INSTALLATION 

Installation involves mounting the FSU module in its desired location, connecting all signal, coaxial and 
power cables, and programming the module data rate and other configuration settings. 

Note 1:  Instructions for the 107460-1 thru -4 FSU units also apply to the following units. 

 108015-1 thru -4, 107460-1-1, 107460-1-2, 107460-2-2 and 107460-3-1 

Note 2: Instructions for the 107460-5 FSU also apply to the 108015-5 and 107460-5-1 units. 

To install the module, proceed as follows: 

1.

Carefully inspect the module for any signs of shipping damage. If you suspect damage to the
module, immediately call RFL Customer Service at the number given at the bottom of this page.

2.

Check the assembly number on the front panel of the module to make sure the unit is compatible
with your interface requirement as shown in Table 1.

3.

Use Table 7 as a wiring guide for the D subminiature connector if your interface is RS-449 or
V.35. Use Table 8 as a wiring guide for the D subminiature connector if your interface is X.21 or
G.703. Use Table 9 as a wiring guide for the D subminiature connector if your interface is 120 ohm
E1. Use Table 10 as a wiring guide for the BNC connectors if your interface is 75 ohm E1. When
fastening the D subminiature connector, make sure that the screws on both ends of the mating
connector are tightened to secure the connector to the FSU front panel.

NOTE 

ALL CABLING TO AND FROM THE FIBER SERVICE UNIT INTERFACE CONNECTOR 
MUST UTILIZE SHIELDED TWISTED PAIR OR COAXIAL CABLE TO MINIMIZE 
CROSSTALK AND INTERFERENCE FROM EXTERNAL SOURCES. 

CAUTION 

BEFORE ATTEMPTING TO MAKE POWER CONNECTIONS TO THE FIBER SERVICE 
UNIT, MAKE SURE THAT YOUR POWER SOURCE IS COMPATIBLE WITH THE FSU.  IF 
THE IMPROPER VOLTAGE IS CONNECTED TO THE FSU, COMPONENT DAMAGE MAY 
RESULT.

 

A suitably rated power disconnect device and over current protection device (e.g. fuse or circuit 
breaker) must be installed between the station battery supply and the FSU power input.  The 
over current protective device should be rated at 0.5 to 1.5 Amps. 

4.

Connect input power to the following terminals on the rear-panel terminal block connector TB1, as
shown in Figure 5, see Figure 6 and 9 for 1U chassis installation.

Station battery positive  TB1-1 
Station battery negative TB1-2 

 Ground 

  TB1-3 

5.

Fiber optic cables with type ST series bayonet fiber optic connectors must be connected to the fiber
optic heads on the front panel of the FSU module and to the far end chassis. When connecting fiber
optic cables, make sure the connectors are properly aligned before tightening, and then fully tighten
them. This will help minimize losses in the connector.

RFL  C37.94FSU 

   RFL Electronics Inc. 

May 20, 2013 

(973) 334-3100

Summary of Contents for 107460-1

Page 1: ...nterface between synchronous electrical signals and optical fiber It can be used with the RFL 9300 RFL 9745 RFL IMUX 2000 or other types of multiplexers It can also be used with any other C37 94 compl...

Page 2: ...emale or two BNCs 15 pin female or two BNCs See Table 7 See Table 7 See Table 7 See Table 7 See Table 8 See Table 8 See Table 8 See Tables 9 10 See Tables 9 10 Table 2 Multimode Fiber Service Unit Cha...

Page 3: ...ge without notice IEEE Standard C37 94 for N times 64 kilobit per second optical fiber interfaces between teleprotection and multiplexer equipment Signal Connector Type 15 pin male type D subminiature...

Page 4: ...10 as a wiring guide for the BNC connectors if your interface is 75 ohm E1 When fastening the D subminiature connector make sure that the screws on both ends of the mating connector are tightened to s...

Page 5: ...the DOWN position to select normal receive data clock Place SW1 6 to the UP position to select inverted receive data clock For 107460 3 set SW1 6 to the DOWN position 8b For 107460 5 select AMI or HDB...

