background image

2.2 Ventilation 

Requirements

WARNING

Insufficient ventilation may result in health problems, carbon 

monoxide poisoning, or death. Always vent enclosed spaces 

and buildings according to national, state, provincial, and 

local codes. 

These heaters are the unvented type. Products of combustion generated are released 

into the space being heated. Sufficient ventilation of fresh air is required to provide 

adequate air for efficient combustion and to dilute and remove the products of combus-

tion. 

In the United States

, the minimum intake and exhaust air openings shall provide for 

not less than 4 CFM per 1,000 BTUH (0.38m3 a minute per kW). In the United States, 

this may be accomplished by either gravity or mechanical means. Both exhaust fans 

and inlet air openings are required in tight buildings. Exhaust openings for removing 

flue products shall be above the level of the heater (ANSI Z223.1/NFPA 54, section 

10.18, Infrared Heaters).
Air for combustion, ventilation, and dilution of flue gases shall be obtained by applica-

tion of one of several methods described in the National Fuel Gas Code, ANSI Z223.1/

NFPA 54, section 9.3, Air for Combustion and Ventilation.
The  ventilation  technical  information  outlined  in  the  current  ASHRAE  Handbooks 

should be observed when locating vents. When mechanical means are provided to 

supply and exhaust, a positive interlock with the heater thermostat must be provided by 

the installer so that the heater cannot operate unless the supply and exhaust system 

is operating.

Mechanical exhaust fans are typically located at high points of the building. For flat 

roof areas, a series of small exhausters should be distributed over the roof areas and 

interlocked with various heating zones. Local codes may permit the use of humidistat 

control to remove water vapor and products of combustion. Humidistat settings will 

typically be in the 40 to 55% relative humidity range.
Fresh  air  intake  openings  are  typically  located  high  on  the  building  sidewalls  at  or 

above the level of the heaters. One square inch of net free inlet area per 1,000

 

BTUH 

(22cm

2

 per kW) is required.

 

Multiple inlets, well distributed, should be used and should 

direct air upward to prevent drafts at floor level. Inlets are typically limited to 1 to 2 

square feet (900-1800cm

2

) in size. 

Total area required can be computed by divid-

ing exhaust CFM by 500 feet per minute. (Total area required can be computed 

by dividing exhaust cubic meters per minute by 152 meters per minute.)
In Canada

, the Natural Gas and Propane Installation Code CAN/CSA B149.1 (latest 

edition) requires the use of mechanical ventilation. The heater shall be provided with 

mechanical ventilation for combustion and ventilation air: 

(1) 

that is so located that products of combustion from each heater are 

effectively removed outdoors; 

(2)

 that has a ventilation volume of at least 3 CFM per 1,000 BTUH (0.29m3 

a minute per kW) for natural gas and 4 CFM per 1,000 BTUH (0.38m3 a 

minute per kW) for LP/propane; and 

(3) 

is sufficient to maintain the level of carbon dioxide at less than 5000 ppm 

measured 6 ft (2M) above the work area. 

3.0 Receiving

Check for any damage that may have been incurred during shipment. 
If damage is found, document the damage with the transporting agency and immedi-

ately contact your distributor. If you are an authorized Distributor, follow the FOB freight 

policy procedures provided by Thomas & Betts for this product. 

Form I-RIH, P/N 131793R8, Page 5 

Summary of Contents for RIH

Page 1: ...ervicing this equipment FOR YOUR SAFETY If you smell gas 1 Open Windows 2 Don t touch electrical switches 3 Extinguish any open flame 4 Immediately call your gas supplier The use and storage of gasoline or other flammable vapors and liquids in the vicinity of this appliance is hazardous WARNING Gas fired appliances are not designed for use in hazardous atmospheres containing flammable vapors or co...

Page 2: ...ructions and in compliance with all codes and requirements of authorities having jurisdiction DANGER These infrared heaters are operated without venting Comply with ventilation requirements in Paragraph 2 2 page 5 Model RIH and RIHV series heaters SHOULD NOT BE USED in the following applica tions Enclosed swimming pool areas Areas with contaminated atmospheres Outdoor applications Residential appl...

Page 3: ...ese codes are available from CSA Information Services 1 800 463 6727 Local authorities having jurisdiction should be consulted before installation is made to verify local codes and installation procedure requirements All electrical wiring including electrical grounding must be in accordance with the National Electric Code ANSI NFPA No 70 latest edition or in Canada the Canadian Electrical Code Par...

Page 4: ...be provided to shut off the burner and prevent its operation until the required clearance has been re established 1 0 General cont d 1 4 Installation Codes cont d Applies to Units Mounted at a 5 Angle Distance from the Wall Maximum Distance Between Heater Rows With Standard Reflector With Parabolic Reflector Option DM2 RIHN 30 8 ft 2 4M 5 ft 1 5M 90 ft 27 4M RIHL 50 RIHN 60 12 ft 3 7M 9 ft 2 7M 10...

Page 5: ...small exhausters should be distributed over the roof areas and interlocked with various heating zones Local codes may permit the use of humidistat control to remove water vapor and products of combustion Humidistat settings will typically be in the 40 to 55 relative humidity range Fresh air intake openings are typically located high on the building sidewalls at or above the level of the heaters On...

Page 6: ... will not cause combustible materials or materials in storage to attain a temperature in excess of 150 F 66 C See Hazard Levels page 2 WARNING Under no circumstances should this heater be installed in a combustible atmosphere or in a location where the heater controls can be subjected to ambient temperatures in excess of 150 F 66 C See Hazard Levels page 2 It is recommended that more distance than...

Page 7: ... ANSI Z233 1 NFPA 54 The stated clearance to combustibles represents a surface temperature of 90 F 50 C above room temperature Building materials with low heat tolerance such as plastic vinyl siding canvas tri ply etc may be subject to degradation at lower temperatures It is the responsibility of the installer to assure that adjacent materials are protected from degradation ANSI Z83 19 It is recom...

Page 8: ...hains along the length of the long chains 5 Check to be sure unit is level Crimp all S hooks closed A B C and D FIGURE 4 Chain Hanging Instructions Using either the chains and S hooks in Option UE1 chain and S hooks in Option UE2 or field provided chain and S hooks 5 0 Suspending the Unit cont d 3 8 10mm all thread rods for rigid mount 200 91kg working load chain for chain mount 1 4 6 3mm diameter...

Page 9: ...y only be used if permitted by local code It is recommended that either the piping or the mounting be flexible to prevent fatigue failure from vibration and or thermal expansion A first stage pressure regulator is required when gas supply pressure exceeds 14 35cm w c If a pressure regulator is required be sure that it is installed in the gas line with the arrow indicating gas flow pointing in the ...

Page 10: ... group of heaters can be controlled by a thermostat or manual switch Total load of all heaters must be considered in determining the required contact rating of the controlling thermostat or switch General Requirements The electrical supply wiring to the heaters using 120 VAC or 24 VAC must be installed in accordance with local codes or the National Electric Code ANSI NFPA 70 latest edition IMPORTA...

Page 11: ...e 120 VAC call for heat Thermostat Heater 1 Heater 2 GND 24 GGS BL BL GGS VR SW MV 24 VAC DSI SINGLE STAGE HEATER ELECTRICAL SUPPLY AND THERMOSTAT WIRING LEGEND 24 24 VAC Supply Voltage GND Earth Ground MV Mechanical Ventilation VR Ventilation Relay SW Ventilation Interlock Switch normally opened GGS Green Ground Screw inside control box BL Blue Wire 24 VAC call for heat Thermostat Heater 1 Heater...

Page 12: ... Blue Wire 24 VAC call for LOW heat R on heater Red Wire 24 VAC call for HIGH heat Use 18 4 solid class 2 thermostat cable between heater and thermostat with a maximum length of 125 feet 38m Heater 1 Heater 2 FIGURE 7A 120 VAC Direct Spark Ignition Electrical Connection Diagram Greem Ground Screw GGS W 1 BK 1 W 2 R 1 W 3 BK 2 1 2 burner R 2 3 4 burner O O Y G 120 GND G R 1 W 2 BK 1 W 1 Y Combinati...

Page 13: ...aving a temperature rating of at least 302 F 150 C and a minimum size of 16 AWG 1 0mm2 24 VAC 60 or 50 Hz 1 Phase Heater Maximum Current Draw 0 96 Amps Total Heater Power Consumed 23 1 VA FIGURE 7C 24 VAC 2 STAGE DIRECT SPARK IGNITION ELECTRICAL CONNECTION DIAGRAM Wire Colors BK Black G Green O Orange R Red W White Y Yellow field wiring Combination Gas Valve CGV Flame Sensor FS Flame Sensor FS Spa...

Page 14: ...the burner fail to light or flame is not detected during the first trial for ignition period the combination gas valve is de energized and the controller starts the 15 second inter purge sequence before another ignition trial After 15 seconds the controller begins two 2 more ignition trials If the burner fails to light after the third trial the controller will de energize the gas valve and go into...

Page 15: ...e heater should be free of objects that may overheat or prevent infrared energy from reaching desired area Post signs indicating maximum stacking height under or near heater Heater may be angle mounted only as specified See Paragraph 5 0 Heater must be level and suspended according to instructions in Paragraph 5 0 Be sure there are no gas or electric lines above or below the heater Adequate ventil...

Page 16: ...s a 24 120 volt thermostat that can be used to control 1 5 units This thermostat can also be used to control the exhaust fan circuit Thermostat Option CL82 is a 24 volt 2 stage digital thermostat that can be used with Option AG2R for automatic control of 1 5 units Parabolic Reflector Option DM2 The addition of the parabolic reflector increases the infrared intensity pattern while decreasing the sc...

Page 17: ...0kPa or less blow off all accumulated dust and dirt Blow air over the ceramic tile avoiding gasket material between tile and alternately into the venturi several times in succession Be careful not to damage gasket material between ceramic tiles Damaging the material between the tiles could lead to burner flashback E D C B A G F LEGEND Symbol Item Description A Gas manifold B Gas orifice C Venturi ...

Page 18: ...o electrical earth ground 3 Provide electrical earth ground 4 Electrical supply line voltage neutral polarity reversed 4 Correct electrical supply polarity 5 Heat on pilot flame sensor insufficient 5 Clean pilot check pilot orifice and alignment No pilot 1 Gas line contains air 1 Purge air from gas line 2 Pilot line orifice or passage blocked 2 Check and clean See Paragraph 11 1 3 Pilot solenoid v...

Page 19: ...t defective 2 Replace thermostat 3 High heat valve not opening 3 Replace high heat valve 2 Stage transition from high heat to low heat does not happen 1 Ambient temperature has not reached low heat zone of thermostat 1 Allow time for ambient temperature to reach low heat zone of thermostat Check thermostat manufacturer s instructions 2 Thermostat defective 2 Replace thermostat 3 High heat valve no...

Page 20: ...______ Model No ______________ Serial No _____________________Date of Installation ____________ SPECIFIC INSTALLATION NOTES i e Location Clearances Amps Gas Pressure Temperature Voltage Warranty etc _______________________________________________________________________________ _______________________________________________________________________________ _________________________________________...

Reviews: