EWHB Series Industrial / Commercial Electric Unit Heater /Installation Instructions, Page 1 of 4 

  23-2180-83-5REZ 

 

 

INSTALLATION INSTRUCTIONS 

 
 

  

 

    RISK OF FIRE / EXPLOSION 

 

This heater should not be used in potentially explosive atmospheres. Do not use in areas where gasoline, 
paint or flammable liquids are used or stored.  

 

Keep electrical cords, drapery, furnishings, insulation and other combustibles at least 3 feet (0.9m) from the 
front of the heater and away from the sides, rear and top.  

 

Installation minimum clearances specified both on the heater nameplate and in the owner’s manual must be 
maintained. 

 

Do not use as a residential or household heater. 

 

 

These air heaters are designed for comfort heating and 
should not be used in ambient temperatures exceeding 
80ºF (26.7ºC). They are to be permanently mounted to the 
wall or ceiling for horizontal discharge. The unit is 
designed to give years of safe, trouble-free operation 
when properly installed and maintained.  

 

A. 

Site Selection: 

 

The heaters are intended for elevated mounting locations 
so that they blow warm air down to the floor area. A 
mounting height should be selected so that the heater is 
out of the way of possible moving equipment or 
personnel, yet low enough to deliver warm air to the 
selected area. See the mechanical installation section for 
recommended installation heights.  
Heater airflow should be directed to areas of greatest heat 
loss. In general, greater numbers of small heaters will 
provide more uniform and even heat distributions than a 
few large ones. In order to help move heated air around 
the room, multiple heaters should be spaced out and 
direct air in a circular pattern around the room perimeter 
such that each heater supports the next heater’s 
airstreams. See Figures 1 & 2 for some typical airflow 
pattern arrangements:  

 

 

 

 

 

 

 

 

 

Large room with exposed walls and roof : 

FIGURE 1

 

 
 

 

 

Small room with one exposed wall: 

EXPOSED WALL

FIGURE 2

 

 

Summary of Contents for EWHB

Page 1: ...ater Owner s Manual This manual covers installation operation and maintenance Read carefully before attempting to install operate or service the EWHB Series Unit Heater IMPORTANT INSTRUCTIONS SAVE THE...

Page 2: ...use is not recommended by the manufacturer and may result in fire electric shock or personal injury 10 The heater and discharge air are hot when in use To avoid burns do not let bare skin touch hot su...

Page 3: ...The unit is designed to give years of safe trouble free operation when properly installed and maintained A Site Selection The heaters are intended for elevated mounting locations so that they blow war...

Page 4: ...installation such that the outlet air is not directed at an adjacent wall Louvered grills can be installed to deflect the discharge air up down or sideways TABLE 2 KW Cabinet Size Air Volume Air Throw...

Page 5: ...INSTRUCTIONS Continued Ceiling or wall mount using swivel bracket cont TABLE 4 KW BH BL M 12 4 25 108mm 19 50 495mm 8 50 216mm 12 1 to 47 7 125 181mm 22 25 565mm 3 25 83mm Optional Ceiling Installati...

Page 6: ...k hazards 4 Confirm that the electrical power supply matches the nameplate voltage phase amperage and frequency rating of the heater to be connected 5 Field supply conductors must be sized for at leas...

Page 7: ...ervice or clean heater while unit is operating as there is a hazard from electric shock injury from operating fan blade and burns from hot heating elements The unit is designed to give years of safe t...

Page 8: ...re reliable operation 10 During normal operation the limit controls are not supposed to cycle the heater ON and OFF If frequent cycling of the limit controls occurs verify the minimum mounting clearan...

Page 9: ...meter to check the current draw of each input line Adjust the room thermostat to its highest temperature to energize heater All input lines should draw approximately equal current which should agree w...

Reviews: