background image

V8205, VR8205 DIRECT IGNITION COMBINATION GAS CONTROLS

7

69-0329—05

1.

Turn off gas supply.

2.

Set the thermostat or controller above room tem-

perature to call for heat.

3.

Watch for ignition spark or for glow at hot surface 

igniter either immediately or following prepurge. 

See DI module specifications.

4.

Time length of igniter operation. See DI module 

specifications.

5.

After the module locks out, open manual gas cock 

and make sure no gas is flowing to burner.

6.

Set the thermostat below room temperature and 

wait one minute.

7.

Operate system through one complete cycle to 

make sure all controls operate properly.

Service

WARNING

Fire or Explosion Hazard

Can cause property damage, severe injury, or 

death.

Do not disassemble the gas control; it contains 

no replaceable components. Attempted 

disassembly or repair can damage the gas 

control.

CAUTION

Do not apply a jumper across (or short) the valve 

coil terminals, even temporarily. Doing so can 

burn out the heat anticipator in the thermostat or 

damage the DI module.

If Main Burner Will not Come On with Call 
for Heat

1.

Make sure the gas control knob is in the ON posi-

tion.

2.

Adjust the thermostat several degrees above room 

temperature.

3.

Using an ac voltmeter, check for voltage across MV  

terminals at gas control.

4.

If voltage is not present, check control circuit for 

proper operation.

5.

If proper control circuit voltage is present, replace 

gas control.

Instructions To The Homeowner (For 
Your Safety, Read Before Lighting)

WARNING

Fire or Explosion Hazard

If you do not follow the warnings below and the 

lighting instructions exactly, a fire or explosion 

can result with property damage, personal injury 

or loss of life.

1. Before lighting, smell around the appliance 

area for gas. If the appliance uses LP (bottled) 

gas, be sure to smell next to the floor because 

LP gas is heavier than air. If you smell gas, 

immediately shut off the manual valve in the 

gas piping to the appliance or, on LP, at the 

tank. Do not try to light any appliance. Do not 

touch  any  electrical  switch  or  use  the 

phone. Leave the building and call your gas 

supplier. If your gas supplier cannot be 

reached, call the fire department.

2. Do not force the gas control knob on the appli-

ance. Use only your hand to turn the gas con-

trol knob. Never use any tools. If the knob will 

not operate by hand, replace the control using 

a qualified service technician. Force or 

attempted repair may result in fire or explosion.

3. The gas control must be replaced if it has been 

flooded with water. Call a qualified service 

technician.

4. The gas control is a safety device. It must be 

re-placed in case of any physical damage such 

as bent terminals, missing or broken parts, 

stripped threads, or evidence of exposure to 

heat.

IMPORTANT:

Follow the operating instructions provided by 

the manufacturer of your heating appliance. The 

information below will be of assistance in a typ-

ical control application, but the specific controls 

used and the procedures outlined by the manu-

fac-turer of your appliance may differ, and 

require spe-cial instructions.

To Turn On Furnace

STOP: Read the safety information above

1.

The lighting sequence on this appliance is auto-

matic; 

Do not attempt to manually light the main 

burner.

2.

If the furnace does not come on when the thermo-

stat is set several degrees above room tempera-

ture, set the thermostat to the bottom of its range 

to reset safety control.

3.

Remove burner access panel if provided on your 

appliance.

4.

Turn the gas control knob (Fig. 4) clockwise 

 to 

OFF.

5.

Wait five minutes to allow any gas in the combus-

tion chamber to vent. If you smell gas in the appli-

ance area or near the floor in an LP installation, 

immediately shut off the manual valve in the gas 

piping to the appliance or, on LP, at the tank. Don’t 

touch any electrical switch or use the phone. Leave 

the building and call your gas supplier. If your gas 

supplier cannot be reached, call the fire depart-

ment. Failure to do so may result in fire or explo-

sion.

Summary of Contents for V8205

Page 1: ...s noted Approvals American Gas Association design certificate L2025006 Canadian Gas Association design certificate L2025006 Australian Gas Association design certificate 4214 Approved for Delta C applications INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a haz ardous condition 2 Check the ratings given in the ...

Page 2: ...t no 394588 to convert from LP to natural manufactured gas Controls with step opening regulators cannot be converted Install Adapters to Control If adapters are to be installed on the gas control mount them as follows Flanges 1 Choose the appropriate flange for your application 2 Remove seal over gas control inlet or outlet 3 Make sure the O ring fits into the flange groove If the O ring is not at...

Page 3: ...erted too deeply refer to Table 4 4 Apply a moderate amount of good quality pipe com pound do not use Teflon tape to pipe only leaving two end threads bare On LP installations use compound resistant to LP gas See Fig 3 5 Remove seals over control inlet and outlet if neces sary 6 Connect pipe to control inlet and outlet Use wrench on the square ends of the control If a flange is used place wrench o...

Page 4: ...d other con trols as required 2 Connect control circuit to gas control terminals See Fig 4 6 and 7 3 Adjust thermostat heat anticipator to 0 50A rating stamped on valve operator NOTE Use leadwires with insulated terminals Fig 6 Wiring connections for 24 volt control in S87 direct ignition system APPLY WRENCH FROM TOP OR BOTTOM OF GAS CONTROL TO EITHER SHADED AREA WHEN FLANGE IS NOT USED APPLY WREN...

Page 5: ...n the appliance nameplate or manufacturer recommended burner orifice pressure for the size orifice s used Make certain the primary air supply to the main burner is properly adjusted for complete combustion refer to the appliance manufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCKING THE GAS METER Make certain there is no gas flow through the meter other than to the appliance being checked O...

Page 6: ...ure to the control 5 STEP OPENING PRESSURE REGULATORS ONLY Carefully check burner lightoff at step pressure Make sure burner lights smoothly and without flashback to orifice Make sure all ports remain lit Cycle burner several times allowing at least 30 seconds between cycles for regulator to resume step function Repeat after allowing burner to cool Readjust full rate outlet pressure if necessary t...

Page 7: ... manual valve in the gas piping to the appliance or on LP at the tank Do not try to light any appliance Do not touch any electrical switch or use the phone Leave the building and call your gas supplier If your gas supplier cannot be reached call the fire department 2 Do not force the gas control knob on the appli ance Use only your hand to turn the gas con trol knob Never use any tools If the knob...

Page 8: ...5422 1 800 468 1502 69 0329 05 M S Rev 09 20 Printed in United States 6 If you don t smell gas turn knob on gas control counterclockwise to ON 7 Replace the burner access panel 8 Reset the thermostat to the desired temperature 9 If the burner does not come on when the room temperature is below thermostat setting turn gas control knob to OFF and contact a qualified ser vice technician for assistanc...

Reviews: