REOVIB MFS 268 UL/CSA
Operating Instructions
7
ELEKTRONIK
7.0 Settings
After checking the correct operation of the controller in conjunction with the vibratory feed system it is
advisable to restrict the user to feeder throughput settings only.
Setting the feeder throughput:
Press the P key twice and adjust the throughput with the cursor keys (Code C. 000).
Parameter:
Code
Factory set-
ting:
Entry
Code:
Vibratory feeder
•
Amplitude (throughput)
0...100 %
A.
0 %
000, 002
The following variable parameters are available for setting up the feed system
Parameter:
Display Factory setting: Entry Code:
Vibratory feeder
•
Amplitude (throughput))
0...100 %
A.
0 %
000, 002, 020,
096
•
Maximum control limit (U
max
)
5...100 %
P.
90 %
008, 020, 096
•
Vibrating frequency
30...140 Hz
(5...300 Hz)
F.
100 Hz
008, 020
040, 096,
•
Soft start ramp up
0...60 Sec.
/.
0.1 Sec.
020, 096
•
Soft stop ramp down
0...60 Sec.
\.
0.1 Sec.
020, 096
•
Switch to external set point
0 / I
E.S.P.
0
003
•
Set point 0(4)...20 mA
0 / I
4.20
0
003
•
Potentiometer set point
0 / I
POT.
0
003
•
Coarse / Fine control
0 / I
S.P.2.
0
003
•
Invert enable
0 / I
-En.
0
003
•
Pulse feed
0 / I
HOP.
0
004, 064
•
On time delay (only if HOP. = I)
0…60 Sec.
H.
1.0 Sec.
004, 064
•
Off time delay (only if HOP. = I)
0…60 Sec. h
1.0 Sec.
004 ,064
•
Invert hopper sensor (not active)
0 / I
-Ho.
0
004, 064
Regulation (with sensor)
•
Switch to regulation
0 / I
ACC.
0
008
•
P characteristic
0...100
P.A.
40
008
•
I characteristic
0...100
I.A.
100
008
•
Automatic frequency control
0 / I
A.F.C
0
008
•
Start automatic frequency search
A.F.S.
008
Track control
•
Switch on time delay
0...60 Sec.
I.
1.0 Sec.
007, 167
•
Switch off time delay
0...60 Sec.
O.
1.0 Sec.
007, 167
•
Invert sensor
PNP / PNP
invert
-SE.
PNP
007, 167
•
Sensor Time-out
0 / I
E.En.
0
015, 167
•
Sense time delay (Sensor Time-out)
1...240 Sec. E.E.
180 Sec.
015, 167
•
Switch off time air valve
0…60 Sec.
A.i.
4 Sec.
015
Service
•
Display actual output current
i.
040
•
Display actual frequency
F.
040
•
Save user settings
PUSH.
143
•
Recall factory settings
FAC.
210
•
Recall user settings
US.PA.
210
•
Hide programming menus
0 / I
Hd.C.
0
117
•
Hide set point adjustment
0 / I
di.S.
0
137
•
Display software version
001