Page 6: ...licable Tx Rx Rx Tx 107460 X Or 108015 X Figure 2 Connecting the FSU to an RFL 9300 Note The FSU unit is orientated differently in a 1U chassis the connections are the same See Fig 6 and 9 RFL 9745 Ch...

Page 7: ...Tx fiber Rx fiber 38 to 150Vdc Input Power Fiber Service Unit 15 pin 37 pin or BNC connectors as applicable Tx Rx Rx Tx Non C37 94 compliant multiplexer 9745 9300 or any other C37 94 compliant device...

Page 8: ...rs on the front and rear panels of the FSU module Figure 7 shows the location of controls and indicators on ECB number 107463 The function of all controls and indicators are described in Table 4 CAUTI...

Page 9: ...he function of all controls and indicators are described in Table 4 1 718 REF 1 25 REF 234 REF 18 312 REF 19 00 REF WT 1 2 3 4 5 6 5 6 3 4 2 1 Wiring Diagram for Two FSU s mounted in a 1U Chassis Fron...

Page 10: ...r v et h er i g h t t oc h a n g ed e s i g n s a n ds p e c i c a t i o n s wi t h o u t n o t i c e U8 SW1 DS5 DS1 DS2 DS3 DS4 TB1 F1 Figure 7 Fiber Service Unit ECB No 107463 Board A controls and i...

Page 11: ...ED Receive Data Clock as follows Down Normal Clock Up Inverted Clock For 107460 3 SW1 6 must be DOWN SW1 7 On 107460 1 2 and 4 selects normal or inverted data as follows Down Inverted Data Up Normal D...

Page 12: ...anels of the FSU module Figures 10 and 11 show the location of controls and indicators on Board A and Board B The function of all controls and indicators are described in Table 5 CAUTIO N SB SB 38 150...

Page 13: ...s on Board A and Board B The function of all controls and indicators are described in Table 5 1 718 REF 1 25 REF 234 REF 18 312 REF 19 00 REF RFL ELECTRONICS INC BOONTON NEW JERSEY USA 2000 CCM FS U W...

Page 14: ...t wer e s e r v et h er i g h t t oc h a n g ed e s i g n s a n ds p e c i c a t i o n s wi t h o u t n o t i c e TB1 F1 U8 SW1 DS7 DS6 DS1 DS2 DS3 DS4 Figure 10 Fiber Service Unit ECB No 107463 5 Bo...

Page 15: ...e s e r v et h er i g h t t oc h a n g ed e s i g n s a n ds p e c i c a t i o n s wi t h o u t n o t i c e ON 1 2 3 4 5 6 TX RX U G G U 12 0 75 J203 J207 J205 SW201 SW203 J206 J204 Figure 11 Fiber S...

Page 16: ...ables or disables fiber Loopback as follows Up Loopback enabled Down Loopback disabled SW1 8 Enables or disables E1Loopback as follows Up Loopback Enabled Down Loopback Disabled DS1 FO D LED green Lig...

Page 17: ...hm E1 port DB 15 male connector Refer to Table 8 for interface connections J206 75 ohm E1 TX port BNC connector J207 75 ohm E1 RX port BNC connector SW201 Selects impedance of E1 port as follows Set t...

Page 18: ...Down Down 640 10 Up Down Up Up 704 11 Up Down Up Down 768 12 Up Up Down Up Note 1 G 703 is 64 kb s only and has N fixed at 1 Note 2 Down OPEN Up CLOSED Table 7 RS 449 and V 35 Interface Connections T...

Page 19: ...TX DATA SYNC YEL PWR 0 59 in 1 5 cm 1 77 in 4 5 cm a Fiber Service Unit front view 5 13 in 13 cm 4 73 in 12 cm 4 13 in 10 49 cm 0 31 in 0 80 cm diameter typical 8 51 in 21 61 cm 7 34 in 18 54 cm b Fib...

Page 20: ...date or incorrect information contained in this publication Disposal When disposing of the equipment it should be done in strict accordance with all local and national regulations for the disposal of...

Reviews: