KP8 CONDENSATE PUMP

Summary of Contents for KP8

Page 1: ...REMKO Edition GB I07 KP8 CONDENSATE PUMP ...

Page 2: ......

Page 3: ...the unit and must always be kept in the vicinity of the installation location or on the unit itself Subject to modifications no liability accepted for errors or misprints Safety notes 4 Environmental protection and recycling 5 Guarantee 5 Description 5 Intended use 5 Scope of delivery 6 Technical data 6 Assembly 7 8 Electrical wiring 9 Electrical wiring diagram 9 Care and maintenance 10 ...

Page 4: ...tions Units and components may not be operated in areas where there is an increased risk of damage Observe the minimum clearances Safety notes The electrical power supply is to be adapted to the requirements of the units The operational safety of the units and components is only assured if they are fully assembled and used as intended Safety devices may not be modified or bypassed Do not operate u...

Page 5: ... waste and sustaining raw materials Only dispose of packaging at approved collection points Disposal of components The manufacturing process for the units is subject to continuous quality control Only high grade materials are processed the majority of which are recyclable Help protect the environment by only disposing of the components in accordance with local regulations and in an environmentally...

Page 6: ...w rate at delivery head 2m horizontal pressure pipe 10m 8 l h Max flow rate at delivery head 4m horizontal pressure pipe 20m 5 l h Max flow rate at delivery head 10 m 1 l h Max condensate temperature 35 C Max environmental temperature 50 C Suction hose diameter 5 mm Pressure hose diameter 4 6 mm Return flow valve on pressure side Available Power supply 230V 1 50Hz Max rated current consumption 0 5...

Page 7: ...ervoir onto the retaining plate and gluing it to a smooth and clean surface 5 Slide the approx 2 m long condensate hose Fig 1 above onto one of the lower connections of the reservoir Pay attention to the inclination angle of the reservoir 6 Place the condensate pump in a cable duct or in the intermediate ceiling Slide the condensate hose onto the plastic connector on the condensate pump Fig 2 Obse...

Page 8: ...TE Make sure that the installation is frost free NOTE 3 Installing the condensate pump 2 Installing the pump Cable tie 4 Installing the condensate pump No difference in height 5 Installing the float Magnetic ring on top The pressure pipe must not be laid with an immediate incline in order to prevent the pressure hose emptying NOTE ...

Page 9: ...column 3 NO Normally open contact violet Connection of malfunction signalling device Indoor unit Connection to NC white Connection to C black RXW Control conductor contact 3 on IT Control conductor contact 3 on AT RVT Control conductor contact S on IT Control conductor contact S on AT MXW Control conductor contact S on IT Control conductor contact S on AT ML DC Control conductor contact S on IT Co...

Page 10: ...dirt Type of task Commissioning Half yearly General X X Check voltage and current X Check condensate drain ventilation X X Clean reservoir see note X X Check insulation if necessary X Check malfunction contact X X Only neutral detergents may be used for cleaning NOTE The float must always be mounted with the magnetic ring upwards after cleaning See page 8 fig 5 NOTE ...

Page 11: ...11 ...

Page 12: ...We reserve the right to make technical changes and provide no warranty as to the accuracy of this data REMKO GmbH Co KG Air conditioning and heating technology Im Seelenkamp 12 D 32791 Lage Postfach 1827 D 32777 Lage Telephone 49 5232 606 0 Fax 49 5232 606 260 E mail info remko de Website www remko de ...