RenewAire HE1.5XRT Installation, Operation & Maintenance Manual Download Page 9

ERV

HE1.5XRT

9

 

1.800.627.4499 

INSTALLATION, OPERATION AND MAINTENANCE MANUAL 

WWW.RENEWAIRE.COM 

4/22/09 MF

SPECIFICATIONS SUBJECT 
TO CHANGE WITHOUT NOTICE.

RenewAire LLC

Scale:  1" = 24"
Do not scale drawing

HE1.5X-RT_CORNER_WEIGHTS_
MAY18.dwg

HE1.5XRT Corner Weights

RR

RF

LF

UNIT COG

RANGE

BASIC UNIT WEIGHTS (lbs.)

Motors

UNIT

LF

LR

RR

RF

.75 HP

394

94

81

102

117

ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)

Motors

UNIT

LF

LR

RR

RF

Double Wall

110

26

23

28

33

VFD'S

8

2

2

2

2

RA or EA Damper

18

7

7

2

2

OA or FA Damper

18

7

7

2

2

Total Selected Weights

Add the additional weights for options to the Basic Module weights 

determined by motor size to determine Module and Corner weights for a 

specific unit.

Corner weights shown above include weatherhoods INSIDE THE UNIT, as 

shipped.

Center of gravity: A=25" B=16" (+/- 2")

30.37" 

Mounting 
Leg Pitch

43.46" Mounting Leg Pitch

MAY18- MHK

266.39

186.

16

LR

RIGGING  
INFORMATION

There are pairs of rigging holes at each upper corner of the unit. Use slings or shackles at all four  
corners. Spreader bars are recommended in order to avoid damage to the unit.

CURB  
SPECIFICATIONS

F2

INSTALLATION

HE1.5XRT UNIT CORNER WEIGHTS (LBS)

SINGLE-WALL

PHASE

UNIT

LF

LR

RR

RF

1-PHASE & 3-PHASE

395

94

81

102

117

DOUBLE-WALL

PHASE

UNIT

LF

LR

RR

RF

1-PHASE & 3-PHASE

504

120

104

130

150

±

INDICATES LOCATIONS AT WHICH CORNER WEIGHTS ARE  

CALCULATED ALONG CENTERS OF CURB RAILS. 

F3

  86" Overall  

  CL 2 1/2" Control In  

  CL 5 5/8" Power In  

  42 7/8" Lift Lugs  

OA

EA

RA

RTF

ONLY

FA

E-Box

Pressure 

Ports (4) Typ.

Disconnect

Switch

(2)  7/8" holes for 

wiring in bottom of

E-Box

FRONT VIEW

RTH

ONLY

FA

22 1/8" Wiring

  3 5/8"  

56 3/4" Overall

  5 7/8"  

CL 26 1/8"

Wiring

54" Case

FA (RTH)

Damper Location

(Optional)

EA Damper

Location

(Optional)

LEFT VIEW

FA (RTH)

18" X 18"

Duct Receiving

Flange

  6 3/8"  

  6"  

33 1/4"

Overall

  1 7/8"  

29 3/4"

Lift Lugs

RIGHT VIEW

RA

18" X 18" 

Duct Receiving

Flange

  45 3/4" Case  

32 5/8" Case

  10 1/8"  

  11 1/8"  

  15 3/8"  

55 5/8" Minimum

Service Area

24 3/4" Minimum Service

Area

FA (RTF)

14" x 16"

Opening

TOP VIEW

Door

Swing

Door

Swing

FA (RTF)

Damper Location

(Optional)

  2 1/8"  

  1 1/8"  

  17 1/8" I.D.  

  17 1/8" I.D.  

  4 1/4"  

  1 7/8"  

  38 1/2" I.D.  

  42 1/4" O.D.  

24 1/2"

I.D.

28 1/4" O.D.

A

A

FA

RA

TOP VIEW

CURB 1.5X

  1 7/8"  

  3"  

SECTION A-A

CURB CROSS-SECTION A-A (TYP.)

1 1/2" X 1/4"

Neoprene Gasket

3/4" X 3 1/2"

Wooden Nailer

Model: HE1.5X RTH/RTF

Drawing Type: Unit Dimension

Version: MAY18

ABBREVIATIONS

EA: Exhaust Air to outside

OA: Outside Air intake

RA: Room Air to be exhausted

FA: Fresh Air to inside

RTF: Rooftop Vertical FA Only

RTH: Rooftop Horizontal RA & FA

INSTALLATION ORIENTATION

Unit must be installed in orientation

shown.

NOTE:

1. UNLESS OTHERWISE SPECIFIED,

DIMENSIONS ARE ROUNDED TO THE 

NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT 

TO CHANGE WITHOUT NOTICE.

  86" Overall  

  CL 2 1/2" Control In  

  CL 5 5/8" Power In  

  42 7/8" Lift Lugs  

OA

EA

RA

RTF

ONLY

FA

E-Box

Pressure 

Ports (4) Typ.

Disconnect

Switch

(2)  7/8" holes for 

wiring in bottom of

E-Box

FRONT VIEW

RTH

ONLY

FA

22 1/8" Wiring

  3 5/8"  

56 3/4" Overall

  5 7/8"  

CL 26 1/8"

Wiring

54" Case

FA (RTH)

Damper Location

(Optional)

EA Damper

Location

(Optional)

LEFT VIEW

FA (RTH)

18" X 18"

Duct Receiving

Flange

  6 3/8"  

  6"  

33 1/4"

Overall

  1 7/8"  

29 3/4"

Lift Lugs

RIGHT VIEW

RA

18" X 18" 

Duct Receiving

Flange

  45 3/4" Case  

32 5/8" Case

  10 1/8"  

  11 1/8"  

  15 3/8"  

55 5/8" Minimum

Service Area

24 3/4" Minimum Service

Area

FA (RTF)

14" x 16"

Opening

TOP VIEW

Door

Swing

Door

Swing

FA (RTF)

Damper Location

(Optional)

  2 1/8"  

  1 1/8"  

  17 1/8" I.D.  

  17 1/8" I.D.  

  4 1/4"  

  1 7/8"  

  38 1/2" I.D.  

  42 1/4" O.D.  

24 1/2"

I.D.

28 1/4" O.D.

A

A

FA

RA

TOP VIEW

CURB 1.5X

  1 7/8"  

  3"  

SECTION A-A

CURB CROSS-SECTION A-A (TYP.)

1 1/2" X 1/4"

Neoprene Gasket

3/4" X 3 1/2"

Wooden Nailer

Model: HE1.5X RTH/RTF

Drawing Type: Unit Dimension

Version: MAY18

ABBREVIATIONS

EA: Exhaust Air to outside

OA: Outside Air intake

RA: Room Air to be exhausted

FA: Fresh Air to inside

RTF: Rooftop Vertical FA Only

RTH: Rooftop Horizontal RA & FA

INSTALLATION ORIENTATION

Unit must be installed in orientation

shown.

NOTE:

1. UNLESS OTHERWISE SPECIFIED,

DIMENSIONS ARE ROUNDED TO THE 

NEAREST EIGHTH OF AN INCH.
2. SPECIFICATIONS MAY BE SUBJECT 

TO CHANGE WITHOUT NOTICE.

Summary of Contents for HE1.5XRT

Page 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR HE1 5XRT WWW RENEWAIRE COM MODEL HE1 5XRT...

Page 2: ...NG The unit s fresh air inlet should be at least 10 away from any exhaust such as dryer vents chimneys furnace and water heater exhausts or other sources of contamination or carbon monoxide Do not loc...

Page 3: ...Voltage Codes 4 8 only available with Phase Code 3 Three Phase 3 Motor Codes EE EC Motors only available with Phase Code 1 Single Phase 4 Unit Control Code G Terminal Strip only available with Motor C...

Page 4: ...t MC W Carbon dioxide control wall mount CO2 W duct mount CO2 D Electric duct heater EK series 1 60 kW designed for indoor ductwork installation only Indirect gas fired duct furnace GH series 50 400 M...

Page 5: ...Roof Curb HE1 5XRTR Room Air RA enters bottom of unit Fresh Air FA exits side of unit Roof Curb HE1 5XRTF Room Air RA enters side of unit Fresh Air FA exits bottom of unit Roof Curb HE1 5XRTH Room Air...

Page 6: ...IEW Door Swing Door Swing FA RTV Damper Location Optional 2 1 8 1 1 8 17 1 8 I D 17 1 8 I D 4 1 4 1 7 8 38 1 2 I D 42 1 4 O D 24 1 2 I D 28 1 4 O D A A FA RA TOP VIEW CURB 1 5X 1 7 8 3 SECTION A A CUR...

Page 7: ...l 2 1 8 1 1 8 17 1 8 I D 17 1 8 I D 4 1 4 1 7 8 38 1 2 I D 42 1 4 O D 24 1 2 I D 28 1 4 O D A A FA RA TOP VIEW CURB 1 5X 1 7 8 3 SECTION A A CURB CROSS SECTION A A TYP 1 1 2 X 1 4 Neoprene Gasket 3 4...

Page 8: ...5X RTV RTR Drawing Type Unit Dimension Version MAY18 ABBREV EA Exh OA Ou RA Roo FA Fres RTV Ro RTR Ro INSTALL Unit mu shown NOTE 1 UNLE DIMENS NEARES 2 SPEC TO CHA F1 It is the installer s responsibi...

Page 9: ...t Use slings or shackles at all four corners Spreader bars are recommended in order to avoid damage to the unit CURB SPECIFICATIONS F2 INSTALLATION HE1 5XRT UNIT CORNER WEIGHTS LBS SINGLE WALL PHASE U...

Page 10: ...ep drywall spray construction dust etc out of unit CAUTION 1 Before servicing or cleaning the unit switch power off at disconnect switch or service panel and lockout tag out to prevent power from bein...

Page 11: ...an may be installed on the underside of the base pan Safely access the underside of the unit to install the patch pan 8 Installtheinsulationintheundesiredopening Seal the insulation 9 At this point if...

Page 12: ...rs to Set and Balance Airflow Rates In most applications the airflow rate for both the Fresh Air and the Exhaust Air should be roughly equal or balanced for best performance of the HE1 5XRT Unit See u...

Page 13: ...the bottom of the HE1 5XRT are generally installed at this time Install 2 ducts with HE1 5XRTV 1 duct with HE1 5XRTR or RTF Drop duct s into openings in top of roof curb Install appropriate gasket on...

Page 14: ...Supply with an External Power Supply NOT AVAILABLE IN EVERY UNIT DOOR INTERLOCK SWITCH This wire omitted with single phase power supply These wires omitted with single phase power supply TRANSFORMER w...

Page 15: ...OT interconnect this unit s Class 2 Power Supply with an External Power Supply NOT AVAILABLE IN EVERY UNIT DOOR INTERLOCK SWITCH This wire omitted with single phase power supply These wires omitted wi...

Page 16: ...Trip Point 3A 1 Connect only to components intended for use with 24VAC power 2 Do not undersize the low voltage wires connected to this device Observe the wire length and gauge limits indicated in th...

Page 17: ...ndependent Blower Control Only Use this schematic if the external control system provides no voltage or current at its output contacts Install jumper provided between terminals 2 3 Connect one side of...

Page 18: ...ally Open N O contacts to terminals 1 4 NOTE See Wiring Schematics G Control System on separate Power Supply Independent Blower Control Use this schematic only if no power is present at the controls o...

Page 19: ...ity These may include timer clocks occupancy sensors dehumidistats for cool weather operation carbon dioxide sen sors and others DDC systems may also control the unit Most control schemes will operate...

Page 20: ...uring device to the Outside Air OA port and the low pressure side to the Fresh Air FA port To read SCFM of Room Air RA install the high pressure side of your measuring device to the Room Air RA port a...

Page 21: ...30 0 40 400 600 800 1000 1200 1400 1600 Clean filter Pressure Drop in w g Unit Airflow CFM Initial Pressure Drop of Optional MERV 13 Filters available for this unit V15 xlsx 14 16x20x2 MERV 8 IOM 0 0...

Page 22: ...ERV HE1 5XRT WWW RENEWAIRE COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 627 4499 22 MAINTENANCE SERVICE PARTS HE1 5XRT www renewaire com 800 627 4499 support renewaire com...

Page 23: ...the unit are usually able to keep the energy exchange core clear for several months Finer filters can be used but must be cleaned more often If using finer filters their increased resistance to flow...

Page 24: ...pital costs by reducing HVAC loads and decreases operational expenses by downsizing equipment resulting in major energy and cost savings RenewAire technologies also enjoy the industry s best warranty...

Reviews: