E1: Input terminal parameters
Code
Name
Setting range
Default
Min.
Attri.
E1.00 X1 input
0...51
35
–
Stop
E1.01 X2 input
36
–
Stop
E1.02 X3 input
0
–
Stop
E1.03 X4 input
0
–
Stop
E1.04 X5 input
0
–
Stop
E1.15 2-wire/3-wire control mode
0...4
0
–
Stop
E1.16 Digital input Up / Down change rate
0.10...100.00 Hz/s
1.00
0.01
Run
E1.17
Digital input Up / Down initial
frequency
0.00...[E0.09] Hz
0.00
0.01
Run
E1.25 Pulse input maximum frequency
0.0...50.0 kHz
50.0
0.1
Run
E1.26 Pulse input filter time
0.000...2.000 s
0.100
0.001
Run
E1.35 AI1 input mode
0: 0...20 mA
1: 4...20 mA
2: 0...10 V
3: 0...5 V
4: 2…10 V
2
–
Run
E1.40 AI2 input mode
1
–
Run
E1.38 AI1 gain
0.00...10.00
1.00
0.01
Run
E1.43 AI2 gain
0.00...10.00
1.00
0.01
Run
E1.60 Motor temperature sensor channel
0: Inactive
1: AI1 analog input
2: AI2 analog input
3: EAI1 analog input
4: EAI2 analog input
5: TSI input (only for IO
plus card)
0
–
Stop
E1.61 Broken wire protection
0: Inactive
1: Warning
2: Error
0
–
Stop
E1.68 Analog input curve setting
0...7
0
–
Run
E1.69 Analog input filter time
0.000...2.000 s
0.100
0.001
Run
E1.70 Input curve 1 minimum
0.0 %...[E1.72]
0.0
0.1
Run
E1.71 Input curve 1 minimum frequency
0.00...[E0.09] Hz
0.00
0.01
Run
E1.72 Input curve 1 maximum
[E1.70]...100.0 %
100.0
0.1
Run
E1.73 Input curve 1 maximum frequency
0.00...[E0.09] Hz
50.00
0.01
Run
54/91
Start-up
Rexroth Frequency Converter VFC
3610 / VFC 5610
Bosch Rexroth AG R912005518_Edition 16
Summary of Contents for VFC 3610
Page 1: ...Frequency Converter VFC 3610 VFC 5610 Series Edition 16 Quick Start Guide R912005518...
Page 6: ...IV Rexroth Frequency Converter VFC 3610 VFC 5610 Bosch Rexroth AG R912005518_Edition 16...
Page 96: ...90 91 Rexroth Frequency Converter VFC 3610 VFC 5610 Bosch Rexroth AG R912005518_Edition 16...
Page 97: ...Notes Rexroth Frequency Converter VFC 3610 VFC 5610 91 91...