9-16
Indications and Operation of the Function Modules
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Parameters of the Comfort Control Panel
The following main functions are assigned to the menu groups:
Menu group
No.
Main function
Indication
(P10xx):
Selection of the operating values and the display structure
Parameterization
(P11xx):
Programming of the connected frequency converter and all memory objects
Parameter administration (P12xx):
Copying and saving of whole parameter records from memory objects
Options
(P13xx):
Setting the functions of the comfort control panel, as well as of all automatic
processes
Fig. 9-14:
Main functions
Menu Group 'Indication'
Parameter
Setting value / description / note
P1001
Bus scan
This parameter starts a bus scan. During the process, a progress bar is shown in the display.
After a bus scan, the parameter is on "Off".
Depending on the result of this process, the comfort control panel will go to "ONLINE" or
"OFFLINE" operating mode.
P1002
FC selection
Selection of the current object for parameterizing/controlling.
The subsequent indication and operating measures relate to the selected object. In the
frequency converter selection list, only the devices identified during the bus scan are
available. The current object is indicated in the status line.
Value range: FC, S1 … S5
P1003
Indicator mode
Selection of the operating value indication of the comfort control panel
Standard: any 3 values next to each other List: any 3 values with unit, one below the other
Large indication: any 1 value with unit
P1004
Value for indication
Selection of an indication value for the actual value indication of the comfort control panel.
The selected value is set to the first position of an internal list of indication values.
Potential actual values for indication:
Actual frequency Voltage Current
Speed
Torque current
Command frequency
DC bus voltage
Actual bus value 1
P1005
Standardization factor
The first value of the indication list is multiplied by the standardization factor. If this
standardization factor is unequal "1", the unit is hidden in the indication.
Value range: -327.67 to +327.67; resolution 0.01
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......