background image

10

Storage and handling

Storage and handling

As this product is a safety element, it should be stored and handled with care.

Avoid: 

• any kind of impact or damage
• contact with water
• deformation of the casing

It is recommended: 

• to unload in a dry area
• not to flip or roll the product to move it
• not to use the damper as a scaffold, working table, etc.
• not to store smaller dampers inside larger ones

Installation

General points

 

The installation must comply with the installation manual delivered with the product and the classification report.

 

Axis orientation: see the declaration of performance.

 

Avoid obstruction of adjoining ducts.

 

Product installation: always with closed damper blade.

 

Verify if the blade can move freely.

 

Please observe safety distances with respect to other construction elements. The operating mechanism must also remain 

accessible: allow for a clearance of 200 mm around the housing.

 

The air tightness class will be maintained if the damper is installed according to the installation manual.

 

Rf-t fire dampers are always tested in standardised constructions according to EN 1366-2. The achieved results are valid for similar 

supporting constructions with a fire resistance, thickness and density equal or superior to the supporting construction used 
during the test.

 

The damper must remain accessible for inspection and maintenance.

 

Schedule at least two running visual checks each year.

2017

2018

2019

2020

2021

TEST

 

|

 

 

|

 

 

|

 

 

|

 

 

|

 

Installation at a minimal distance from another damper or from an adjacent supporting construction

≥ 75 mm

≥ 200 mm

1. Principle 
According to the European test standard, a fire damper must 
be installed at a minimum distance of 75 mm from an adjacent 
wall and 200 mm from another damper, unless the solution was 
tested at a shorter distance.

1

Summary of Contents for CU4L

Page 1: ...www rft be en Rf Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel 32 9 362 31 71 Fax 32 9 362 33 07 info rft be 0749 C6 EN M 11 2019 CU4 Rectangular fire damper 240...

Page 2: ...oor penetration o i meets the criteria from the outside o to the inside i i o fire side not important V AC Volt alternating current V DC Volt direct current E TELE power supply magnet E ALIM power sup...

Page 3: ...o EN 13501 3 Essential characteristics Performance Range Wall type Wall Sealing Installation Classification 200x200 mm CU4 1200x800 mm Rigid wall Aerated concrete 150 mm Fire resistant plaster 1 EI 24...

Page 4: ...or built in installation air tightness in accordance with EN 1751 class B class C in option tested according to EN 1366 2 up to 500 Pa operating mechanism outside the wall maintenance free for indoor...

Page 5: ...n Range and dimensions CU4L Wn Hn per step of 50 mm intermediate dimensions are subject to extra cost heights between 275 and 299 mm are not possible Exceeding blade X on the mechanism side Y on the w...

Page 6: ...return actuator BFL 24V with thermo electric fuse T KITS BFLT24 ST Spring return actuator BFL 24V with thermo electric fuse T and plug ST KITS BFL230 Spring return actuator BFL 230V KITS BFLT230 Spri...

Page 7: ...uator BFN 230V with thermo electric fuse T KITS BF24 Spring return actuator BF 24V BF kits must be used instead of BFN kits for fire dampers produced before 1 7 2015 KITS ONE T 24 FDCU Spring return a...

Page 8: ...witch FCU DCU FCB DCB KITS SN2 BFL BFN Auxiliary limit switch open closed KITS FTH72 Fusible link FTH 72 C for CFTH KITS ZBAT 72 Black spare part for thermo electric fuse for BFLT BFNT FUS72 ONE Fusib...

Page 9: ...8 5 x 16 mm 23 20 20 400 23 23 HnxWn Hn 6 x Wn 6 PG20 Connection to ducts with 20 mm flanges Elliptical holes 6 5 x 16 mm 40 HnxWn Hn 6 x Wn 6 L 70 PM Connection to ducts by insertion This type of fr...

Page 10: ...n elements The operating mechanism must also remain accessible allow for a clearance of 200 mm around the housing The air tightness class will be maintained if the damper is installed according to the...

Page 11: ...ed Schedule at least two running visual checks each year Remove dust and all other particles before start up Follow the local maintenance regulations i e BS9999 Annex V NF S 61 933 and EN13306 Read th...

Page 12: ...s at the time of order FCU Limit switch closed FDCU Unipolar limit switch open closed FDCB Bipolar auxiliary limit switch open closed Unlocking manual unlocking use the unlocking button 1 automatic un...

Page 13: ...the battery the LED fades away Close the battery compartment motorised resetting switch off the power supply for at least 5 sec Power the actuator respect the prescribed voltage for at least 75 sec Th...

Page 14: ...natively be unlocked by pushing the test button on the thermo electric fuse automatic unlocking the thermo electric fuse reacts as soon as the temperature reaches 72 C type BFLT remote unlocking by in...

Page 15: ...on on the thermo electric fuse automatic unlocking the thermo electric fuse reacts as soon as the temperature reaches 72 C type BFNT remote unlocking by interrupting the power supply Caution The therm...

Page 16: ...A 0 28W 4 2W 1mA 1A 60V ONE T 24 FDCB 24 V AC DC 10 20 N A 0 28W 4 2W 1mA 1A 60V ONE T 230 FDCU 230 V AC 15 15 N A 0 57W 4 2W 1mA 1A 60V ONE T 230 FDCB 230 V AC 15 15 N A 0 57W 4 2W 1mA 1A 60V ONE T 2...

Page 17: ...dB A 60 dB A 1 m 2 x 0 75 mm 1 m 6 x 0 75 mm IP 54 60 s 20 s 43 dB A 62 dB A 1 m 2 x 0 34 mm halogen free 1 m 6 x 0 75 mm halogen free IP 54 60 s 20 s 43 dB A 62 dB A 1 m 2 x 0 75 mm halogen free 1 m...

Page 18: ...8 17 3 18 7 20 2 21 7 23 1 24 6 26 0 27 5 29 0 30 4 31 9 33 3 34 8 36 3 37 7 39 2 40 7 42 1 43 6 350 kg 15 6 17 1 18 7 20 3 21 9 23 5 25 1 26 6 28 2 29 8 31 4 33 0 34 5 36 1 37 7 39 3 40 9 42 5 44 0 4...

Page 19: ...50 4 450 kg 39 4 41 2 43 1 44 9 46 7 48 5 50 3 52 2 54 0 500 kg 40 1 42 1 44 0 45 9 47 9 49 8 51 8 53 7 55 6 57 6 550 kg 40 6 42 7 44 7 46 8 48 8 50 9 53 0 55 0 57 1 59 1 61 2 600 kg 40 8 43 0 45 2 4...

Page 20: ...8 0 56 0 55 0 53 0 52 0 51 0 5 0 5 0 49 0 48 0 48 450 1 44 1 06 0 85 0 73 0 64 0 58 0 54 0 5 0 48 0 45 0 44 0 42 0 41 0 4 0 39 0 38 0 37 0 36 0 36 0 35 0 35 500 1 25 0 9 0 71 0 6 0 52 0 47 0 43 0 4 0...

Page 21: ...7 22 70 16 72 25 73 81 75 02 75 99 76 77 77 43 77 98 78 45 800 Sn m 0 0978 0 1317 0 1657 0 1996 0 2336 0 2675 0 3015 0 3354 0 3694 0 4033 0 4373 Sn 63 48 67 99 70 97 73 09 74 66 75 89 76 86 77 66 78 3...

Page 22: ...guarantees conformity with the standard NF S 61 937 Parts 1 and 5 Syst mes de S curit Incendie Dispositifs Actionn s de S curit conformity with the national decree of March 22 2004 changed on 14 March...

Reviews:

Related manuals for CU4L