Examples for Operation of PZD Process Data Area
Example 1
The master communicates with the slave via PPO4. From
quest Data Frame in PKW Area_from master to slave" on page 196
12-50 "Process data PZD3 – PZD 10 values and function code settings" on
, we need to set status monitoring value corresponding to PZD3 -
PZD6 in parameters of Frequency Converter Fv.
If we need to start frequency converter for forward rotation at 50.00 Hz
(0×1388), and request PZD3 to reflect output current, PZD4 to reflect output
voltage, PZD5 to reflect DC bus voltage, PZD6 to reflect radiator tempera‐
ture, respective function codes are set as: [H0.04]=82; [H0.05]=67. Complete
PPO request and response messages are shown in
PZD process data area_request and response messages of PPO" on page
PZD1
PZD2
PZD3
PZD4
PZD5
PZD6
PPO request
message
CW
REF
0x0000
0x0000
0x0000
0x0000
0x0001
0x1388
PPO response
message
SW
ACT
0x0000
0x0206
0x02DD
0x0019
0x0002
0x1388
Fig.12-51:
Example 1 for PZD process data area_request and response messag‐
es of PPO
In this example, request and response data frame is the message
of frequency converter at stable operation. Actually, at the instant
start-up of the frequency converter, response data frame in PZD
area is “000× 0000 0001 0000 1369 0019” (× means rotation di‐
rection is not certain at the instant of activation).
Example 2
When the converter forward runs at 50 Hz, to stop the converter as parame‐
ter settings, please refer to example 1.
PZD1
PZD2
PZD3
PZD4
PZD5
PZD6
PPO request
message
CW
REF
0x0000
0x0000
0x0000
0x0000
0x0008
0x1388
PPO response
message
SW
ACT
0x0000
0x0000
0x0049
0x0013
0x0000
0x0000
Fig.12-52:
Example 2 for PZD process data area_request and response messag‐
es of PPO
Example 3
To reverse start the converter at 50 Hz, please refer to example 1 for param‐
eter settings.
PZD1
PZD2
PZD3
PZD4
PZD5
PZD6
PPO request
message
CW
REF
0x0000
0x0000
0x0000
0x0000
0x0005
0x1388
DOK-RCON02-FV*********IB01-EN-P
Rexroth Frequency Converter Fv
Bosch Rexroth AG
205/219
Communication Protocols
Summary of Contents for Fv Series
Page 20: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 18 219...
Page 30: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 28 219...
Page 34: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 32 219...
Page 52: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 50 219...
Page 58: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 56 219...
Page 144: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 142 219...
Page 164: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 162 219...
Page 180: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 178 219...
Page 214: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 212 219...
Page 216: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 214 219...
Page 220: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 218 219...
Page 221: ...Notes DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv Bosch Rexroth AG 219 219...