Rheem Direct Vent Gas Tankless Water Heater Use And Care Manual Download Page 10

Installing the water heater:

Venting Through Closed Spaces

If the coaxial vent piping passes through a closed space, a minimum
clearance of 1” (2.5 cm) when installed horizontally or 6” (15 cm) when
installed vertically should be maintained between the coaxial vent pipe
and combustibles and noncombustibles. Be sure to follow local codes and
vent manufacturer’s installation instructions.

For maintenance and inspection purposes, the following access panels are
required.

Two (2) inspection access panels large enough to allow access for
venting inspection. One (1) of these access panels should be close
to where the coaxial vent pipe enters the ceiling. The other access
panel should be near the vent termination.

A ventilation access panel with a 16 in

2

(103 cm

2

) opening should

be provided every 10 ft (3 m).

downward slope 

1/4" per foot 

Ceiling 

Vent Pipe 

Wall Thimble 

Board 

Inspection 

Fire 
Stop

Access Panel #1 

Inspection 

Access 

Panel #2  

Appliance Vent Adapter

The water heater must be installed
with a UL 1738 approved Category III
Stainless Steel appliance coaxial vent
adapter.

Read the following instructions before
installation.

Test fit the adapter over the water heater
collar before proceeding.

Slide adapter end “A” down over heater
collar “B” as far as it will go.

Use the screws provided with the vent
adapter to attach the adaptor to the heater
collar.

NOTICE: 

Follow the appliance coaxial vent

adapter manufacturer’s instructions.

Appliance 
Vent Adapter

Water Heater

Exhaust

Flow

B

Collar

A

Draining the Condensate

Provision should be made to collect and
dispose of condensate from venting systems.

When a water heater is 

vented horizontally,

the vent pipe can have a DOWNWARD or
UPWARD slope towards the termination. If 
an UPWARD slope is used, a condensate trap
must be installed as close as practical to the
water heater in order to prevent condensate
from draining back into the water heater. See
Examples A and B on page 14 for
DOWNWARD and UPWARD slope for
horizontally vented water heaters. 

When a water heater is 

vented vertically,

an

UPWARD slope must always be used. A
condensate trap must be installed in the
horizontal section of the vent and as close 
as practical to the water heater in order to
prevent condensate from draining back into 
the water heater. See the diagram on page 15
showing UPWARD slope for vertically 
vented water heaters.

Always attach a drain hose to the drain fitting
and plumb the hose to a sanitary sewer drain.

A high temperature silicon tubing suitable for
use with acidic condensate and appropriate for
the temperature range should be used.

The drain tube is fashioned into a “pigtail” trap
and must be filled with water to prevent flue
gases from emitting into the building prior to
operating the appliance.

CAUTION: Condensate

must drain away from the
water heater and should
not be allowed to drain
back into any part of the
vent system.

WARNING: Failure to

provide a vent condensate
drain close to the appliance
could allow acidic flue gas
condensate to enter into
appliance flueways, causing
premature failure of the
appliance.

CAUTION: Condensate

is known to be acidic; refer
to local, state (provincial)
or federal codes for proper
handling and discharge
methods.

10

CAUTION: Ensure that the
appliance vent adapter is
securely attached to the
water heater collar. 

Summary of Contents for Direct Vent Gas Tankless Water Heater

Page 1: ...the proper installation and adjustment of the water heater and two to the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This...

Page 2: ...ce READ THIS MANUAL FOR YOUR RECORDS Write the model and serial numbers here You can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date...

Page 3: ...er flammable materials and liquids adhesives solvents paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible mater...

Page 4: ...ng allows operating temperatures between 100 F 38 C and 120 F 49 C Temperatures of up to 140 F 60 C can be achieved with the MAIN UMC 117 remote control and a dip switch adjustment Only qualified serv...

Page 5: ...e or LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to...

Page 6: ...ON READ ALL INSTRUCTIONS BEFORE USING WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explosion electric shock or to prevent property damage per...

Page 7: ...of any flammable liquids which may be improperly stored or accidentally spilled The water heater should be installed as close as practical to the vent termination to minimize vent length and the numbe...

Page 8: ...operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This manual also includes a parts list It is imperative that all persons who are expec...

Page 9: ...eting the installation and putting the water heater into service DANGER Failure to install the appliance vent adapter and properly vent the water heater to the outdoors as outlined in the Venting sect...

Page 10: ...and dispose of condensate from venting systems When a water heater is vented horizontally the vent pipe can have a DOWNWARD or UPWARD slope towards the termination If an UPWARD slope is used a condens...

Page 11: ...let to any building or other appliance 6 inches 15 cm for appliances 10 000 Btuh 3 kW 12 inches 30 cm for appliances 10 000 Btuh 3kW and 100 000 Btuh 30kW 36 inches 91 cm for appliances 100 000 Btuh 3...

Page 12: ...maintenance Do NOT extend exposed vent pipe of indoor water heaters outside of building Guard vent against accidental contact with people and pets Indoor Water Heater 12 WARNING Moisture in the flue...

Page 13: ...Example A Typical Horizontal Termination w 1 4 per foot DOWNWARD Slope 13 Installing the water heater...

Page 14: ...llow the vent manufacturer s recommended installation instructions provided with the vent purchased from the manufacturer Chase Requires 6 15 cm Clearance to Combustibles Firestop Firestop Roof Jack A...

Page 15: ...or pressure relief valve To ensure proper operation of the water heater the following water pressure guidelines should be followed Operation of the water heater requires the minimum water pressure of...

Page 16: ...e copper connections are recommended on the HOT and COLD water lines so that the water heater may disconnect easily for servicing if necessary Install a Check Valve between the water heater and the wa...

Page 17: ...be installed in the discharge line Notice Local codes govern the installation of relief valves If local codes require that a temperature and pressure relief valve should be installed the manufacturer...

Page 18: ...the action of LP gas Use compound sparingly on male threads only A sediment trap should be installed at the bottom of the gas line Do not use excessive force over 31 5 ft lbs 42 7 Nm in tightening the...

Page 19: ...controls can connect to the water heater Therefore a maximum of three controls can connect to the water heater No other manufacturer s controls are suitable for use with this water heater DO NOT atte...

Page 20: ...NING Field wiring connections and electrical grounding must comply with local codes or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 or in Canada C...

Page 21: ...personal injury or death CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify correct operation after servicing BK 8 R...

Page 22: ...22 Installing the water heater Typical Installation of Water Heater Venting Required...

Page 23: ...y heat loss encountered with storage tank heaters This water heater does not store water making an insulation blanket unnecessary The manufacturer s warranty does not cover any damage or defect caused...

Page 24: ...sufficient for the water heater Gas line equipped with shut off valve union and sediment trap Approved pipe joint compound used Soap and water solution used to check all connections and fittings for...

Page 25: ...and all other labels on the water heater as well as the warnings printed in this manual Failure to do so can result in unsafe operation of the water heater resulting in property damage personal injur...

Page 26: ...alves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines Contact a licensed plumber or the local plumbing authority for further information Se...

Page 27: ...otter water increases the risk of scald injury Always supervise young children or others who are incapacitated The water heater is equipped with a device that will shut off the gas supply to the burne...

Page 28: ...nance and or cleaning ensure proper operation by turning on a hot water faucet Housekeeping Before performing Housekeeping tasks to this water heater turn the unit off and disconnect the power supply...

Page 29: ...t It is recommended that qualified service personnel familiar with Category III venting inspect the venting system Check vent connection joint sections with a solution of soapy water to assure air tig...

Page 30: ...freezing conditions even for a short period of time be sure to drain all water from the unit as instructed above Exposure to freezing conditions can occur from down draft of venting system or from in...

Page 31: ...functions if applicable Check and replace if necessary Error code displayed on remote control See instructions for Error Code and if required contact a dealer for service Not enough water demand Incre...

Page 32: ...r safety devices Refer repairs to qualified service personnel CAUTION Make certain power to water heater is OFF before removing protective cover FOR ANY REASON CAUTION Label all wires prior to disconn...

Page 33: ...33...

Page 34: ...splay of the Main Remote Control is on continuously Change the DIP Switch 4 setting back to the OFF position DO NOT alter any other DIP Switch The LED on the PCB will stop illuminating At the same tim...

Page 35: ...35 Notes...

Page 36: ...ll be located in the room that houses the appliance or equipment and shall a Be powered by the same electrical circuit as the appliance or equipment such that only one service switch services both the...

Reviews: