System separation underfloor heating
Activation if a mixed heating cycle is separated by a heat exchanger.
If system separation is activated, the set temperature is increased.
Menu item
Parameter
Factory setting
System separation FBH
Deactivated
Deactivated
Activated
Setpoint increase
After activating the system separation it is possible to select a setpoint increase, in order to balance the heat
losses with a heat exchanger.
Menu item
Parameter
Factory setting
Setpoint temperature
0 - 10
5.0 K
Setting the building time constant
The building time constant specifies the ability of the building to retain heat. The building time constant is
dependent upon the type of building (see table). The value is also dependent on individual temperature per-
ception, and so the information in the table should only be treated as a guide.
Recommended are:
Building
type
Heat retention ability
Recom-
mended value
Light
Low heat retention ability, e.g. prefab/wood-frame houses
approx. 10 h
Medium
Moderate heat retention ability, e.g. house made from hollow blocks
approx. 20 h
Heavy
High heat retention ability, e.g. brick house
approx. 30 h
Very heavy
Very high heat retention ability, e.g. exterior and interior walls > 30 cm
approx. 60 h
Passive
Well-insulated, e.g. zero-energy housing
approx. 100 h
Menu item
Parameter
Factory setting
Building time constant
0 - 100 h
According to design! - 10 h
REMKO Smart-Control Touch
90