REMKO MVT 1050 DC Operation,Technology,Spare Parts Download Page 20

Before commissioning 

After the tightness check has 
been successfully completed, 
connect the vacuum pump via the 
pressure gauge station to the valve 
connections on the outdoor unit 
(see chapter "Tightness check") 
and create a vacuum.  
 

Perform the following checks 
prior to commissioning the 
unit for the first time and after 
any interventions affecting the 
refrigerant circuit. Record the 
results in the commissioning 
report: 

■ 

Check of all refrigerant pipes 
and valves with leak detection 
spray or soapy water for leaks 
and for inadvertent mix up of 
suction and injection pipe, with 
the unit at a standstill.

■ 

Check of all refrigerant pipes 
and insulation for damage.

■ 

Check of all electrical 
connections between indoor 
unit and outdoor unit for 
correct polarity.

■ 

Check that all fastenings, 
mountings etc. are firm and at 
the correct level.

Commissioning 

Commissioning should only be 
performed and documented by 
specially trained personnel. 

Observe the manuals for the 
indoor unit and outdoor unit 
when commissioning the 
entire system.

      NOTE

The system can be commissioned 

once all the components have 

been connected and checked. 

A functional check should be 

performed to verify its correct 

function and identify any unusual 

operational behaviour prior to 

handing it over to the operator.  

This check is dependent on the 

installed indoor unit.  

The procedures are specified in the 

manual for the indoor unit being 

commissioned.

Add refrigerant

The unit contains a basic quantity 
of refrigerant.  
In addition, an additional amount 
of refrigerant must be added for 
refrigerant pipe lengths exceeding 
5 meters per circuit. Refer to the 
following chart:

Note that the employed 
refrigerant is always filled in 
liquid form!

      CAUTION

      NOTE

Check the overheating to 
determine the refrigerant fill 
quantity.

Wear protective clothing when 
handling refrigerant.

      CAUTION

MVT 

600 DC - 1050 DC

Basic pipe length

Additional  

filling quantity

Up to and incl.  

5 m

0 g/m

0 g/m

5 m to max. 15 m 

per circuit

30 g/m

30 g/m

Condensate connection 
and safe drainage

Condensate connection

If the temperature falls below the 
dew point, condensation will form 
on the finned condenser during 

heating mode

.

Below the register is a collection 
tray, which must be connected to 
a drain.

■ 

The condensate line should 
have a fall of min. 2 %. 
This is the responsibility of the 

customer.   
If necessary, fit vapour diffusion 
proof insulation.

■ 

When operating the unit at 
outdoor temperatures below 4 °C, 
make sure to route the condensate 
line so that freezing is prevented. 
The lower part of the housing 
must also be kept frost free by the 
user, in order to ensure permanent 
draining of the condensate.
If necessary, fit a pipe heater.

■ 

After installation is complete, 
check for unobstructed 
condensation run off and 
ensure that a permanent seal is 
provided.

Safe drainage in the event of  
leakage 

Local regulations or environmental 
laws, for example the German Water 
Resource Act (WHG), can require 
suitable precautions to protect 
against uncontrolled drainage in 
case of leakage to provide for safe 
disposal of escaping air conditioning 
fluid or hazardous media.

REMKO MVT

20

Summary of Contents for MVT 1050 DC

Page 1: ...Edition GB C01 REMKO MVT MVT 600 DC MVT 900 DC MVT 950 DC MVT 1050 DC Inverter multisplit outdoor units Operation Technology Spare parts...

Page 2: ......

Page 3: ...ycling 4 Warranty 4 Intended use 5 Transport and packaging 5 Description of the equipment 5 6 Combinations 7 8 Operation 9 Shutdown 9 Care and maintenance 9 Troubleshooting and customer service 10 11...

Page 4: ...ould only be set up and installed by qualified personnel The setup connection and operation of the unit and its components must be in accordance with the operating conditions stipulated in this manual...

Page 5: ...n valves and a liquefier fan The outdoor unit is combinable with REMKO indoor units of series MXW in accordance with the cooling output see chapter Combinations The outdoor unit refrigerant circuit is...

Page 6: ...System design The connection between indoor units A B C D and outdoor units connection circuit A B C D of the outdoor unit is achieved with refrigerant pipes and a control line Injection pipe Suction...

Page 7: ...s Combination 13 Combination 14 Combination 15 Combination 16 Combination 17 Combination 18 Combination 19 Combination 20 Combination 21 Combination 22 MXW MXD MXT 200 201260 261350 351520 521 One ind...

Page 8: ...1 MXW MXD MXT 200 260 350 520 One indoor unit Combination 1 Combination 2 Combination 3 Combination 4 Two indoor units Combination 5 Combination 6 Combination 7 Combination 8 Combination 9 Combination...

Page 9: ...tenance It is recommended that maintenance contract with annual maintenance interval with an appropriate specialist company This ensures the operational reliability of your equipment TIP The compresso...

Page 10: ...on the outdoor unit running Fan winter controller should be checked Leaking refrigerant circuit Are there signs of severe frost on the large stop valve Repair by a specialist Fault Possible cause Chec...

Page 11: ...between outdoor and indoor unit Contact specialist dealer P0 Excessive temperature Klixon compressor Check refrigerant Check the resistance of the compressor sensor normal 0 P1 High pressure sensor ha...

Page 12: ...basic length of the refrigerant pipe exceeds 5 metres For the quantity of additional refrigerant refer to chapter Add refrigerant Only use the union nuts for the refrigerant pipes included in the del...

Page 13: ...d by the measures Wind If the unit is being installed in windy areas ensure the air discharges in the prevailing wind direction If this is not the case it may be necessary to install a windbreak provi...

Page 14: ...s and potential cracking are the consequences Minimum clearances Oil return measures Outdoor unit Oil pump bend in suction pipe to outdoor unit 1 x every 2 5 metres of rising pipe Radius min 50 mm max...

Page 15: ...mentary information for Installation When combining the outdoor unit with indoor unit MXW 350 the connection of the refrigerant pipes differs In this case install the expansion fittings to the outdoor...

Page 16: ...completely extracted from the system the valves on the pressure gauge station are closed and the valves on the outdoor unit are opened as described in the chapter on Commissioning All electrical inst...

Page 17: ...Suction pipe A A B B C C Control board Control board Trans former Trans former Trans former Trans former Sensor Sensor Sensor suction pipe Sensor suction pipe Heating Heating Fan motor Fan motor Power...

Page 18: ...ve A B C D Compressor Line filter C B A D Indoor units Heating Fan motor Power output 230V 1 50Hz Inverter valve Power board Sensor Suction pipe High pressure switch Low pressure switch Sensor MVT 105...

Page 19: ...ns cable 230 V 1 50 Hz L1 N PE N L N L1 MVT 900 DC Indoor unit Circuit A Plug Outdoor unit Circuit A Indoor unit Circuit B Indoor unit Circuit C Plug Outdoor unit Circuit B Plug Outdoor unit Circuit C...

Page 20: ...a basic quantity of refrigerant In addition an additional amount of refrigerant must be added for refrigerant pipe lengths exceeding 5 meters per circuit Refer to the following chart Note that the emp...

Page 21: ...pen the stop valves by turning them anti clockwise using a spanner If leaks were found draw off the refrigerant and rework the defective connection It is imperative that the vacuum creation and drying...

Page 22: ...sensor liquefier Temperature sensor air inlet Liquefier Temperature sensor hot gas Power consumption compressor Degree of opening for electronic Expansion valve no 4 Degree of opening for electronic e...

Page 23: ...45 C 12 45 50 C 13 50 55 C 14 55 60 C 15 60 65 C 16 65 70 C Display Temperature 15 7 5 C 20 5 0 C 25 2 5 C 30 0 C 35 2 5 C 40 5 0 C 45 7 5 C 50 10 0 C 55 12 5 C 60 15 0 C 65 17 5 C 70 20 0 C 75 22 5...

Page 24: ...ensions and constructional design as part of the ongoing technical development process Unit dimensions All values in mm MVT 600 DC MVT 900 DC MVT 950 DC 560 335 705 315 845 595 335 860 305 900 MVT 105...

Page 25: ...r compressor 111103 111033 111053 9 Condenser liquefier fan 111104 111034 111109 111081 10 Stop valve suction pipe 111035 111036 111055 111082 11 Stop valve injection pipe 111037 111038 111056 111083...

Page 26: ...0 10 80 13 50 Electr starting current max A 35 35 40 67 Electrical power consumption max kW 3 10 4 00 4 80 6 30 Compressor model Rotary piston Twin pistons Flow regulator Electronic expansion valves R...

Page 27: ...VT 1050 DC Kombination mit 4 x MXW 260 0 00 2 00 4 00 6 00 8 00 10 00 12 00 14 00 16 00 18 00 24 12 7 4 0 5 7 15 Au entemperatur C Heizleistung kW Reihe MVT 1050 DC Characteristic curves heat Heating...

Page 28: ...mentation Inverter multisplit outdoor units Series Designation REMKO MVT 600 DC MVT 900 DC MVT 950 DC MVT 1050 DC Series Class Number 783 784 785 1042 Applicable regulations MA RL 2006 42 EC Machine d...

Page 29: ...Notizen...

Page 30: ...REMKO MVT 30...

Page 31: ......

Page 32: ...salesmen above all they must advise our clients in the areas of air conditioning and heating technology Customer Service Our equipment is precise and reliable However should a fault should occur REMKO...

Reviews: