15
t
L1
= air inlet temperature / t
L2
= air outlet temperature
Type
PWL 101-HK
PWL 102-HK
PWL 103-HK
Version
2-speed
2-speed
2-speed
Speed
rpm
920
750
920
750
920
750
Electrical connection
400/3~N
Frequency
Hz
50
Power consumption kW
0.1/0.07
Nominal current
A
0.26/0.13
Air volume
m³/h
2030
1685
1960
1610
1885
1530
Sound pressure level
1)
dB (A)
56
47
56
47
56
47
Sound power level
dB
64
55
64
55
64
55
Hydraulic connection Inches
R 1“
R 1“
R 1“
Water volume
l
1.0
1.6
2.5
Max.
condensate
accumulation
l/h
2.8
2.6
4.3
4.1
6.3
5.7
Weight
kg
31
35
38
Motor vehicle
refrigerant
t
L1
Q
g
Q
s
t
L2
Q
g
Q
s
t
L2
Q
g
Q
s
t
L2
Q
g
Q
s
t
L2
Q
g
Q
s
t
L2
Q
g
Q
s
t
L2
°C
kW kW
°C
kW kW
°C
kW kW
°C
kW kW
°C
kW kW
°C
kW kW
°C
5/10 °C
23
3.5 3.4 19 3.1 3.5 19 5.8 3.5 16 5.1 3.5 16 8.4 3.5 14 7.2 13
13
25
3.9
20 3.5
20 6.5
17 5.8
17 9.4
15 8.0 14
14
26
3.7
21 3.3
21 6.0
18 5.3
17 8.7
15 7.4 14
14
27
4.1
22 3.7
21 6.7
18 6.0
18 9.7
15 8.3 15
15
32
5.4
25 4.9
25 8.9
21 7.9
20 12.5
17 10.8 16
16
7/12 °C
23
2.7
20 2.4
19 4.5
17 4.0
17 6.7
15 5.8 15
15
25
3.2
21 2.9
21 5.2
18 4.7
18 7.7
16 6.6 15
15
26
3.0
22 2.7
21 4.8
19 4.3
18 7.1
16 6.1 16
16
27
3.4
22 3.0
22 5.6
19 4.9
19 8.1
17 7.0 16
16
32
4.7
26 4.2
25 7.7
22 6.8
21 10.8
18 9.4 18
18
9/14 °C
23
2.0
20 1.8
20 3.3
18 2.9
18 5.1
16 4.4 16
16
25
2.4
22 2.2
21 4.0
19 3.6
19 6.1
17 5.2 17
17
26
2.7
22 2.4
22 4.4
20 3.9
19 6.2
17 5.3 17
17
27
2.7
23 2.4
23 4.4
20 3.9
20 6.4
18 5.6 17
17
32
3.9
26 3.5
26 6.4
23 5.7
22 9.2
20 8.0 19
19
11/16 °C
23
1.6
21 1.4
21 2.6
19 2.3
19 3.9
17 3.4 17
17
25
1.9
22 1.7
22 3.1
20 2.7
20 4.4
18 3.9 18
18
26
2.2
23 1.9
23 3.5
21 3.1
20 4.7
18 4.1 18
18
27
2.4
23 2.2
23 3.9
21 3.5
21 5.5
19 4.8 18
18
32
3.3
27 2.9
27 5.2
24 4.7
23 7.6
21 6.6 20
20
13/18 °C
23
1.2
21 1.0
21 1.9
20 1.7
20 2.7
19 2.3 18
18
25
1.6
23 1.4
23 2.6
21 2.3
21 3.5
19 3.0 19
19
26
1.8
23 1.6
23 2.9
22 2.5
21 3.9
20 3.4 19
19
27
2.0
24 1.8
24 3.2
22 2.8
22 4.3
20 3.7 20
20
32
3.1
27 2.7
27 5.0
24 4.4
24 7.2
22 5.8 21
21
PWL 101-103 - Cooling • Performance tables • Technical data
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
1)
LpA 1m, Noise level measurement DIN 45635 - 01 - KL 3
Summary of Contents for PWL 101-H