Group S2: Motor and Encoder Parameters
S2.00
Rated motor frequency
Factory default 50.00 Hz
Setting range
8.00 − 400.00 Hz
Minimum unit
0.01 Hz
S2.01
Rated motor rotation speed
Factory default 1440 rpm
Setting range
1 − 30000 rpm
Minimum unit
1 rpm
S2.02
Rated motor power
Factory default Depends on model
Setting range
0.4 − 1000.0 kW
Minimum unit
0.1 kW
S2.03
Rated motor voltage
Factory default Depends on model
Setting range
0 − 480 V
Minimum unit
1 V
S2.04
Rated motor current
Factory default Depends on model
Setting range
0.1 − 1000.0 A
Minimum unit
0.1 A
Set parameters [S2.00] − [S2.04] according to the nameplate of the motor.
The rated motor power should be the same or one class lower than the rated
power of the converter. Otherwise the performance could be affected.
S2.05
Stator resistance factor
Factory default Depends on model
Setting range
0.00 % − 50.00 %
Minimum unit
0.01 %
S2.06
Rotator resistance factor
Factory default Depends on model
Setting range
0.00 % − 50.00 %
Minimum unit
0.01 %
S2.07
Leakage inductance factor
Factory default Depends on model
Setting range
0.00 % − 50.00 %
Minimum unit
0.01 %
S2.08
Mutual inductance factor
Factory default Depends on model
Setting range
0.0 % − 2000.0 %
Minimum unit
0.1 %
S2.09
No-load current
Factory default Depends on model
Setting range
0.0 − 1000.0 A
Minimum unit
0.1 A
S2.10
Parameter auto-tuning
Factory default 0
Setting range
0, 1, 2
Minimum unit
1
The motor parameters ([S2.00] − [S2.04]) must be set before using ‘Parame‐
ter auto-tuning’[S2.10]. The necessary information can be found on the
nameplate of the motor.
●
[S2.10]=0: No action
●
[S2.10]=1: Auto tuning with running motor
–
‘Auto tuning with running motor’ can ensure the dynamic control
performance of the converter. Before using ‘Auto tuning with run‐
ning motor’, any load must be removed from the motor. Parame‐
ters [S2.05] − [S2.09] will be updated during auto tuning.
●
[S2.10]=2: Auto tuning with static motor
–
Parameters [S2.05] − [S2.07] will be updated during auto tuning.
Bosch Rexroth AG
DOK-RCON02-FV*********IB01-EN-P
Rexroth Frequency Converter Fv
104/219
Parameter Settings
Summary of Contents for Fv Series
Page 20: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 18 219...
Page 30: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 28 219...
Page 34: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 32 219...
Page 52: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 50 219...
Page 58: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 56 219...
Page 144: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 142 219...
Page 164: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 162 219...
Page 180: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 178 219...
Page 214: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 212 219...
Page 216: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 214 219...
Page 220: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 218 219...
Page 221: ...Notes DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv Bosch Rexroth AG 219 219...