Once your air door has been installed, it will be necessary to adjust the air  w. With the door
all the way open, turn the unit on “High,”, 

 the air stream split by holding a square piece of

light weight cloth by its corners in the stream of air and move it back and forth (inside and
outside), approximately 6" from the 

r. The cloth will show the 

 pattern and will allow

you to make the proper adjustments to the directional vane for maximum 

y. If your unit

is properly adjusted, the split should be just outside the threshold with the top of the air
current being about 2' from the 

r.

The air 

 angle can easily be adjusted by turning the directional vane using your hand. No

tools are needed. The angle of the air 

 depends on the height of the door and is normally

between 5° and 10°. 
It should never exceed 20°.

If the air current is too severe or exceeds the 2' level, you can turn the power switch to “Low.”

ADJUSTMENTS

MOUNTING

2

Attaching the Air Door to the Mounting Plate

After the Mounting Plate has  been securely attached  the air door must be attached to the mounting

 

plate. 

1. Lift the unit  into place

with the outlet nozzle
at the bottom and the
intake grill facing 
away from the
mounting plate.

2. Slip the unit over the

mounting plate lip.

3. Gently push the

unit down so it
rests on the lip.

4. Replace all the

mounting plate
screws and 
tighten.

4. Plug the unit

into a properly
grounded 3
prong, 120 V
electrical outlet.

Directional

Vane

Intake

Grill

Outlet

Nozzle

Mounting

Plate

Lip

Mounting

Plate

Screws

2' Air Flow

Split

SPECIAL APPLICATIONS

Mounting Above the Ceiling

1. Mount the Air Door using the “Wall Mounting” method (see page 1).
2. The intake vent should be at least 36'' away from the outlet vent.
3. It is extremely important to fabricate the intake ductwork so it encapsulates the

entire intake grill. 

Figure  5.

1. Mount the Air Doors using 

 

the  

mounting   

method

(see page 1).

2. The space between units

should be between 1'' and 2''.

Figure  6.

Mounting Tandem Units

Figure  5

Intake

Vent

Intake

Ductwork

CEILING

DOORWAY

OPENING

Outlet

Vent

DOORWAY

OPENING

1''-  2''

AT LEAST 36''

Figure  6