4.2 Top Down Clamps 

Clamps are an approved method of mounting for Renogy modules. A 
clamp holds two modules in a row. The centerline of the clamps must be 
in-line with the module mounting holes and installed according to code.  

 

 

4.3 Grounding 

The frame of the PV module, as well as any exposed non-current carrying 
metal parts of fixed equipment that can be energized must be grounded to 
avoid electrical shock. Renogy recommends grounding all PV module 
frames to ensure the voltage between the conductive equipment and the 
earth ground is zero in all circumstances.  

Appropriate grounding consists of using an appropriately sized EGC or 
racking system that can be used for integrated grounding. Renogy panels 
implement a coated aluminum frame for corrosion resistance. The frame 
rails have pre-drilled holes marked with the grounding sign. Do not drill 
additional holes into the frame rails.  

 

 

 

  Note that the stainless steel washer is used between the grounding 

wire and the module frame. This is for avoiding corrosion due to 
dissimilar metals.  

  The module frame must be properly grounded (refer to NEC clause 

250). The grounding wire must be properly fastened to the module 
frame to assure good electrical contact. Use the recommended type, 
or an equivalent, connector for this wire. 

  If the support frame is made of metal, the surface of the frame must 

be electroplated and have excellent conductivity. 

  We recommend the lay-in lug (Cat. No. GBL4-DBT; rated for 

600Volts; company: ILSCO; UL number is E34440

when 

grounding. First strip 16mm insulating jacket from the end of the 
ground wire (4-14 STR.) carefully to avoid nicking or cutting 
conductors, insert the wire into the slot of the lug (see the picture), 
and screw down the slotted screw. 

  Next, assemble the recommended ILSCO grounding lug to the 

aluminum frame using stainless steel M3 or M5 screw and hardware 
as shown below. Note: there are two different size grounding holes, 
the smaller of which is being phased out. 

  Further, buildup of hardware for mounting the grounding lug are the 

same—except for the M3 screw, an added flat washer is mounted 
directly under the M3 screw head. The star washer is fitted directly 
under the grounding lug and makes electrical contact by penetrating 
the anodized coating of the aluminum frame, The screw assembly is 
further fitted with a flat washer, then a split lock washer and finally a 
nut to secure the entire assembly, as shown. Recommended torque 
of M3 or M5 screw assembly is 0.8NM or 1.5 NM. 

5. Electrical Installation 

5.1 Cables and Wiring

 

Renogy  modules are equipped with two (2) stranded, PV-rated, output 
MC4 cables. The positive connector is a male connector and the negative 
connector is a female connector. These wires by themselves are rated for 
series connections, but could be adapted to hold parallel connections with 

Summary of Contents for RNG Series

Page 1: ...INSTALLATION GUIDE FOR PHOTOVOLTAIC PV MODULES...

Page 2: ...Installation Requirements 4 3 3 Site Considerations 5 3 4 System Fire Rating 5 4 Module Mounting 5 4 1 Bolting 5 4 2 Top Down Clamps 6 4 3 Grounding 6 5 Electrical Installation 6 5 1 Cables and Wiring...

Page 3: ...ation including without limitation the risk of electric shock One individual module may generate DC voltages greater than 30 volts when exposed to direct sunlight Contact with a DC voltage of 30V or m...

Page 4: ...e structure can bear the module system load Ensure the supporting roof has fire resistant roof covering Renogy modules are listed as Class C under the UL790 Standard 3 1 Unpacking and Storing Unpack m...

Page 5: ...ng All installation methods herein are only for reference and Renogy will not provide their own mounting components Instead the system installer is responsible for making sure installation is abided b...

Page 6: ...made of metal the surface of the frame must be electroplated and have excellent conductivity We recommend the lay in lug Cat No GBL4 DBT rated for 600Volts company ILSCO UL number is E34440 when groun...

Page 7: ...nections Appropriate MC4 connectors will have a manufacturer name of the following Model Renogy Forward Electronics Jiangsu Forward Electronic Technology Co Ltd No 291 East Street Zhulin Town Jintan C...

Page 8: ...mally approve and inspect such a system before it can be connected to the grid 6 Commission and Maintenance Renogy recommends that all work in commissioning and maintenance of a system must be perform...

Page 9: ...face Insert a 3mm flat screwdriver into the slot on the junction box cover The cover has a sign of screwdriver Gently pull up the four slots until the cover been opened Insert the 3mm flat screwdriver...

Reviews: