12.2 Input and Output Terminals Configuration
12.2.1 Digital Input Configuration
5 multi-function digital inputs are available with PNP and NPN wiring.
Code
Name
Setting range
Default
Min.
Attri.
E1.00
X1 input
0...46
35
–
Stop
E1.01
X2 input
36
–
Stop
E1.02
X3 input
0
–
Stop
E1.03
X4 input
0
–
Stop
E1.04
X5 input
0...47
0
–
Stop
●
0: Inactive
●
1: Multi-speed control input 1
●
2: Multi-speed control input 2
●
3: Multi-speed control input 3
●
4: Multi-speed control input 4
16 multi-speeds are available by combination of 4 terminals, see
the setting frequency by multi-speed function" on page 136
.
●
10: Acceleration / deceleration time 1 activation
●
11: Acceleration / deceleration time 2 activation
●
12: Acceleration / deceleration time 3 activation
Used to switch between 8 groups of acceleration / deceleration time, see
ter 12.4.3 "Acceleration and Deceleration Configuration" on page 142
●
15: Freewheeling stop activation
'Freewheeling stop activation' generates a stop command and forces the fre-
quency converter to freewheel to stop regardless of the stopping mode con-
figured by E0.50.
●
16: Stop DC-braking activation
This function is used when stopping mode is set with [E0.50] = '0: Decelerat-
ing stop'.
See
chapter 12.5.5 "Stop Behavior Setting" on page 159
●
20: Frequency Up command
●
21: Frequency Down command
●
22: Up / Down command reset
Used to change the output frequency, see
chapter "Adjust the setting frequency
by digital input Up / Down command" on page 134
●
23: Torque / speed control switch
●
25: 3-wire control