background image

PRODUCT DATA 

Due to continuing product development, specifications are subject to change without notice

 

EV130_200_300Man_Mar13.docx  

134777_012 

 

Revised 03/2013 

 

 2013 RenewAire LLC  

Page 

 

EV130/EV200/EV300

 

 

E n e r g y  
E x c h a n g e  
S y s t e m :  

  Cross flow fixed-plate enthalpic energy exchange core: engineered, proprietary resin-media 

composite.  Provides both sensible and latent heat transfer. 

C e r t i f i e d  
P e r f o r m a n c e :  

  See HVI Certified Ratings 

A c c e s s   D o o r :  

  Front panel opens to provide access to filters, blowers, and heat exchanger.  Snap latches and hinges 

provided for easy service. 

I n s u l a t i o n :  

  One inch foil-faced fiberglass throughout. 

M o u n t i n g  
O p t i o n s :  

  Unit may be mounted to wall or floor joists using integral mounting flange with hanging bracket kit 

provided.   

B l o w e r / M o t o r :  

  A single high efficiency PSC motor directly drives two large diameter centrifugal blowers for quiet 

operation. 

F i l t e r s  

  Cleanable polyester air filters for both exhaust and fresh air streams. 

D e f r o s t :  

  Passive frost-free design under most residential conditions.  Optional defrost accessory available for 

severe applications and climate zones. 

W a r r a n t y :  

  Ten year limited warranty on energy exchange core; two year limited warranty against defects in 

material and workmanship on all other components. 

 
 

 

 

 

 

 

EV130

 

EV200

 

EV300

 

A i r f l o w  
R a n g e :  

  50-140 CFM for each air 

stream. 

100-200 CFM each air stream. 

150-300 CFM each air stream.

 

R a t e d   A i r f l o w :  

  130 CFM for each air 

stream at 0.2” external 
static pressure (ESP). 

200 CFM for each air stream 
at 0.2” external static pressure 
(ESP). 

300 CFM for each air stream at 
0.4” external static pressure 
(ESP).

 

D i m e n s i o n :  

  28 3/4” wide x 20 1/8” 

high x 13” deep (not 
including duct collars). 

28 3/4” wide x 20 1/8” high x 
24” deep (Not including duct 
collars). 

28 3/4” wide x 20 1/8” high x 
24” deep (Not including duct 
collars).

 

U n i t   W e i g h t :  

  58 lbs. 

80 lbs. 

88 lbs.

 

D u c t  
C o n n e c t i o n s :  

  Insulating double collars 

with six-inch/eight-inch 
round connections for 
flexible or rigid duct work. 

Insulating double collars with 
six-inch/eight-inch round 
connections for flexible or 
rigid duct work. 

Insulating double collars with 8-
inch oval connections for flexible 
or rigid duct work.

 

E l e c t r i c a l :  

  Power: 0.1 HP, 120 Volt, 

60 Cycle, single phase, 1.2 
FLA, 102 watts at 130 
CFM.  Control: On-board 
24 volt transformer and 
relay. 

Power: 0.1 HP, 120 Volt, 60 
Cycle, single phase, 1.5 FLA, 
157 watts at 181 CFM.  
Control: On-board 24 volt 
transformer and relay. 

Power: 0.2 HP, 120 Volt, 60 
Cycle, single phase, 3.3 amps, 
315 watts at 297 CFM. Control: 
On-board 24 volt transformer 
and relay.

 

 

 
 
 
 

 

 

 

Summary of Contents for EV130 SERIES

Page 1: ...This unit must be properly ducted to the outdoors 8 Outside air inlet for this unit must be located away from sources of hazardous air such as auto exhausts 9 Sufficient air is needed for proper comb...

Page 2: ...e preferred mounting location for the unit is on a concrete foundation wall because the foundation wall will isolate any blower vibration If a basement area is not available or practical use other mec...

Page 3: ...8 round on EV300 Bathroom 4 X 10 or 6 X 10 40 to 60 sq in Kitchen 6 X 10 or 60 sq in CAUTION DO NOT PLACE ANY STALE AIR RETURNS IN GARAGES Can an ERV be used to ventilate bathrooms A RenewAire ERV can...

Page 4: ...layout on the hanging bracket is spaced for 16 19 2 and 24 on center layouts CAUTION RISK OF INJURY WHEN LIFTING UNIT AND INSTALLING IT OVERHEAD GET A HELPER AND WEAR EYE PROTECTION Installing Outsid...

Page 5: ...er to maintain good airflow Installing Controls WARNING DANGER OF ELECTRICAL SHOCK WHEN SERVICING AN INSTALLED UNIT ALWAYS UNPLUG UNIT BEFORE CONNECTING OR SERVICING CONTROLS Optional controls RenewAi...

Page 6: ...nergy exchange core two year limited warranty against defects in material and workmanship on all other components EV130 EV200 EV300 A i rf lo w R a ng e 50 140 CFM for each air stream 100 200 CFM each...

Page 7: ...ent specifications are subject to change without notice EV130_200_300Man_Mar13 docx 134777_012 Revised 03 2013 2013 RenewAire LLC Page 7 EV130 Front View Top View Right View EV200 Front View Top View...

Page 8: ...CERTIFIED RATINGS Due to continuing product development specifications are subject to change without notice EV130_200_300Man_Mar13 docx 134777_012 Revised 03 2013 2013 RenewAire LLC Page 8...

Page 9: ...n most homes for most people At this rate you will be changing the air in your home over eight times per day Most ERV systems are generally designed to provide at least this ventilation rate Be sure t...

Page 10: ...tor I Blower wheel divider side J Door assembly K Hinge set both parts L Terminal strip M Line cord with bushing N Filter set of two P Core cross bar Q Core gasket kit not shown R Hanging bracket kit...

Page 11: ...Control board with standoffs G Blower assembly complete H Motor I Blower wheel divider side J Door assembly K Hinge set both parts L Terminal strip M Line cord with bushing N Filter set of two P Core...

Page 12: ...exchange core with a soft brush attachment 3 After servicing the filters re install them see above 4 Vacuum out dust from the rest of the unit case Dust collects only on the entering faces of the ener...