Appendix Sensor Selection Table

Tested gas

Measuring

range

Selectable range

Resolution

Alarm point

Combustible EX

0-100%lel

0-100%vol(Infrared)

1%lel/1%vol

low

20high

50

O2

0-30%vol

0-30%vol

0.1%vol

low

19.5%high

23.5%vol

H2S

0-100ppm

0-50/200/1000ppm

0.1ppm

low

10 high

20 ppm

Carbon monoxide

CO

0- 1000ppm

0-500/2000/5000ppm

1ppm

low

50 high

150 ppm

CO2

0-5000ppm

0-1%/5%/10%vol

Infrared

1ppm/0.1%vol

low

1000 high 2000

Nitric oxide NO

0-250ppm

0-500/1000ppm

1ppm

low

50 high

150 ppm

NO2

0-20ppm

0-50/1000ppm

0.1ppm

Low: 5 High: 10 ppm

SO2

0-20ppm

0-50/1000ppm

0.1/1ppm

Low: 5 High: 10 ppm

CL2

0-20ppm

0-100/1000ppm

0.1ppm

Low: 5 High: 10 ppm

Hydrogen H2

0-1000ppm

0-5000ppm

1ppm

Low: 50 High: 150 ppm

Ammonia

0-100ppm

0-50/500/1000ppm

0.1/1ppm

Low: 20 High: 50 ppm

Phosphine PH3

0-20ppm

0-20/1000ppm

0.1ppm

Low: 5 High: 10 ppm

Hydrogen

chloride HCI

0-20ppm

0-20/500/1000ppm

0.001/0.1ppm

Low: 5 High: 10 ppm

Chlorine dioxide

CLO2

0-50ppm

0-10/100ppm

0.1ppm

Low: 5 High: 10 ppm

HCN

0-50ppm

0-100ppm

0.1/0.01ppm

Low: 10 High: 20 ppm

Ethylene oxide

C2H4O

0-100ppm

0-100ppm

1/0.1ppm

Low: 20 High: 50 ppm

O3

0-10ppm

0-20/100ppm

0.1ppm

Low: 2 High: 5 ppm

Formaldehyde

CH2O

0-20ppm

0-50/100ppm

1/0.1ppm

Low: 5 High: 10 ppm

Hydrogen fluoride

HF

0-100ppm

0-1/10/50/100ppm

0.01/0.1ppm

Low: 2 High: 5 ppm

Xylene / toluene

0-20ppm

0-1/10/50/100ppm

0.01/0.1ppm

Low: 5 High: 10 ppm

Summary of Contents for RS-MG41-1

Page 1: ...RS MG41 1 Composite Multi Gas Detector User Manual V1 0 Shandong Renke Control Technology Co Ltd www renkeer com 1 RS MG41 1 Composite multi gas detector User manual Document version V1 0...

Page 2: ...rrying 6 5 Function and operation instructions 7 5 1Key Description 7 5 2Main interface introduction 8 5 3Instructions 9 5 3 1System setup instructions 9 5 3 2Channel setting instructions 11 5 3 3Stor...

Page 3: ...rial site safety monitoring for high reliability of the equipment The housing is made of high strength engineering plastics and composite non slip rubber which has high strength and good feel and is w...

Page 4: ...y safe explosion proof products 3 High definition color screen design easy to check the gas status 4 The product can detect four gases oxygen flammable gas carbon monoxide and hydrogen sulfide 5 Can s...

Page 5: ...OL Indication error Absolute error 5ppm 5 ppm 5 FS 3 FS Relative error 10 Duplicate value 2 2 2 1 Zero drift 3ppm 5ppm 2 FS 1 Span drift 5 5ppm 3 FS 1 Alarm action value 50 150ppm 10 35ppm 20 50 LEL 1...

Page 6: ...pment USB plug USB data cable standard gas hood certification warranty card factory inspection report 4 Way of carrying Open the device with the surface buckle snap the device to the place where you n...

Page 7: ...face short press to increase current value long press to increase current value quickly Decrease key Main interface long press to turn off the buzzer alarm Menu bar interface short press the cursor mo...

Page 8: ...current option 5 2Main interface introduction Serial number name Description 1 Real time value Display the current actual gas concentration value 2 Gas name Show gas name 3 time Display the current ti...

Page 9: ...annot be enabled 11 Proportion Display the current remaining battery level 5 3Instructions 1 In the shutdown state press and hold the 2S confirmation key the device detects whether the buzzer flash an...

Page 10: ...m doesn t affect the low battery alarm function Standby screen Select the corresponding time click the OK button Password setup With increase button and reduce button to confirm the present value the...

Page 11: ...ore than H Alarm value it will has has Alarm II Zero standard concentration Note this operation must be operated in the clear air or N2 Enter in the operation screen please move the cursor to Confirm...

Page 12: ...ice View Note The storage settings need to be turned on in the system settings The device cannot view the specific historical data You need to use the configuration soft armor to read the data Can be...

Page 13: ...parameters Connect the device to the computer through the USB data cable click Read Device Information in the toolbar and click Write Device Information after editing the device parameters to write th...

Page 14: ...hen an alarm occurs on the detector If you do not allow it you cannot turn off the alarm sound quickly Sound on Set the alarm sound of the detector on or off Alarm on Set the detector s sound light an...

Page 15: ...nd then connect the recorder to the computer via a USB cable Click Read Data to import the data stored in the tester into the configuration software Click on the data to view the stored historical dat...

Page 16: ...k Delete device storage data in the drop down menu to clear the device data After clearing the software prompts Delete cleared successfully 7 Gas calibration Due to the normal loss and aging of the se...

Page 17: ...be used normally 9 Precautions 1 Prevent the machine from falling from high places or receiving severe vibration 2 In high concentration gas environment the machine may not work properly 3 Please use...

Page 18: ...m detection gas circuit failure Contact your dealer or manufacturer for repairs Inaccurate display Sensor expired Contact your dealer or manufacturer Long uncalibrated Replace the sensor Time display...

Page 19: ...ntact information Shandong Renke Measurement Control Technology Co Ltd Address 2 F East Block Building 8 Shun Tai Plaza High tech Zone Jinan City Shandong Province Postcode 250101 Phone 400 085 5807 F...

Page 20: ...ppm Low 5 High 10 ppm SO2 0 20ppm 0 50 1000ppm 0 1 1ppm Low 5 High 10 ppm CL2 0 20ppm 0 100 1000ppm 0 1ppm Low 5 High 10 ppm Hydrogen H2 0 1000ppm 0 5000ppm 1ppm Low 50 High 150 ppm Ammonia 0 100ppm 0...

Reviews: