Rheem Commercial Point-of-Use Electric Water Heater Use & Care Manual Download Page 4

4

4. RELIEF VALVE — A new combination pressure and temperature relief

valve, complying with the Standard for Relief Valves and Automatic Gas
Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22, must be
installed in the opening provided and marked for the purpose on the
water heater. (Refer to Fig. 2 or 3.) No valve of any type should be
installed between the relief valve and the tank. Local codes shall govern
the installation of relief valves.

The pressure rating of the relief valve must not exceed 150 psi, the
maximum working pressure of the water heater as marked on the rating
plate. The BTUH Rating of the relief valve must not be less than the
input rating of the water heater as indicated on the rating label located on
the front of the heater (1 watt = 3.412 BTUH).

Connect the outlet of the relief valve to a suitable open drain so that the
discharge water cannot contact live electrical parts and to eliminate
potential water damage. Piping used should be of a type approved for hot
water distribution. The discharge line must be no smaller than the outlet of
the valve and must pitch downward from the valve to allow complete
drainage (by gravity) of the relief valve and discharge line. The end of the
discharge line should not be threaded or concealed and should be
protected from freezing. No valve of any type, restriction or reducer
coupling should be installed in the discharge line.

5. TO FILL WATER HEATER — Make certain drain valve is completely

closed. Open shut-off valve in cold water supply line. Open each hot water
faucet slowly to allow air to vent from the water heater and piping. A steady
flow of water from the hot water faucet(s) indicates a full water heater.

Tank MUST BE full of water before power is turned on. Heating
element(s) WlLL BE DAMAGED if energized for even a short time while
tank is dry. The water heater’s warranty does not cover damage or
failure resulting from operation with an empty or partially empty tank.
(Reference is made to the limited warranty for complete terms and
conditions.)

6. ELECTRICAL CONNECTIONS — The voltage requirements and wattage

load for all heaters is specified on the rating plate. Table 1 recommends
minimum branch circuit sizing based on the National Electrical Code. All
wiring must conform to local codes or latest edition of National Electrical
Code ANSI/NFPA 70.

Some models are supplied with a plug connected power supply cord for use

only in 120 VAC applications. The cord must be connected to a properly

Installation

Figure 2. — Typical Side Connect Installation

Figure 3. — Typical Under Counter Top Connect Installation 

WARNING

!

Recommended

Heat Trap

6" Min.

Hot Water

Outlet to Fixtures

Opening for 

1/2" or 3/4"

Electrical Fitting

(Use only Copper

Conductors)

Jacket Access

Panel

Union

Shut-Off

Valve

Air Gap
6"

Auxiliary

Catch Pan

Drain Valve

(Not Supplied)

Temperature & Pressure

Relief Valve

To Cold Water

Supply

Relief Valve
Discharge
Line to suitable
open drain

Table 1. —

Branch Circuit Sizing and Wire Size
Guide Based on N.E.C. ANSI / NFPA 70

Shut-Off Valve

Unions

Cold Water Supply

Relief Valve
Discharge Line

Hot Water Outlet
(To Fixtures)

Suitable Open Drain

6"

Auxiliary Catch Pan

Auxiliary Catch Pan Drain Line

Jacket Access Panel

Power Supply Cord
2

1

/

2

gal. models only

Drain valve*

Temperature
Pressure
Relief Valve

*Drain valve is located below and to right of Jacket Access Panel and is not

visible in this view.

Recommended Over

Total

Current Protection

Copper Wire Size -

Water Heater

(Fuse or Circuit Breaker)

AWG Based on N.E.C.

Wattage

Amperage Rating

Table 310-16 (75°C.)

120V 208V 240V 277V 480V 120V 208V 240V 277V 480V

1440

15

---

---

---

---

14

---

---

---

---

1500

20

15

15

15

15

12

14

14

14

14

2000

25

15

15

15

15

10

14

14

14

14

2500

30

15

15

15

15

10

14

14

14

14

3000

35

20

20

15

15

8

12

12

14

14

4500

---

30

25

25

15

---

10

10

10

14

6000

---

40

35

30

20

---

8

8

10

12

Vacuum Relief Valve

(Not Supplied)

If required, install per local codes

and valve manufacturer’s

instructions.

Anode

Summary of Contents for Commercial Point-of-Use Electric Water Heater

Page 1: ...s who are expect ed to install operate or adjust this water heater read the instructions carefully so that they may understand how to do so NOTICE This water heater is designed for use in a commercial...

Page 2: ...ermostat is set too high NOTE When this water heater is supplying general purpose hot water requirements for use by individuals a thermostatically controlled mixing valve for reducing point of use wat...

Page 3: ...ONS Refer to Fig 2 or 3 for suggested typical installation The installation of unions or flexible copper connectors on the water connections is recommended so that the water heater may be easily disco...

Page 4: ...es not cover damage or failure resulting from operation with an empty or partially empty tank Reference is made to the limited warranty for complete terms and conditions 6 ELECTRICAL CONNECTIONS The v...

Page 5: ...tions The presence of water in the piping and water heater does not provide sufficient conduction for a ground Non metallic piping dielectric unions flexible connectors etc can cause the water heater...

Page 6: ...k of scald injury Contact a licensed plumber or the local plumbing authority for further information Make certain power to water heater is OFF before removing jacket access panel FOR ANY REASON If adj...

Page 7: ...sting devices are usually available from your plumber or local plumbing supply store 2 ANODE ROD INSPECTION The anode rod should be removed from the water heater s tank annually for inspection and rep...

Page 8: ...ers Address parts orders to the distributor or store from where the heater was purchased All parts orders should include 1 Model number and Serial number of heater from rating plate 2 Specify voltage...

Page 9: ...l number and Serial number of heater from rating plate 2 Specify voltage and wattage as marked on rating plate 3 Part Description as noted below and number of parts desired Ref Qty No Part Description...

Page 10: ...at s Heating Elements or other Operating Controls Refer repairs to qualified service personnel CAUTION 1 Should you have any questions about your new water heater or if it requires adjustment repair o...

Page 11: ...11 THIS PAGE WAS INTENTIONALLY LEFT BLANK...

Page 12: ...HIGH TEMP LIMIT ECO HEATING ELEMENT WHITE BLACK BLACK H G TO PROPERLY GROUNDED RECEPTACLE ON BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL JUNCTION BOX N 120 V Plug Connected Cord Set ONLY SINGLE EL...

Reviews: