Mounting position

 

The gas control can be mounted 0 to 90

in any direction from 

the upright position i.e. from the position when the knob is on 
top.

 

Main gas connection

 

•  Take care that dirt cannot enter the gas control during 

handling.

 

•  Use a clean taper fitting with thread according to BS 21 or 

a piece of new, properly reamed pipe, free from swarf.

 

•  Do not tighten the pipe or pipe fitting too far (see table 

below). Otherwise valve distortion and malfunction could 
result.

 

 

Pipe size

 

Max. length of pipe thread

 

1

/

2

 

18.6 mm

 

•  Apply a moderate amount of good quality thread 

compound to the pipe or fitting only, leaving the two end 
threads bare. PTFE tape may be used as an alternative.

 

•  Ensure the gas flows in the same direction as the arrow on 

the bottom of the gas control.

 

Pilot gas connection

 

•  Square off the end of tubing and remove burrs.

 

•  Slip compression fitting over tubing.

 

•  Insert tubing into gas control housing until it bottoms, slide 

fitting into place and turn finger tight.

 

•  Use a wrench to tighten fitting about 

3

/

turn beyond finger

 

tight to make a pressure tight joint. 

Do not use jounting

 

compound.

 

•  Connect other end of tubing to pilot burner according to the 

pilot burner manufacturer’s instructions.

 

    

CAUTION 

Do not bend tubing at gas control after compression 
fitting has been tightened, as this may result in gas 
leakage at the connection.

 

Thermocouple connection

 

The gas control has an electrical thermocouple connection 

and must therefore be kept clean and dry; thread compound 
should never be applied to it. Tighten only 

1

/

turn beyond 

finger tight in order to give good electrical connection. When

 

routing the thermocouple tubing, do not bend it too sharply 
(min. radius 2.5 mm).

 

Perform gas leak test

 

 

    

WARNING 

FIRE OR EXPLOSION HAZARD CAN CAUSE 
PROPERTY DAMAGE, SEVERE INJURY OR DEATH

 

•  With the main burner in operation, paint all pipe joints 

(including adapters) and gas control inlet and outlet with 
with a rich soap and water solutionan approved leak 
detection fluid.

 

•  If another gas leak is detected, tighten adapter screws, 

joints and pipe connections.

 

•  Replace the part if gas leak can not be stopped.

 

 

    

CAUTION 

Keep soap and water solution away from electrical 
connections.

 

 

Electrical connection

 

    

CAUTION 

Switch off power supply before making electrical 
connections.

 

Take care that wiring is in accordance with local 
regulations.

 

Follow the instructions supplied by the appliance 
manufacturer. If there are no such instructions, 
see fig. 2. and 3. for typical wiring diagrams.

 

Use lead wire which can withstand 105 

_

C ambient. 

The electric on/off servo operator is provided with:

 

both 6.3 mm terminals suitable for 6.3 mm receptacles (e.g. 
”Series 250” AMP fasteners) and screw terminals,

 

or provided with:

 

quick connect terminals suitable for 6.3 mm receptacles 
(e.g. ”Series 250” AMP fasteners) or for a female connector 
according DIN 43650.

 

 

Wiring 220/240 V, 50 Hz (see fig. 2.)

 

Install the line voltage thermostat (or controller) and other 
controls as required.

 

Provide hard PVC boots on the AMP terminals to prevent 
touching of life terminals. When fitting a cover a Heyco

type 

strain relief should be used.

 

 

Wiring 24 V, 50 Hz (see fig. 3.)

 

Install the transformer, low voltage thermostat and other 
controls as required.

 

Adjust heat anticipater to the A rating as stamped on the gas 
control.

 

Check for gas leaks with a rich soap and water 
solution any time work is done on a gas control.

 

Gas leak test

 

•  Paint all pipe connections upstream of the gas control with 

with a rich soap and water solution.Bubbles indicate a gas 
leak.

 

•  If a gas leak is detected, tighten the pipe connection.

 

•  Stand clear while lighting the main burner to prevent injury 

caused from hidden gas leaks, which could cause  flasback

 

 
 
 

Line voltage

 

Limit control

 

Thermostat

 

 
 
 
 
 

 

 
 
 
 
 
 

 

Valve operator

 

in the appliance vestibule. Light the main burner. 

Fig. 2. Wiring 220/240 V, 50 Hz

 

Summary of Contents for V4600

Page 1: ...electric safety device according to european standards EN 125 and EN 126 and closes off the gas supply to both main burner and pilot burner The electric on off servo operator is an automatic shut off valve of class J according to EN 161 and closes off the gas supply to the main burner SPECIFICATIONS Models V4600 serie 220 240 V 50 Hz V8600 serie 24 V 50 Hz Suffix E fast opening and throttle valve ...

Page 2: ...uding cover IP 40 with cover or plug IP 44 with plug according to DIN 43650 INSTALLATION IMPORTANT Take care that installer is a trained experienced service person Turn off gas supply before starting installation Disconnect power supply to prevent electrical shock and or equipment damage Do not remove seals over gas control inlet and outlet until the device is ready to be installed Working voltage...

Page 3: ...With the main burner in operation paint all pipe joints including adapters and gas control inlet and outlet with with a rich soap and water solutionan approved leak detection fluid If another gas leak is detected tighten adapter screws joints and pipe connections Replace the part if gas leak can not be stopped CAUTION Keep soap and water solution away from electrical connections Electrical connect...

Page 4: ...0 Volt Pressure tap The gas control is provided with a pressure tap of 9 mm outer diameter at inlet and outlet side When checking the pressure undo the screw a half turn and slip tube over nipple Ensure that screw is retightened after making test Pilot flame adjustment see fig 1 The gas control is packed for shipment with pilot flow at maximum Refer to the pilot burner manufacturer s instructions ...

Reviews: