REMKO MXT 263 Assembly And Operating Instructions Manual Download Page 33

11 

Care and maintenance

Regular care and observation of some basic points

will ensure trouble-free operation and a long

service life.

 DANGER!

Prior to performing any work, ensure the equip-

ment is disconnected from the voltage supply

and secured to prevent accidental switch-on!

Care

n

Ensure the unit is protected against dirt, mould

and other deposits.

n

Only clean the unit using a damp cloth. Do not

use any caustic, abrasive or solvent-based

cleaning products. Do not use a jet of water.

n

Clean the fins on the unit prior to long shut-

down periods.

Maintenance

n

It is recommended that you take out a mainte-

nance contract with an annual service from an

appropriate specialist firm.

 

This enables you to ensure the operational reli-

ability of the plant at all times!

n

For systems which operate year-round (e.g. in

server rooms), the maintenance intervals must

be reduced accordingly.

 NOTICE!

Statutory regulations require an annual leak

test for the cooling cycle dependant on the

refrigerant quantity. Inspection and documenta-

tion of the work performed is to be carried out

by specialist technicians.

Type of task

Checks/maintenance/inspection

Commis-

sioning

Monthly

Half-

yearly

Yearly

General

l

 

 

l

Check voltage and current

l

 

 

l

Check function of compressor/fans

l

 

 

l

Dirt on condenser/evaporator

l

l

 

 

Check the refrigerant volume

l

 

l

 

Check condensate drainage

l

 

l

 

Check insulation

l

 

 

l

Check moving parts

l

 

 

l

Sealing test for cooling cycle

l

 

 

l

1)

1)

 see note

Cleaning the housing

1.

Disconnect the power supply to the unit.

2.

Open the air inlet grill on the front side and

fold it forwards or backwards.

3.

Clean the grill and cover with a soft, damp

cloth.

4.

Close the grill.

5.

Switch the power supply back on.

Air filter for indoor unit

Clean the air filter at intervals of no more than 2

weeks. Reduce this interval if the air is especially

dirty.

 

 

 

 

 

33

Summary of Contents for MXT 263

Page 1: ...Assembly and operating instructions Read the instructions prior to performing any task REMKO MXT MXT 263 MXT 353 MXT 523 Inverter compact wall chest in multisplit design 0136 2016 06 Edition 1 en_GB...

Page 2: ...g inal Read these operating instructions carefully before commis sioning using this device These instructions are an integral part of the system and must always be kept near or on the device Subject t...

Page 3: ...2 Unit dimensions 8 3 Design and function 9 3 1 Unit description 9 4 Operation 10 4 1 General notes 10 4 2 Display on indoor unit 11 4 3 Manual air distribution 12 4 4 Keys on the remote control 14 5...

Page 4: ...ay be fatal or cause serious injury WARNING This combination of symbol and signal word warns of a potentially hazardous situation which if not avoided may be fatal or cause serious injury CAUTION This...

Page 5: ...ctures walls or floors n Mobile units must be set up securely on suit able surfaces and in an upright position Sta tionary units must be permanently installed for operation n The units and components...

Page 6: ...ion and recycling Disposal of packaging All products are packed for transport in environ mentally friendly materials Make a valuable contri bution to reducing waste and sustaining raw mate rials Only...

Page 7: ...per level m h 450 580 680 360 470 550 520 650 740 Sound pressure level per speed setting 3 dB A 35 40 45 35 41 47 39 44 48 Sound power level max dB A 56 58 59 Power supply V Ph Hz 230 1 50 Enclosure c...

Page 8: ...pipe length 2 Air inlet temp TK 20 C outside temperature TK 7 C FK 6 C max air flow volume 5 m pipe length 3 Distance 1m free field 4 Contains greenhouse gas according to Kyoto protocol GWP 2088 2 2...

Page 9: ...porator evapo rator fan controller and condensate tray The indoor unit can be combined with REMKO outdoor units from the MVT 602 DC 1402 DC range that provide sufficient combination options The outdoo...

Page 10: ...control is pointed at the receiver and no objects are obstructing the transmission path Two AAA batteries must be inserted into the remote control in preparation To do so remove the flap from the bat...

Page 11: ...remote control for this The indoor units are ready to be plugged in for connection The mating connector on the indoor unit can be found below the electrical connection Fig 5 The plug is colour coded...

Page 12: ...8 2 The switch to select the blow out direction can be found below the LED s s Fig 9 3 If the switch is set to the symbol A s Fig 9 the indoor unit automatically determines the blow out side dependin...

Page 13: ...tom side when the setpoint is nearly reached to optimally distribute the warm air When the unit is started or when the room temperature is low Blow out direction The unit only blows out from the top t...

Page 14: ...ed by pressing the MODE FAN Speed or ON OFF keys 5 FRESH key Press this key to activate deactivate the ion gener ator air freshener 6 TURBO key Activation of the turbo function makes it possible to re...

Page 15: ...his mode is automati cally deactivated 14 LED key This activates deactivates the display on the indoor unit Indicators on the LCD 2 1 4 3 6 9 8 10 5 7 11 13 12 Fig 11 Indicators on the LCD 1 Mode disp...

Page 16: ...in increments of 1 C 3 Press the ON OFF key to switch the air conditioning unit on 1 3 2 Fig 12 Auto mode In automatic mode the cooling unit automati cally selects among cooling recirculation and hea...

Page 17: ...time and the TIMER OFF key to set the Auto off time for the unit Setting the Auto on time 1 Press the TIMER ON key The remote con trol shows TIMER ON the last Auto on time setting and the symbol H ap...

Page 18: ...llowing settings 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 5 5 6 0 6 5 7 0 7 5 8 0 8 5 9 0 9 5 10 11 12 13 14 15 16 17 18 19 20 21 22 23 and 24 Example TIMER function settings TIMER ON Auto on mode Exam...

Page 19: ...function is acti vated On Set time Stop Start 2 hours later after setting 10 hours later after setting Fig 18 TIMER OFF TIMER ON example TIMER ON TIMER OFF Off Start Stop Example You want the air cond...

Page 20: ...pping company n Lift the unit on the corners and not on the refrigerant or condensate drainage connec tions n The refrigerant piping injection and suction pipe valves and connections must be insu late...

Page 21: ...n should only be performed by authorised specialists Unit installation The unit is fixed using two retaining frames observing the air discharge sides 1 Mark the mounting points on the structurally per...

Page 22: ...m on the indoor unit during cooling Below the evaporator is a collection tray which must be connected to a drain n The condensate drainage line should have an incline of min 2 This is the responsibili...

Page 23: ...rminals NOTICE The electrical connection for the units must be made at a separate feedpoint with a residual current device in accordance with local regula tions and should be laid out by an electricia...

Page 24: ...DC 230V 1 50 Hz L A N A S A L N L B N B S B L C N C S C L D N D S D L N S L N S L N S L N S A 1 B1 B2 B3 B4 2 2 Fig 27 Electrical wiring diagram A Outdoor unit MVT 602 DC 1402 DC B Indoor units MXT 2...

Page 25: ...L N PE L N PE 1 2 N S 1 S L N WH BK PE PE A B C 1 2 3 L 1 L 1 2 N Fig 28 Electrical wiring diagram A Outdoor unit B Indoor unit C Condensate pump KP 6 KP 8 1 Power supply 2 Condensate pump supply 3 Co...

Page 26: ...perature SW 2 ON 1 2 MXT 263 SW 102 ON 1 2 6 C ON 1 2 MXT 353 ON 1 2 4 C ON 1 2 MXT 523 ON 1 2 2 C ON 1 2 0 C Factory setting MO MU Automatic restart after power failure Switch Switch setting Fan spee...

Page 27: ...J2 ON 1 SW1 OFF ON XT1 L N S 3 4 2 7 5 6 1 A B C Fig 29 Electrical drawings MXT 263 A Control board B Auxiliary circuit board C Display circuit board 1 Temperature probe evaporator 2 Temperature prob...

Page 28: ...e Gn Ge Gn ON 1 SW1 OFF ON XT1 L N S Fig 30 Electrical drawings MXT 353 523 A Control board B Auxiliary circuit board C Display circuit board 1 Temperature probe evaporator 2 Temperature probe indoor...

Page 29: ...Temperature setting Fan speeds and switching to recirculation or dehumidification mode 5 Check the correct function of the condensate drainage line by pouring distilled water into the condensate tray...

Page 30: ...or unit working correctly Observe temperature ranges of indoor unit and outdoor unit Electrical surges caused by thunderstorms Have there been light ning strikes in the area recently Switch off the ma...

Page 31: ...ction container Faulty external conden sate pump or float Is the collection tray full of water and the pump not running Call out a specialist to replace the pump Condensate has not drained away and ha...

Page 32: ...tch triggered optional OFF 8 Current consumption is too high ON 1 Outdoor unit air inlet temperature probe faulty ON 2 Outdoor unit condenser temperature probe faulty ON 3 Outdoor unit hot gas line co...

Page 33: ...rooms the maintenance intervals must be reduced accordingly NOTICE Statutory regulations require an annual leak test for the cooling cycle dependant on the refrigerant quantity Inspection and document...

Page 34: ...is used let the filter dry out properly in the air before fitting it back into the unit 7 Carefully insert the filter Ensure that it locates correctly 8 Close the front side as described above in reve...

Page 35: ...Exploded view of the unit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Fig 34 Exploded view of the unit MXT 263 523 We reserve the right to modify the dimensions and design as...

Page 36: ...peller 5 DC fan motor 6 Fan motor bracket 7 Fan motor mounting plate 8 Front cover 9 Pollen filter 10 Air filter 11 Housing front 12 Evaporator 13 Temperature probe evaporator 14 Air line system evapo...

Page 37: ...the electrical power supply to the unit 4 Check the unit for visible signs of damage and clean it as described in the Care and maintenance chapter Permanent shutdown Ensure that units and components a...

Page 38: ...nance 33 Malfunction indicated by flashing code 32 Malfunctions Checks 30 Possible causes 30 Remedial measures 30 Manual air distribution 12 Manual mode 10 Minimum clearances 21 O Ordering spare parts...

Page 39: ......

Page 40: ...t as advisers to our customers in air conditioning and heating technology SFlbCustomer Service Our equipment operates precisely and reliably However in the event of a fault REMKO customer service is q...

Reviews: