Rexroth IndraDrive FCS01.1
Commissioning
10-1
DOK-INDRV*--FCS01*****-IB01_EN-P
10 Commissioning
The motor may only be started by a release signal after it the parameters
have been successfully set by qualified personnel.
WARNING
⇒
The frequency converter does not have a mains
switch. Thus, it is always energized when connected
to mains voltage. Accordingly, voltage may be
applied to a connected motor.
1.1 Basic
Settings
All frequency converters supplied by Bosch Rexroth are pre-programmed
by default for standard applications with 4-pole DS standard motors (of
identical power and voltage). When motors of other power ratings or pole
numbers are used, the information on the motor's type label must be
input in the P201...P207 parameters of the menu group >Motor data<.
Note:
All motor data can be set by means of the parameter P200.
After completed utilization of this function the parameter is
reset to
0 = no change
! The data is once loaded automatically
into the parameter P201…P209. Here, it can be compared
again to the data of the motor type label.
RECOMMENDATION:
To ensure smooth operation of the drive unit, it is necessary to set the
motor data as accurately as possible in accordance with the type label.
We specifically recommend automatic stator resistance measurement via
parameter P220.
To determine the stator resistance automatically, P220 must be set to = 1
and then confirmed with "ENTER". The value converted to the phase
resistance (in dependence on P207) is saved to parameter P208.
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......