![REMKO KP8 Instruction Manual Download Page 7](http://html1.mh-extra.com/html/remko/kp8/kp8_instruction-manual_1439018007.webp)
7
Assembly
Assembling the condensate pump
for the units RVT, RXW, MXW, ATY, MVW
1. Connect condensate hose with an inner
diameter of 15 mm to the condensate
drain of the air conditioner, shorten
if necessary.
2 Slide the approx. 10 cm long vent
hose (Fig. 1, above) onto the upper
connection of the reservoirs.
3. Place the reservoir so that the end of
the vent hose is at least 2 cm above
the condensate tray and that an axial
rotation of 15° is not exceeded.
4. Fix the reservoir with the retaining
plate by pushing the reservoir
onto the retaining plate and gluing
it to a smooth and clean surface.
5. Slide the approx. 2 m long
condensate hose (Fig. 1, above)
onto one of the lower connections
of the reservoir. Pay attention
to the inclination angle of the reservoir!
6. Place the condensate pump in a cable
duct or in the intermediate ceiling. Slide
the condensate hose onto the plastic
connector on the condensate pump
(Fig. 2).
Observe the flow direction of the pump.
Water inlet: on the brass socket Water
outlet: on the plastic hose.
7.
Ensure that the condensate pump
is adequately ventilated. The pump
must be not insulated.
1 Installing the reservoir
15°
15°
15
°
8. Drain the pressure pipe of the pump
into the drain (Fig. 3).
Vent hose
Condensate hose