background image

Intr

oduction

When connected to the RE5000 Contr

ol Unit, the

RE5000AD may be used to communicate up to three

separate message phrases (usually relating to Intruder,

Fire and Medical Alert conditions).  The Dialler Tamper

Switch may be connected to Zone 6 on the RE5000CU

if tamper protection is required.

The Communicator Interface Cable connection supplied

with the RE5000 Control Unit allows simple connection

between the Control Unit and Dialler.

THE FOLLOWING MUST BE READ IN CONJUNCTION

WITH THE RE5000AD (TSD1+) INSTALLATION AND

OPERATING INSTRUCTIONS SUPPLIED AND THE

RE5000 INSTALLATION AND OPERATING MANUAL.

CONNECTING THE RE5000AD TO

THE RE5000 CONTROL UNIT.

1.

Disconnect all power (Mains and Back-up Battery)

from the Control Unit before making any connections.

2. Plug the Interface Cable into the Control Unit plug

and connect the lead to the Dialler as shown.

3. Ensure that all cabling is connected correctly and that

all unused cores of the Interface Cable are cut back or

insulated to prevent accidental short circuits.

4. Connect the Telephone Cable to the Dialler - (see

Dialler Installation Instructions).

5. Reconnect power to the Control Unit and proceed to

programme and test the Dialler in accordance with

the Dialler Operators Manual.

Note:

If your RE5000CU is supplied with an 8-Cor

e

interface cable, please call our Technical

Helpline for connection advice.

Loudspeaker

Tamper

Switch

Microphone

Set Trig Polarity 

Link to '+' for 

negative trigger 

to suit RE5000CU 

trigger output

Telephone Line
Connection Terminals

Factory

Restart Pins

Factory Restart

0/P1
0V

+12V

TRIGGER

POLARITY

A    B    A1  B1

TELEPHONE CONNECTIONS

TAMP    ABORT  C        B        A

TRIG INPUT

TSD1

+

Optional Dialler Tamper Connection

To Zone 6 Hard Wired Zone Input

on RE5000CU

9-Core Interface Cable

Red   +12V

Blue

Grey

Brown

Orange

Yellow

Green

Mauve

White

AC Power
Failure
– 0V

Arm

Disarm

Low Batt

Intruder

Fire

Medical Alert/
Personal Attack

Control Unit

Terminal Block

Plug-in Connector to Control Unit PCB

N.O.

COM

N.C.
V+

GRD

Zone 6

Siren

Charge

Tamper

Communicator

Interface Cable

Connection

Connections for 9-Cor

e Interface Cable

9

CORE

Using the RE5000AD with a

RE5000

System Contr

ol Unit

Installation and Operating Instr

uctions