Minimum Clearances
Maintain clearance from enclosure walls, wires,
and other adjacent devices. Keep 2” space on all sides
for adequate ventilation. Plan for adequate space around the product and inside the enclosure for
ventilation and cabling. Take into consideration the heat produced by other devices in the enclosure. The
ambient temperature around this product must be 0° to 50°C.
Mounting FP2 with I/Os Products
FP2 series HMI with I/Os
products must be installed on the front panel, using the clamp accessories
shipped with the product. Before mounting, make sure that the sealing gasket is properly positioned. This
gasket forms a compression type seal. Do not use sealing compounds. Then, place the unit in the panel
cutout and tighten the mounting screws evenly (torque 0.4Nm) to maintain water and dust resistance.
ATTENTION
ATTENTION: Mounting FP2
series HMI with I/Os
on Panel
Do not push the LCD display when pushing the unit into the panel as it may damage
the display.
Connecting Power
FP2 series HMI with I/Os
requires a 24VDC isolated power supply. Follow the steps mentioned below to
connect the power:
Make sure that terminal is not connected to a power source
Secure the 24VDC power wires
Secure the functional earth ground wire to the functional earth ground terminal screw on the
terminal block
Apply 24VDC power to the terminal
Power Rating
Unit
Voltage
Current
Wattage
FP2043T-E
24VDC
130mA
3.12W
FP2043TN-E
24VDC
150mA
3.6W
FP2070T-E
24VDC
200mA
4.8W
FP2070TN-E
24VDC
230mA
5.52W