Radio Frequency Systems
BD1500W Series Air Dryers User’s Guide
Page 94 of 98
100518834 – Rev. B
14.2 Set Point Limits and Defaults
14.2.1
System Adjustments
14.2.2
Alarm Set Points
Description
Minimum
Value
Maximum
Value
Default
Value
Unit of
Measurement
Shut
down
High Flow Rate Alarm
W & WLP
0
0
2000 (56.6)
1500 (42.5)
SCFD
(SCMD)
High Outlet Pressure
Alarm
W
WLP
0.6 (4.1)
0.31 (2.1)
20.0 (137.9)
7.50 (51.7)
12.0 (82.7)
7.50 (51.7)
PSI (KPa)
Low Outlet Pressure
Alarm
W
WLP
0.5 (3.4)
0.30 (2.1)
19.9 (137.2)
7.49 (51.6)
6.5 (44.8)
0.30 (2.1)
PSI (KPa)
High Humidity Alarm
3
15
10
%
YES
High Compressor Last
Run Time Alarm
2:00
5:00
3:00
Minutes
High Cabinet
Temperature Alarm
120 (48.9)
Deg F
(Deg C)
YES
Compressor Total Run
Time Alarm
8000
Hours
14.2.3
System Operations
Description
ON Value
OFF Value
Default
Value
Unit of
Measurement
Compressor
W & WLP
25.0* (172.4)*
90.0 (620.5)
PSI (KPa)
Fan
90 (32.2)
80 (26.7)
Deg F (Deg C)
*
(50 – 90 PSI (344.7 – 620.5 KPa) for Dryers using Firmware v2.84 and older)
Description
Minimum
Value
Maximum
Value
Default
Value
Unit of
Measurement
System Pressure
W & WLP
80 (551.6)
PSI (KPa)
Static Pressure
W & WLP
17 (117.2)
PSI (KPa)
Outlet Pressure
W
WLP
2.0 (13.8)
0.30 (2.1)
15.0 (103.4)
7.50 (51.7)
PSI (KPa)
Alarm Delay
OFF
ON
ON
Startup Delay
0
10
0
Seconds