The line shield must be applied in the bus connector. In case of installation in
the control cabinet, the line shield of the connected PROFIBUS line must be
connected to a shield bus using cable clips, if possible directly behind the cable
bushing. Use an appropriate shield terminal.
8.3.7
Connecting Lines to Tension Spring Connection Points
General Information
Connect the lines for peripheral equipment and voltage supply to the tension
spring connection points.
Shielded/unshielded lines
Unshielded lines are used for the digital inputs and outputs as well as for the
voltage supply. Shielded lines are connected to analog inputs and outputs.
AWG
Lines with an average wire gauge of 0.2 mm
2
to 1.5 mm
2
(AWG 24 – 16) can
be connected. These lines can conduct signals up to 250 V AC/DC and 5 A.
Connecting Unshielded Lines
Fig.8-9:
Connecting lines to tension spring connectors
Wire the connectors as required according to the application.
Proceed as follows to wire the connectors:
●
Strip the line to a length of 8 mm. Wiring is provided without core end
sleeves. However, core end sleeves may be used, if desired. In this case,
do ensure that the core end sleeves are properly crimped.
●
Put a screwdriver into the actuation slot of the corresponding terminal point
(figure
, A), so that the core can be inserted into the opening of the
spring. Insert the core (figure
, B). Pull the screwdriver out of the open‐
ing. This fixes the core. We recommend you to label the cores and terminal
points after the installation.
8.4
Maintenance
Regular maintenance
Include the following measures in the maintenance schedule:
Bosch Rexroth AG
DOK-CONTRL-IC*L25*****-PR03-EN-P
Rexroth IndraControl L25
54/69
Installation and Maintenance
Summary of Contents for IndraControl L25 CML...3N Series
Page 6: ...Bosch Rexroth AG DOK CONTRL IC L25 PR03 EN P Rexroth IndraControl L25 IV 69...
Page 22: ...Bosch Rexroth AG DOK CONTRL IC L25 PR03 EN P Rexroth IndraControl L25 20 69...
Page 30: ...Bosch Rexroth AG DOK CONTRL IC L25 PR03 EN P Rexroth IndraControl L25 28 69...
Page 44: ...Bosch Rexroth AG DOK CONTRL IC L25 PR03 EN P Rexroth IndraControl L25 42 69...
Page 58: ...Bosch Rexroth AG DOK CONTRL IC L25 PR03 EN P Rexroth IndraControl L25 56 69...
Page 66: ...Bosch Rexroth AG DOK CONTRL IC L25 PR03 EN P Rexroth IndraControl L25 64 69...
Page 68: ...Bosch Rexroth AG DOK CONTRL IC L25 PR03 EN P Rexroth IndraControl L25 66 69...
Page 71: ...Notes DOK CONTRL IC L25 PR03 EN P Rexroth IndraControl L25 Bosch Rexroth AG 69 69...