Storage and handling

Storage and handling

As this product is a safety element, it should be stored and handled with care. 

Avoid: 

• any kind of impact or damage
• contact with water
• deformation of the casing

 

It is recommended: 

• to unload in a dry area
• not to flip or roll the product to move it
• not to use the damper as a scaffold, working table, etc.
• not to store smaller dampers inside larger ones

Installation

General points

 

The installation must comply with the installation manual and the classification report.

 

Axis orientation: see the declaration of performance.

 

Avoid obstruction of adjoining ducts.

 

Product installation: always with closed damper blade.

 

Verify if the blade can move freely.

 

Please observe safety distances with respect to other construction elements. The operating mechanism must also remain 

accessible: allow for a clearance of 200 mm around the housing.

 

The air tightness class will be maintained if the damper is installed according to the installation manual.

 

Rf-t fire dampers are always tested in standardised constructions according to EN 1366-2. The achieved results are valid for similar 

supporting constructions with a fire resistance, thickness and density equal or superior to the supporting construction used 
during the test.

 

The damper must remain accessible for inspection and maintenance.

 

Schedule at least 2 visual checks each year.

2021

2022

2023

2024

2025

TEST

 

|

 

 

|

 

 

|

 

 

|

 

 

|

 

Summary of Contents for CRS60

Page 1: ... eu en Rf Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel 32 9 362 31 71 Fax 32 9 362 33 07 info rft eu 0749 C16 EN A 08 2022 CRS60 Circular EI60S fire damper for surface and remote mounting ...

Page 2: ... data 26 Correction factor ΔL 26 Sample order 26 Approvals and certificates 27 Explanation of the abbreviations and pictograms Wn nominal width Hn nominal height Dn nominal diameter E integrity I thermal insulation S smoke leakage Pa pascal ve vertical wall penetration ho horizontal floor penetration o i meets the criteria from the outside o to the inside i i o fire side not important V AC Volt al...

Page 3: ...sealant 2 EI 60 h o i n o S 300 Pa Stone wool coating with acrylic sealant 1 EI 60 h o i n o S 300 Pa Stone wool coating with acrylic sealant 2 EI 60 h o i n o S 300 Pa Flexible wall Metal studs gypsum plasterboard Type A EN 520 100 mm Fire resistant acrylic sealant 1 EI 60 v e i n o S 300 Pa Fire resistant acrylic sealant 2 EI 60 v e i n o S 300 Pa Stone wool coating with acrylic sealant 1 EI 60 ...

Page 4: ...depending on the specific needs linked to the project or to the local regulations 5 easy to install 5 optimal free air passage and minimal pressure loss 5 optimal acoustic performance 5 air tightness class C according to EN1751 suitable for surface mount in rigid wall and light wall metal stud gypsum plasterboard wall suitable for installation remote from the wall tested according to EN 1366 2 up ...

Page 5: ...polar beginning and end of range switch KITS BFLT24 Spring return actuator BFL 24V with thermo electric fuse T KITS BFLT230 Spring return actuator BFL 230V with thermo electric fuse T KITS BFNT24 Spring return actuator BFN 24V with thermo electric fuse T KITS BFNT230 Spring return actuator BFN 230V with thermo electric fuse T KITS ZBAT 72 Black spare part for thermo electric fuse for BFLT BFNT FUS...

Page 6: ...ucts Product installation always with closed damper blade Verify if the blade can move freely Please observe safety distances with respect to other construction elements The operating mechanism must also remain accessible allow for a clearance of 200 mm around the housing The air tightness class will be maintained if the damper is installed according to the installation manual Rf t fire dampers ar...

Page 7: ...7 Installation Installation in a rigid wall sealing with acrylic sealant Dn 10 mm 100 Fire resistant acrylic sealant M6 Fire resistant acrylic sealant 1 2 3 4 ...

Page 8: ...8 Installation Installation in a rigid wall sealing with stone wool Dn 50 mm 100 Fire resistant acrylic sealant M6 Stonewool stuffed Fire resistant acrylic sealant 1 2 3 4 ...

Page 9: ...nstallation in flexible wall metal stud gypsum plasterboard wall sealing with acrylic sealant 50 2x12 5 1x25 mm F EN520 A EN520 100 mm Dn 10 mm Fire resistant acrylic sealant M6 Fire resistant acrylic sealant 1 2 3 4 5 ...

Page 10: ...ation in flexible wall metal stud gypsum plasterboard wall sealing with stone wool 50 2x12 5 1x25 mm F EN520 A EN520 100 mm Dn 50 mm Fire resistant acrylic sealant M6 Stonewool stuffed Fire resistant acrylic sealant 1 2 3 4 5 ...

Page 11: ...11 Installation Installation in shaft wall 50 2x15 1x30 mm F EN520 80 mm Dn 10 mm Fire resistant acrylic sealant M6 1 2 3 4 ...

Page 12: ...12 Installation Installation in rigid floor sealing with acrylic sealant 100 Dn 10 mm Fire resistant acrylic sealant M6 Fire resistant acrylic sealant 1 2 3 4 5 ...

Page 13: ...13 Installation Installation in rigid floor sealing with stone wool 100 Dn 50 mm Fire resistant acrylic sealant M6 Fire resistant acrylic sealant Stonewool stuffed 1 2 3 4 5 ...

Page 14: ...ension where necessary in accordance with the instructions of the duct manufacturer 3 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive 4 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant 1 2 3 4 5 ...

Page 15: ...e necessary in accordance with the instructions of the duct manufacturer 3 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive 4 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant Stonewool stuffed 1 2 3 4 5 ...

Page 16: ...0 mm 3 Provide suspension where necessary in accordance with the instructions of the duct manufacturer 4 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive 5 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant 1 2 3 4 5 6 ...

Page 17: ...ide suspension where necessary in accordance with the instructions of the duct manufacturer 4 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive 5 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant Stonewool stuffed 1 2 3 4 5 6 ...

Page 18: ... acrylic sealant 3 Provide suspension where necessary in accordance with the instructions of the duct manufacturer 4 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive 5 Apply the insulation in accordance with the manufacturer s instructions 1 2 3 4 5 ...

Page 19: ...ealant 100 Dn 10 mm 4 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive Silicate based adhesive 5 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant 1 2 3 4 5 6 ...

Page 20: ...n 50 mm 4 Attention Make sure that the movement of the damper blade is not impeded by the screws Silicate based adhesive Silicate based adhesive 5 Apply the insulation in accordance with the manufacturer s instructions Fire resistant acrylic sealant Stonewool stuffed 1 2 3 4 5 6 ...

Page 21: ...egulations i e BS9999 Annex V NF S 61 933 and EN13306 Read the maintenance instructions on our website https www rft eu assets PIM DOCUMENTS BROCHURE 20KITS BRO_K139_MAINTENANCE_C pdf Use the damper at up to 95 humidity non condensing The fire damper can be cleaned with a dry or slightly damp cloth It is forbidden to use abrasive cleaners or mechanical cleaning techniques brush ...

Page 22: ...h off the power supply for at least 5 sec Power the actuator respect the prescribed voltage for at least 75 sec The resetting stops automatically when the end of range is reached damper open Caution If the LED 3 flickers fast 3x sec the battery is discharged use a new battery If the LED 3 flickers slowly 1x sec the resetting is in progress If the LED 3 is continuously on the resetting is complete ...

Page 23: ...n the thermo electric fuse automatic unlocking the thermo electric fuse reacts as soon as the temperature reaches 72 C type BFLT remote unlocking by interrupting the power supply Caution The thermo electric fuse will not move the damper into its safety position when the temperature reaches 72 C if the motor is not powered Resetting manual resetting turn the enclosed handle anti clockwise To block ...

Page 24: ...cts as soon as the temperature reaches 72 C type BFNT remote unlocking by interrupting the power supply Caution The thermo electric fuse will not move the damper into its safety position when the temperature reaches 72 C if the motor is not powered Resetting manual resetting turn the enclosed handle anti clockwise To block the motor place the locking button on lock motorised resetting switch off t...

Page 25: ...1mA 1A 60V 75 s cabled 85 s battery ONE T 230 FDCU L 230 V AC 15 15 N A 0 57W 4 2W 1mA 1A 60V 75 s cabled 85 s battery BFLT24 24 V AC DC N A 0 8W 2 5W 1mA 3A AC 250V 60 s BFLT230 230 V AC N A 1 4W 4W 1mA 3A AC 250V 60 s BFNT24 24 V AC DC N A 1 1W 4W 1mA 3A AC 250V 60 s BFNT230 230 V AC N A 1 8W 5 5W 1mA 3A AC 250V 60 s MEC Running time spring Noise level motor Noise level spring Cable supply contr...

Page 26: ...069 47 11 004 54 60 dB Δp Pa 112 15 110 44 87 46 68 76 43 51 31 91 22 78 17 56 11 08 Q m h 225 36 428 97 775 21 1 227 60 1 846 66 2 898 00 3 966 52 5 793 47 7 910 05 50 dB Δp Pa 48 09 47 73 39 04 30 26 20 89 15 88 12 12 9 05 5 73 Q m h 147 60 278 76 506 67 813 60 1 292 49 2 044 80 2 799 16 4 118 16 5 685 83 40 dB Δp Pa 20 63 20 15 10 74 13 29 10 24 7 91 6 03 4 57 2 96 Q m h 96 48 176 71 337 30 540...

Page 27: ...cates All our dampers are submitted to a number of tests by official test institutes Reports of these tests form the basis for the approvals of our dampers 0749 requested requested If the product is manipulated in any other way than described in this manual Rf Technologies will decline any responsibility and the guarantee will expire ...

Reviews: