R4184D; R8184G,M,N,P PROTECTORELAY® OIL PRIMARY CONTROLS

69-0618—04

2

Fig. 2. Wire and mount 150°F (66°C) maximum ambient 

temperature oil primary control.

Line Voltage Wiring Connections

Wiring must comply with all local codes and ordinances.

1.

Be sure all line voltage connections are in a wiring 

enclosure such as a junction box or the appliance 

wiring compartment.

2.

Make the line voltage connections as shown in 

Fig. 3 through 9.

3.

Splice the leads with solderless connectors.

IMPORTANT

Do not exceed the load ratings listed in Table 1.

4.

Thread the line voltage cad cell leads through the 

hole on the bottom of the low voltage terminal 

strip. See Fig. 1 or 2.

Alarm Contact Rating: 

25 VA at 24V, 50/60 Hz.

Mounting

1.

If necessary, use the control as a template to mark 

and drill new mounting holes.

2.

Mount the control using no. 8 screws (obtained 

locally).

Low Voltage Wiring Connections

After mounting, make low voltage connections to screw 

terminals as follows:

• R4184D—connect the cad cell leads to the F-F 

terminals. See Fig. 3.

• R8184G—connect the cad cell leads to the F-F 

terminals and thermostat leads to the T-T terminals. 

See Fig. 4 and 5.

• R8184M—connect the cad cell leads to the F-F 

terminals and connect remaining low voltage wiring 

as shown in Fig. 6.

NOTE:

The Y and G terminals are not connected to the 

internal circuitry of the R8184M. The Y and G 

terminals are provided to simplify the connec-

tions of the cooling equipment.

• R8184N—connect the cad cell leads to the F1-F2 

terminals and thermostat leads to the T1-T2 

terminals. See Fig. 7.

• R8184P hydronic hookup. Connect the cad cell leads 

to the F-F terminals. See Fig. 6.

• R8184P warm air hookup. Connect the card cell leads 

to the F-F terminals and the thermostat leads to the 

R-W terminals. See Fig. 9.

Fig. 3. Typical hookup for R4184D.

CAD 

CELL LEADS

LINE 

VOLTAGE LEADS

MOUNTING

SCREW HOLE

RED RESET

BUTTON

VENTILATION 

SLOTS

4 x 4 JUNCTION

BOX

HOLE OR KNOCKOUT FOR

CAD CELL LEADS

LOW VOLTAGE

TERMINAL STRIP

1 STRIP WIRES 3/8 in. (9.5 mm); INSERT FROM SIDE, ABOVE OR BELOW.

ATTACH WITH NO. 8 MOUNTING SCREWS (OBTAINED LOCALLY).

VENTILATION SLOTS ONLY AVAILABLE ON SELECT MODELS.

1

2

2

3

3

M1642C

Table 1. Load relay contact ratings.

Model

120 Vac

240 Vac

AFL

ALR

AFL

ALR

R4184D; R8184G,M,N 

(45-second models)

7.4A 44.4A 3.7A 22.2A

R8184P (15-, 30-, 45-

second models)

7.4A 44.4A NA

NA

R8184G (15- and 

30-second models)

10.0A 60.6A 5.0A 30.0A

JUNCTION BOX

BLACK

ORANGE

WHITE

R2

SAFETY
SWITCH

M715A

POWER SUPPLY.  PROVIDE DISCONNECT MEANS 
AND OVERLOAD PROTECTION AS REQUIRED.

CAD 
CELL

F

F

R4184D PROTECTORELAY   CONTROL

SAFETY 
SWITCH 
HEATER

1K

TRIAC

BILATERAL 
SWITCH

CAPACITOR

R1

1K2

1K1

1

1

IGNITION

LIMIT

THERMOSTAT

OIL VALVE
(OPTIONAL)

BURNER
MOTOR

L2

L1 

(HOT)

®

Summary of Contents for Protectorelay

Page 1: ...defined in UL 296 The valve on delay and blower off delay in this control are only intended to help establish draft and reduce oil after drip related problems INSTALLATION When Installing This Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a haz ardous condition 2 Check the ratings given in these instructions to make sure the integrated furnace...

Page 2: ...n in Fig 6 NOTE The Y and G terminals are not connected to the internal circuitry of the R8184M The Y and G terminals are provided to simplify the connec tions of the cooling equipment R8184N connect the cad cell leads to the F1 F2 terminals and thermostat leads to the T1 T2 terminals See Fig 7 R8184P hydronic hookup Connect the cad cell leads to the F F terminals See Fig 6 R8184P warm air hookup ...

Page 3: ...ALS AND CONNECT LINE VOLTAGE THERMOSTAT IN SERIES WITH LIMIT CONTROLLER 2 2 2 1 IGNITION LIMIT LINE VOLTAGE THERMOSTAT OIL VALVE OPTIONAL BURNER MOTOR L2 L1 HOT JUNCTION BOX THERMOSTAT BLACK ORANGE WHITE RED RED R2 SAFETY SWITCH SAFETY SWITCH TO REMOTE ALARM CIRCUIT M5172A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TO USE R8184 WITH LINE VOLTAGE CONTROLLER JUMPER T T...

Page 4: ...WHITE ORANGE BLACK JUNCTION BOX IGNITION OIL VALVE BURNER LIMIT L1 HOT L2 1 1 JUNCTION BOX THERMOSTAT BLACK ORANGE WHITE R2 SAFETY SWITCH M717A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TO USE R8184N WITH LINE VOLTAGE CONTROLLER JUMPER T1 T2 TERMINALS AND CONNECT LINE VOLTAGE THERMOSTAT IN SERIES WITH LIMIT CONTROLLER CAD CELL F1 T1 T2 F2 R8184N PROTECTORELAY CONTRO...

Page 5: ...e until a call for heat ends 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 IGNITION TRANSFORMER CAN BE CONNECTED TO VALVE OR BURNER MOTOR 3 OMIT ON SYSTEMS WITHOUT POWER VENTING 4 JUMPER R W RED BLACK VIOLET WHITE ORANGE L1 HOT F L2 LINE 1 3 2 3 M10022 OIL VALVE AIR FLOW SWITCH AQUASTAT CONTROLLER BURNER MOTOR IGNITION TRANSFORMER VENTER MOTOR CAD CELL F R W RC Y G ...

Page 6: ... Only a trained experienced service technician should perform the troubleshooting procedure 2 This control contains no field replaceable parts Do not attempt to take it apart Replace the entire control if operation is not as described Preliminary Steps 1 Check the wiring connections and power supply Make sure power is on to the controls burner motor and ignition transformer 2 Make sure the limit c...

Page 7: ...R4184D R8184G M N P PROTECTORELAY OIL PRIMARY CONTROLS 7 69 0618 04 ...

Page 8: ...o Technologies Inc All rights reserved This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Douglas Drive North Golden Valley MN 55422 1 800 468 1502 69 0618 04 M S Rev 06 20 Printed in United States ...

Reviews: