12.2.4 Digital Output Configuration
Please read through the information on 'Wiring diagram' and 'Terminals' before
configuration of 'Digital output', see
chapter 8 "Frequency Converter Wiring" on
chapter "Digital outputs" on page 56
respectively. To configure this
output DO1, take the following steps:
Step 1: Select the output signal
Code
Name
Setting range
Default
Min.
Attri.
E2.01 DO1 output setting
0...99
0
–
Stop
E2.15 Relay 1 output selection
0...99
1
–
Stop
●
0: Converter ready
After powering on, if no error occurs and there is no run command or output
active indication, the frequency converter is ready for running.
●
1: Converter running
The output is active when the frequency converter is running and has fre-
quency output (including 0.00 Hz).
●
2: Converter DC-braking
The output is active when the frequency converter is in Start- or Stop- DC
braking, see
chapter "DC-braking before start" on page 155
braking during deceleration to stop" on page 160
.
●
3: Converter running at zero speed
The output is active when the frequency converter is running at zero speed.
There is no output for this selection during dead zone time of rota-
tion direction change.
●
4: Speed arrival
See
chapter 12.7.2 "Frequency Arrival" on page 175
●
5: Frequency level detection signal (FDT1)
●
6: Frequency level detection signal (FDT2)
chapter 12.7.3 "Frequency Level Detection" on page 177
.
●
7: Simple PLC stage complete; 8: Simple PLC cycle complete
chapter 12.8.4 "Stop and Pause Simple PLC Control" on page 183
.
●
10: Converter undervoltage
The output is active when DC-bus voltage is lower than 230 VDC (1P 200 VAC
models) / 430 VDC (3P 400 VAC models). The output will be inactive when
DC-bus voltage resumes and becomes stable.
In addition, this digital output will be activated by any soft start error.
EFC x610 Series
Bosch Rexroth AG
Functions and Parameters
DOK-RCON03-EFC-X610***-IT05-EN-P
111/389