Hourly Check
Supervisories,
every hour
Maintenance
Needed
Temporal 3
(Loud)
Yellow
(Pulsing)
Supervisories Not
Sent
Replace Unit
Specifications
Approval:
UL217 Self-Contained Fire Alarm Device
Smoke Sensitivity:
1.31 – 2.28 %/ft (UL 217)
0.11 – 0.165 dB/m (EN54-7)
Smoke Sensing Technology:
Photoelectric
Heat Alarm Point:
135 – 149 F (UL 521)
Alarm Sound:
Temporal Three
Replacement Battery:
Panasonic CR123A
Temperature Range:
32 to 120 F (Long Term)
Humidity:
10 – 85% Relative Humidity
Housing dimensions:
4.7 inch diameter, 2.1 inch high
Design & Manufacture:
Resolution Products, Inc.
Specifications subject to change without notice.
Pictures
RE312_DSC-Compat_Smoke_Instructions.doc
Page
2
of
3
22-Dec-14
24-Hour Tech Support Line: (715)808-0164
www.ResolutionProducts.com
TEST Button
LED
Battery
+
Smoke Sensing
Element
Mounting
Tabs
Tamper
Summary of Contents for RE312