including but not limited 

to decks and porches, the following requirements shall 

be satisfied.
1. INSTALLATION OF CARBON MONOXIDE 

DETECTORS. At the time of installation of the side-wall, 

horizontally vented, gas-fueled equipment, the installing 

plumber or gas fitter shall observe that a hard-wired 

carbon monoxide detector with an alarm and battery 

backup is installed on the floor level where the gas 

equipment is to be installed. In addition, the installing 

plumber or gas fitter shall observe that a battery-

operated or hard-wired carbon monoxide detector 

with an alarm is installed on each additional level of 

the dwelling, building, or structure served by the side-

wall, horizontally vented, gas-fueled equipment. It shall 

be the responsibility of the property owner to secure 

the services of qualified licensed professionals for the 

installation of hard-wired carbon monoxide detectors.
a. In the event that the side-wall, horizontally vented, 

gas-fueled equipment is installed in a crawl space or 

an attic, the hard-wired carbon monoxide detector with 

alarm and battery backup may be installed on the next 

adjacent floor level.
b. In the event that the requirements of this subdivision 

cannot be met at the time of completion of installation, 

the owner shall have a period of thirty (30) days to 

comply with the above requirements, provided, however, 

that during said thirty (30) day period, a battery-

operated carbon monoxide detector with an alarm shall 

be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. 

Each carbon monoxide detector as required in 

accordance with the above provisions shall comply with 

NFPA 720 and be ANSI/UL 2034-listed and IAS-certified. 

3. SIGNAGE. A metal or plastic identification plate 

shall be permanently mounted to the exterior of the 

building at a minimum height of eight (8) feet above 

grade directly in line with the exhaust vent terminal for 

the horizontally vented, gas-fueled heating appliance 

or equipment. The sign shall read, in print size no less 

than one-half (1/2) inch in size, “GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. INSPECTION. The state or local gas inspector of the 

side-wall, horizontally vented, gas-fueled equipment 

shall not approve the installation unless, upon 

inspection, the inspector observes carbon monoxide 

detectors and signage installed in accordance with the 

provisions of 248 CMR 5.08 (2)(a)(1 through 4). 
(b) EXEMPTIONS: The following equipment is exempt 

from 248 CMR 5.08 (2)(a)(1 through 4): 
1. The equipment listed in Chapter 10 entitled 

“Equipment Not Required To Be Vented” in the most 

current edition of NFPA 54 as adopted by the Board, 

and 
2. Product-approved side-wall, horizontally vented, 

gas-fueled equipment installed in a room or structure 

separate from the dwelling, building, or structure used in 

whole or in part for residential purposes. 
(c) MANUFACTURER REQUIREMENTS – GAS 

EQUIPMENT VENTING SYSTEM PROVIDED. When 

the manufacturer of product-approved side-wall, 

horizontally vented, gas-fueled equipment provides a 

venting system design or venting system components 

with the equipment, the instructions provided by the 

manufacturer for installation of the equipment and the 

venting system shall include:
1. Detailed instructions for the installation of the venting 

system design or the venting system components; and
2. A complete parts list for the venting system design or 

venting system. 
(d) MANUFACTURER REQUIREMENTS – GAS 

EQUIPMENT VENTING SYSTEM NOT PROVIDED. 

When the manufacturer of product-approved side-

wall, horizontally vented, gas-fueled equipment does 

not provide the parts for venting the flue gases, but 

identifies “special venting systems,” the following 

requirements shall be satisfied by the manufacturer:
1. The referenced “special venting systems” instructions 

shall be included with the appliance or equipment 

installation instructions, and 
2. The “special venting systems” shall be product-

approved by the Board, and the instructions for that 

system shall include a parts list and detailed installation 

instructions. 
(e) A copy of all installation instructions for all 

product-approved side-wall, horizontally vented, 

gas-fueled equipment, all venting instructions, all 

parts lists for venting instructions, and/or all venting 

design instructions shall remain with the appliance or 

equipment at the completion of the installation. 

Summary of Contents for ECOH200DV

Page 1: ...Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance To do so may result in an explosion or fire Installation and service must be performe...

Page 2: ...erts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and either the word DANGER WARNING CAUTION or NOTICE 2 These words mean IMPOR...

Page 3: ...and adhesives are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere in the vicinity of a water heater or any other appliance Be sure to read...

Page 4: ...ast 30 minutes to melt the frozen water or the water heater may not work properly NOTICE The factory setting allows operating temperatures between 100 F 38 C and 120 F 49 C Temperatures of 85 F 29 C a...

Page 5: ...leak Some people may not physically be able to smell or recognize this odorant If you are unsure or unfamiliar with the smell of natural gas or LP ask the gas supplier Other conditions such as odorant...

Page 6: ...this label 2 Turn off all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5...

Page 7: ...ed only by qualified service personnel Make certain the power to the water heater is OFF before removing the unit cover panel Exposed electrical components and moving parts can cause personal injuries...

Page 8: ...ut off Be sure your water heater is properly installed in accordance with local codes and the provided installation instructions Do not attempt to repair or replace any part of your water heater unles...

Page 9: ...4 248 mm 21 4 59 mm 51 2 140 mm 61 8 156 mm 21 8 54 mm 37 8 98 mm 27 8 73 mm 41 8 105 mm 91 2 241 mm 11 2 38 mm Specifications Direct Vent Models 177 8 454 mm 185 8 473 mm 183 4 476 mm 275 8 702 mm 9...

Page 10: ...ow Rate gpm 0 25 0 25 Hot Water Capacity gpm 35 F rise 9 5 9 5 Hot Water Capacity 77 F rise 5 5 Default Temperature Setting no controller 120 120 Temperature Default Setting 100 100 Minimum Temperatur...

Page 11: ...ower Switch To Hot Water Faucet s Drain Valve Water Filter Cold Water Supply Shut Off Valve Note A flexible drain tube can be used To Suitable Drain To Suitable Drain Power Supply Cord Union Union Man...

Page 12: ...Gas Supply Line Shut Off Valve Manual Gas Shut Off Valve Cap Sediment Trap Service Valve Relief Valve Relief Valve Note A flexible drain tube can be used To Suitable Drain To Suitable Drain Condensat...

Page 13: ...death from scalds Children disabled and elderly are at highest risk of being scalded See instruction manual before setting temperature at water heater Feel water before bathing or showering Temperatu...

Page 14: ...eater may not operate with a small water flow Increase the water flow and recheck If it still does not operate with the hot water faucet completely open increase the temperature setting on the remote...

Page 15: ...ndling and discharge methods Do not operate without the condensate collector drain connected and routed to the proper drain This could cause the system to malfunction or fail On a regular basis inspec...

Page 16: ...Turn on a hot water faucet While the water heater is operating inspect the main burner flames through the burner sight glass The flames should be blue when the main burner is firing NOTICE If the flam...

Page 17: ...off and the electrical power supply disconnected Vacuum around the water heater to remove any dust dirt and or lint buildup Clean the water heater and the remote control with a damp soft cloth and mil...

Page 18: ...out of the line Clean the water filter under running water To remove severe sediment and dirt use a soft brush CAUTION Do not overtighten the water filter Overtightening can deform and or damage the f...

Page 19: ...ral gallons have drained release the lever handle to close the valve and stop draining NOTICE If the pressure relief valve on the hot water heater discharges periodically this may indicate a problem i...

Page 20: ...disconnect the power supply at the circuit breaker box Open all hot water faucets Run the water until it is COLD then shut off the faucet Close the water shut off valve Using a suitable container to...

Page 21: ...not work properly until this water is thawed To put the water heater back in service Disconnect drain hose Make sure the drain valve is closed Reinstall the water filter in the base of the cold water...

Page 22: ...e water heater down to an ambient temperature of approximately 30 F 34 C These temperatures are all based on temperatures without wind The heater only protects the internal components of the water hea...

Page 23: ...le Cause Solution Not enough or no hot water 1 Unit is not ON 1 Turn on the unit by pressing the POWER ON OFF button 2 Water shut off valve is not completely opened 2 Check shut off valve and open com...

Page 24: ...g size 4 Bleed over in one of the hot water fixtures 4 Contact a dealer or a qualified service technician Water too hot 1 Temperature is set too high 1 Decrease the temperature setting at the remote c...

Page 25: ...nectors or other safety devices Refer repairs to a qualified service technician When an error code is displayed Turn off all the hot water faucets Turn off the water heater by pressing the POWER ON OF...

Page 26: ...nit can be used for a while but contact a dealer or qualified service technician 93 The neutralizer must be replaced The unit cannot be used until the neutral izer is replaced Contact a dealer or qual...

Page 27: ...INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR Installation...

Page 28: ...quids with flammable vapors are used or stored Such liquids include gasoline LP gas butane or propane paint adhesives and their thinners solvents or removers Flammable vapors carry long distances from...

Page 29: ...0 0 mm 0 min 0 mm Sealed Do not install the water heater outdoors or in bathrooms bedrooms or any occupied rooms normally kept closed Do not install the water heater where it is subject to vibrations...

Page 30: ...ing a water heater in any of the following locations beauty shops dry cleaning establishments photo processing labs and storage areas for liquid and powdered bleaches or swimming pool chemicals These...

Page 31: ...Vent Water Heater Venting Required To Hot Water Faucet s Drain Valve Wall Plate Water Filter Cold Water Supply Shut Off Valve Power Supply Cord Union Union Union Manual Gas Supply Line Shut Off Valve...

Page 32: ...t s Drain Valve Cold Water Supply Shut Off Valve Hard Wire Union Manual Gas Supply Line Shut Off Valve Flue Terminal Cap Sediment Trap Manual Gas Shut Off Valve Water Filter Union Union Service Valve...

Page 33: ...to wall If mounting to dry wall or concrete wall use drywall anchors or lag bolts Make sure the proper electrical outlet or supply 120 VAC 60 Hz is available and located near the unit Direct vent mod...

Page 34: ...lowing recommended pipe material Use only 2 or 3 inch diameter pipe Refer to local codes for restrictions on the use of PVC CPVC or ABS pipe and fittings All exhaust venting materials for product inst...

Page 35: ...locations as described in this manual have been met Carefully inspect the entire venting and air intake system for any signs of cracks or fractures particularly at the joints between elbows or other f...

Page 36: ...e detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be perman...

Page 37: ...AFT Horizontal Vent Terminal Location Outside Walls Fixed Closed Fixed Closed Operable Operable V V V V V V X X V V Interior Wall Vent Terminal Air Supply Inlet Area Where Terminal is Not Permitted B...

Page 38: ...ther appliance 6 in 15 cm for water heaters less than or equal to 10 000 Btuh 3 kW 9 in 23 cm for water heaters greater than 10 000 Btuh 3 kW and less than or equal to 50 000 Btuh 15 kW 12 in 30 cm fo...

Page 39: ...enter to center distance between each pair of vent terminations of 24 in 61 cm for a two unit installation 24 in 61 cm and 36 in 91 4 cm for an installation of three units and 24 in 61 cm 36 in 91 4 c...

Page 40: ...iners For applications below 32 F use only lower temperature type solvent cement Appropriate solvent and cleaner must be used for the type of vent pipe used PVC CPVC or ABS Cleaner Primer and Medium B...

Page 41: ...ke termination Insert a small length of vent pipe through the wall and connect the coupling Connect vent cap or terminal to the vent pipe on the exterior of the building 1 Use the vent plate as a temp...

Page 42: ...Slope Exhaust Vent Pipe Air Intake Pipe Wall Plate Inspection Access Panel Optional Inspection Access Panel Optional Ceiling Downward Slope Alternative horizontal vent termination kits are commerciall...

Page 43: ...ector fittings Use cleaner primer and PVC cement where the vent pipes join the water heater Support vertical and horizontal runs as described on page 35 Vertical supports are required every 4 ft 1 2 m...

Page 44: ...l E Required vent clearance from any gable dormer or other roof structure with building interior access i e vent window 4 ft 1 2 m 4 ft 1 2 m F Required vent clearance from any forced air inlet includ...

Page 45: ...45 Venting INSTALLATION INSTRUCTIONS Adjustable Roof Flashing Support Clamp Upward Slope Support Hanger Air Intake Pipe Exhaust Vent Pipe Condensate Drain Optional Standard Vertical Vent Termination...

Page 46: ...ve Anticipated Snow Level Condensate Drain Alternative Vertical Vent Termination INSTALLATION INSTRUCTIONS Venting for Direct Vent Water Heater cont Venting Alternative vertical vent termination kits...

Page 47: ...nstalling contractor water supplier or plumbing inspector Water Supply Connections CAUTION IMPORTANT Do not apply heat to the HOT or COLD water connections If sweat connections are used sweat tubing t...

Page 48: ...upply line and connect it to the water inlet on the water heater To ensure proper operation of the water heater follow these water pressure guidelines Operation of the water heater requires a minimum...

Page 49: ...Use the following guidelines when connecting the HOT WATER OUTLET Connections between the water heater and point s of use should be as short as possible Local codes shall govern the piping used for wa...

Page 50: ...lief valve discharge line connects to the HOT water outlet pipe as shown above The other end of the pipe should be routed to a suitable drain to eliminate potential water damage For safe operation of...

Page 51: ...ater Outlet Water Inlet Water Inlet Drain Drain Condensate Drainage Be sure the condensate runs freely to a drain and does not accumulate inside the water heater In cold climates precautions may need...

Page 52: ...e Apply a thin coat of pipe compound to all threaded male ends Compound must be of the type resistant to the action of LP gas To ensure proper water heater operation the gas pipe and gas meter must be...

Page 53: ...TU HR Additional appliances at the location require 75 000 BTU HR Therefore the cubic feet per hour 199 900 75 000 2500 109 FT3 HR If the pipe length is 100 ft then the 3 4 inch pipe size capable of s...

Page 54: ...as supply line NOTICE Lever type gas shut offs should all be T handle type Using the proper size piping fittings and components build the gas supply line to the water heater NOTICE The gas supply line...

Page 55: ...it indicates a gas leak that must be corrected Contact a qualified service technician Pressure Testing the Gas Supply System CAUTION Install a gas pressure regulator in the gas supply line This regula...

Page 56: ...of the power supply cord on the outside of the water heater If local codes require hard wiring see instructions for Hard Wiring the Electrical Connections below Hard Wiring the Electrical Connections...

Page 57: ...OID VALVE 2 LECTROVALVE 2 LECTROVALVE 1 SOLENOID VALVE 1 LECTROVALVE DANS ADMISSION DE GAZ SOLENOID VALVE 0 ELECTRODE ALLUMEUR ANTI FROST HEATER CHAUFFAGE ANTI GIVRE FUSIBLE 3A OVER HEAT LIMITER LIMIT...

Page 58: ...ll any remote control outdoors or where it can come in contact with water Avoid installing the remote control in the following areas and or conditions area exposed to heat area exposed to steam area e...

Page 59: ...ll the remote control cable between the location of the remote control and the water heater Remove the remote control from the base plate Feed the remote control cable through the large center hole in...

Page 60: ...n cables from the remote control to the remote control connection terminals NOTICE The remote control wire connection terminals are not polarity sensitive Firmly tighten the terminal screws by hand Se...

Page 61: ...d devices unless authorized by the manufacturer The use of unauthorized energy saving devices can result in death personal injury and or property damage The manufacturer disclaims any responsibility f...

Page 62: ...t All vent runs are properly installed Vent terminal is properly installed Maximum vent length is observed Water supply has sufficient pressure Air has been purged from the water heater and the piping...

Page 63: ...Read the safety information above on this label 2 Turn off all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the...

Page 64: ...ting label or on the front cover of this manual Turn the gas shut off valve counterclockwise to the ON position Turn on all electric power to the water heater The water heater burner will automaticall...

Page 65: ...o 140 F 60 C Turn on the remote control Turn off the gas and water to the water heater by closing the shut off valves Press the UP adjustment button repeatedly until 120 F 49 C shows in the LED displa...

Page 66: ...ontrol Turn off the gas and water to the water heater by closing the shut off valves Press the DOWN adjustment button repeatedly until 100 F 38 C or 85 F 29 C shows in the LED display Hold the DOWN bu...

Page 67: ...alves The OFF position is DOWN Minimum Temperature Adjustment by the Main Remote Control UMC 117 USC1 117 and USC2 117 Residential water heater temperatures can be adjusted down to 85 F 29 C when requ...

Page 68: ...m change the third switch on DIP 2 to the ON position UP If altitude is above 6 560 ft 2 000 m and below 9 840 ft 3 000 m change the fourth switch to the ON position UP NOTICE Do not alter any other...

Page 69: ...rders should include 1 The model and serial number of the water heater from the rating plate 2 Specify the gas type natural or LP as marked on the rating plate 3 Parts description as shown below and n...

Page 70: ...s Ref Description 1 Control Board 2 Gas Valve 3 Burner Assembly 4 Blower Motor 5 Burner Manifold 6 Gas Inlet Connector 7 Water Control Body 8 Water Inlet Connector 3 4 9 Drain Relief Valve 10 Hot Outl...

Page 71: ...71 NOTES...

Page 72: ...72 NOTES...

Reviews: