14
2.3
Communication Ports
Gateway unit has two communication ports. Both the ports have DB9 type connectors and are compatible
with RS232C, RS422, RS485 and CMOS signal levels. PLC1 (also known as COM1) and PLC2 (also known
as COM2) have exactly the same pin outs which are as shown below:
PLC1 / PLC2 ports
TX- (RS422/RS485)
DB9 Female
1
5
9
+5VDC*
*(DO NOT USE)
G N D
RX+ (RS422/RS485)
RXD (RS232C/CMOS)
TXD (RS232C)
TX+ (RS422/RS485)
TXD (CMOS)
RX- (RS422/RS485)
6
8
9
7
2
4
5
3
1
6
Pin Description
User can convert RS485 4 wire + Signal Ground system to a 2 Wire + Signal Ground system by shorting
following signals in the communication cable:
TX+
TX-
A
RX+
B
RX-
SG
SG
Note: If user has attached shield to Earth on Device end, leave the shield open on Gateway end. If user
has connected shield to Signal Ground on Device end, connect shield to Signal Ground on Gateway
end.
Upto 31 Devices can be multi-dropped on RS485 port of Gateway.
Pin
Name
Signal Level
Description
1.
TX+
RS422 / RS485
Differential Tr, also referred as TXA
2.
TXD
RS232
Transmit
3.
RXD
RS232 / CMOS
Receive
4.
RX+
RS422 / RS485
Differential R, also referred as RXA
5.
GND
-
Signal Ground common to all signals.
6.
+5VDC
-
DO NOT USE
7.
TXD
CMOS
Transmit
8.
TX-
RS422 / RS485
Differential Transmit -, also referred as TXB
9.
RX-
RS422 / RS485
Differential Receive -, also referred as RXB
Summary of Contents for GWY-00
Page 1: ...GATEWAY USER S MANUAL ...
Page 25: ...25 TYPICAL PROJECTS In this chapter Project Setup Example 1 Example 2 Example 3 ...
Page 30: ...30 CONFIGURATION SOFTWARE In this chapter System Requirements Installation Instructions ...
Page 32: ...32 CABLE DIAGRAMS In this chapter Wiring Diagrams Communication Cable ...
Page 34: ...34 COMMUNICATION CABLES FOR GWY 00 ...
Page 69: ...69 COMMUNICATION CABLES FOR GWY S7 ...
Page 83: ...83 COMMUNICATION CABLES FOR GWY S8 ...
Page 85: ...85 IBM CABLES ...
Page 88: ...88 TROUBLESHOOTING GUIDE ...
Page 104: ...CIV INDEX ...