REMKO RVS 100H Functional Overview Download Page 4

W

e r

eserve the right to make technical changes, and pr

ovide no guarantee as to the accuracy of this data!

Measurement  

temperature 

Probe resistance

value

 NTC

-20

71.67 k

Ω

-10

44.07 k

Ω

0

27.86 k

Ω

+10

18.13 k

Ω

+20

12.11 k

Ω

+30

8.29 k

Ω

+40

5.80 k

Ω

+50

4.14 k

Ω

+60

3.01 k

Ω

+70

2.22 k

Ω

+80

1.66 k

Ω

+90

1.26 k

Ω

+100

0.98 k

Ω

Electrical drawings

Legend:

A1 

Controller

A2 

Fan speed controller

B1 

Probe medium inlet

B2 

Probe medium outlet

B3 

Probe condenser

EV 

Reversing valve

FCR  Phase sequence relay
FL 

Flow switch

FR 

Motor overload protection

EV 

Reversing valve

FCR  Phase sequence relay
FL 

Flow switch

FR 

Motor overload protection

HP 

High pressure switch

LP 

Low pressure switch

M1  Compressor
M2  Circulation pump
M3/4 Condenser fan 1/2

RC1  Compressor crank case heater
RF1  Defrost heater
TA1  Transformer 230/24V
TR1  Pressure transducer
TS 

Temperature controller

TX1/2 Thermal contact fan 1/2

RVS 100H / RVS 150H

Pr

obe inlet

High pr

essur

switch

Pr

obe outlet

Low pr

essur

e switch

Four

-way-valve

Enable contact

 

potential fr

ee

O

pe

ra

tin

co

nt

ac

C

-H

 p

ot

en

tia

l f

re

e

General alarm signal

 

potential fr

ee

Pr

obe condenser 

Flow switch

Pressure 

transducer

Controller

Colour code:

BU 

blue

BR 

brown

BK 

black

GR 

green

RT 

red

OR 

orange

WT 

white

YE 

yellow

YE/GR  yellow/green

Compressor

Power supply

440-460V / 60Hz

max. 506 V

Circulation pump

Condenser 

fan 1

Condenser 

fan 2

Crank case 

heater

Defrost 

 heater

Summary of Contents for RVS 100H

Page 1: ...tand By mode safety equipment is active but no operat ing mode is set Key Using this key the current menu can be resetted Key This key is used for selecting or e g to open close the set point or parameter Key Prolonged pressing 5 sec allows to switch between the operating modes Cooling and Stand by Short pressing displays the current values of the temperature probes B1 to B3 and the pressure tranc...

Page 2: ...B3 16 Calibration B4 21 Digital filter 22 Input limit 23 Unit of measurement C F A01 Set point frost protection A02 Hysteresis frost protection A03 Time delay frost protection A04 Set point medium heating A05 Hysteresis medium heating A06 Probe medium heating A07 min antifreeze protection setting C01 min working time compressor C02 min down time compressor C03 Time delay On On compressor C04 Time ...

Page 3: ...tage controller Tr Supply voltage too low Check the voltage of the transformer both sides EP1 EEPROM driver defective Internal controller error Replace the controller EPb EEPROM alarm at start Config Internal controller error Replace the controller EPr EEPROM alarm during operation Config Internal controller error Replace the controller FL Flow switch has responded ID1 Differential switch Flow swi...

Page 4: ... FR Motor overload protection HP High pressure switch LP Low pressure switch M1 Compressor M2 Circulation pump M3 4 Condenser fan 1 2 RC1 Compressor crank case heater RF1 Defrost heater TA1 Transformer 230 24V TR1 Pressure transducer TS Temperature controller TX1 2Thermal contact fan 1 2 RVS 100H RVS 150H Probe inlet High pressure switch Probe outlet Low pressure switch Four way valve Enable conta...

Reviews: