Reznor, AB - 2 Gas, GB 2019-08, D301177 Issue A PAGE 25
Ensure gas & electricity supplies
are on, and that control panel
heat enable is on to burner.
Burner controls
Check:
1. Ignition controller.
Check:
1. Operation of cycling/manual
thermostats. If tripped,
diagnose fault, reset.
2. Check control panel `burner
on` 230V supply.
3. Check any external circuit
breakers/ fuses.
Does the
fan run?
Check
:
1. Wiring harness & plugs.
2. Operation of vacuum switch
3. Replace fan.
Check:
1. Vacuum switch tube.
2. Emitter tubes, air inlet & vent
for obstructions.
3. Operation of vacuum switch
4. Replace fan.
Does the
vacuum switch
pull in?
Check
:
1. Ignition controller.
2. Wiring harness.
Is the burner
sparking?
Check
:
1. Integrity of spark leads
2. Integrity of spark electrode,
assembly & spark gap.
3. Ignition controller.
Check:
1. Ignition controller.
2. Replace gas valve.
Does the gas
valve open?
If the heater still fails
to operate normally,
please contact
the Reznor
service department
Check:
1. Burner inlet pressure.
2. Burner nozzle pressure.
3. Check live & neutral polarity.
4. Check presence of good
earth.
Is there power
to the burner?
YES
YES
NO
NO
NO
YES
YES
NO
NO
YES
YES
Fault Finding