resideo 5800PIR-OD2 Installation And Setup Manual Download Page 3

-3- 

 

DIP Switches 

There are four DIP switches that control the LED, transmitter contact input, Transmission Lockout, and Anti-Masking. 

 

Default values shown

 

 

 

DIP 1 - LED 
DIP 2 

– Normally Closed or Open 

DIP 3 

– Transmission Lockout 

DIP 4 

– Anti-Masking

 

 

DIP 1 - 

When enabled, the red LED will always reflect the detector’s status for alarm and trouble and will illuminate through the lens.  

When disabled, it will only illuminate for its Warm-up period and Walk Test Mode. 

o

 

Warm-Up Period 

– Blinks for 60 seconds or less. 

o

 

Alarm 

– Lights for 2 seconds 

o

 

Mask Detection 

– Blinks 3 times and repeats until condition is restored. 

o

 

Blinks for 5 seconds when Walk Test expires. 

 

DIP 2 

– Selects whether the alarm/trouble output to the transmitter will be normally open or normally closed.  This needs to stay in 

the N.C. position (default). If it is set to N.O., the fault/restore signals for alarms/troubles may operate backwards.  

 

DIP 3 

– Selects 120 seconds (2 minutes) or 5 seconds Transmission Lockout.  This is how much time must pass from the time it was 

activated to when it can be activated again.  This timeout option helps save battery life. 

 

DIP 4 

– Enables or disables Anti-Masking.  When enabled and it detects a masking condition it will generate a trouble.

  

 

 
Detection Masking 

Detection masking allows you to block certain parts of the lens to prevent nuisance alarms from objects such as bushes.  When any part of the 
lens is masked, the detector will not be able to detect any movement within the masked segments. 

1. 

Use a 
screwdriver, 
carefully pry 
on all four 
locking tabs 
to remove 
the lens 
holder. 

 

2. 

Identify the segments on the lens to be masked. 

3. 

Then, apply the adhesive masking strip(s) on 
the inside of the lens to mask the desired 
segments. 

      

 

4. 

Last, reassemble the lens to the lends 
holder and to the covers. 

       

 

 

Program the Control Panel 

The transmitter's 7-digit serial number and loop number (Loop 1) must be programmed in the zone along with Input Type 3 (RF Supervised), 
and the appropriate response type for the application.  Refer to the control panel’s instructions for further details on zone programming. 

NOTE: 

 The serial number and loop number can be programmed by either manually entering them in the zone program or by learning it in via 

wireless transmission by walking across the coverage area, activating the detector.  Make sure it is not in the 5 second or 2-minute 
transmission lockout, else it will not activate until after the lockout time expires. 
 

Mask Learn Mode and Walk Test 

When the cover is closed, two things happen:   
1.  The detector starts Mask Learn Mode for 1 minute with a 10 minute Anti-Mask Test Mode afterwards.  Learn Mode means it learns what 

normal objects will be within 3.3 ft (1 m) of it inside its Coverage Area so it will know the difference between a normal object and a masking 
object.  Do NOT leave any object within 3.3ft (1 m) from the detector.  During test mode, it will send a trouble after 20 seconds of being 
masked, whereas after test mode, it takes 3 minutes to go into trouble.  It uses Active Infrared technology and constantly monitors the 
signal strength of the IR beam’s reflection.  When the lens surface is covered by an object such as a piece of paper, the strength of the IR 
beam reflection increases, then, the detector initiates a trouble condition. 

2.  Walk Test Mode is automatically enabled for 3 minutes.  Walk test the detector to ensure that it will detect movement where desired and 

that it is operating correctly with the alarm system.   

 

 

 

 

 

Reviews: